    POWER

    INTERFACE

    UNIT

    (PIU)

  • 7/29/2019 Piu Basics

    2/23

    PIU : INTRODUCTION

    The system features:

    Static Mains Regulator.

    Built- in isolationtransformer.

    Micro-controller based

    AMF Panel.

    Security & Safety Alarm

    System.

    Lightning & SurgeProtection.

    AC Distribution.

    SMPS Battery Charger for

    DG battery.

    High/Low Voltage

    Disconnection. Modular Arrangement.

    Integrated System for

    easy installation &

    operation.

    User Friendly Interface

    NMS.

  • 7/29/2019 Piu Basics

    3/23

    S.NO PARAMETERS SPECIFIED

    1Lightning Protection 10/350_s, 100kA @let through voltage

    240V

    200V

    Response time < 10ms

    4 N Earth Protection Over voltage with complete true isolation

    5 Manual Error Protection Imported Machine Interlock accessories

    6 AMF Panel Micro controller based true RMSequipment, GEN ON-OFF Control & Alarms

    7 Line Conditioner Static Line Conditioner withIsolation Input two phase - 240 485V(Extended 265 470V)

    Isolation Output single phase - 200 240V

    8 Distribution for external load As per customer requirement

    9 Dimension 1800mm x 600mm x 400mm

    10 Weight 300Kg.

    A Sample Specs Sheet

  • 7/29/2019 Piu Basics

    4/23

    Lightening

    Protection

    Surge

    Protection

    Auto Phase

    Selector

    Line

    Conditioning

    Unit

    AC

    DistributionPanel

    Input

    MCB

    To SMPS

    To Air Conditioner

    To Power Points

    To Lights,

    Fans, etc

    To Aviation

    Lamp

    L1L2

    L3

    N

    P1

    P2

    P

    N

    Block Diagram of PIU

  • 7/29/2019 Piu Basics

    5/23

    Lighting and surge protector

    PIU of acme telepower isincorporated with lightning

    protection of 10/ 350 micro

    sec, 100 KA @ let through

    voltage < 700 ; where as for

    surge protection of about

    8/20 micro sec ,15 KA .

  • 7/29/2019 Piu Basics

    6/23

    Auto phase selector

    It will select another two healthy

    phase out of three phases.Healthy phase - Voltage across

    phases between 240V to 480V

  • 7/29/2019 Piu Basics

    7/23

    Central processing unit

    Brain of PIU,

    responsible for

    performing various

    functions like

    measuring, display,adjustment and

    interface, alarm,

    automation and

    rectification and

    coordination between

    various internal aswell external

    parameters.

  • 7/29/2019 Piu Basics

    8/23

    Line Conditioner Unit

    Equipment operates with

    microprocessor-based

    controller to provide

    correction of mains even inmicro seconds. System

    supports to operate on

    phase-to-phase basis to get

    rid of neutral problem, as it

    is very common. Mains

    utilization even at extremelow voltage 140V for air-

    condition operation

  • 7/29/2019 Piu Basics

    9/23

    Alarm Interface

    Extension of alarms from

    cpu card.

    ALARM S AND MEASURES TO

    BE TAKEN

  • 7/29/2019 Piu Basics

    10/23

    AC Distribution Panel

    AC Distribution panel is

    provided for load termination.

    SMPS, Air conditioners,Power Point and Tube Light

    for Aviation Lamp etc are

    being connected to various

    points. Surge arresters for

    class I protection are

    provided on the inputinterface panel before the

    output gets divided to MCBs

  • 7/29/2019 Piu Basics

    11/23

    Automation Layout ( New)

  • 7/29/2019 Piu Basics

    12/23

  • 7/29/2019 Piu Basics

    13/23

    Alarm

    Extension

    from PIU,

    Color

    Codes foreach

  • 7/29/2019 Piu Basics

    14/23

    Alarm From PIU

    SN Type of Alarm Safety Status in existing PIU Alarm Cable Pair Details

    1 Mains fail Alarm Available Brown(Com),Red(NO)

    2 Door open (FROM SENSOR) Alarm Available Brown(Com),Brown(NO)

    3 Smoke & fire Safety+Alarm Available Black(com),Blue(NO)

    4 Room Temperature high Alarm Available Brown(NC), Grey(NO),White(com)

    5 Low fuel level (at 50% fuel) Alarm Available Black(com),Orange(NO)

    6 Load on DG Alarm Available Grey(com),Red(NO)

    7 DG on Alarm Available Red(NO),orange(NC),Green(Com)

    8 DG fail to start Alarm Available Green(NC),Red(NO),White(Com)

    9 DG fail to Stop Alarm Available Blue(NC),ORANGE(NO) ,White(COM)

    10 DG Common fault

    Alarm+ Safery( incase of

    Alternator fault and

    HCT/LLOP) Available Blue(Com),White(NO),Red(NC)

    10.a a. LLOP Safety+Alarm Available Availble in common fault pair

    10.b c. Alt.fault

    LED indication + Alarm as

    DG Common fault Available Availble in common fault pair

    10.c d. HCT/HWT

    LED indication + Alarm as

    DG Common fault Available Availble in common fault pair

    10.d e. V belt

    Safety+ Alarm as DG

    Common fault( can be

    connected as HCT Port) Available Availble in common fault pair

    10.e f. LWL

    Safety+ Alarm as DGCommon fault( can be

    connected as HCT Port) Available Availble in common fault pair

  • 7/29/2019 Piu Basics

    15/23

    BHARTI 11:30:35T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    MAINS OK

    BHARTI 12 JAN,2004T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    OP1:230V OP2:000V

    +yes

    -- NONO

    menu

    LOG

    Scroll

    888888

    888888

    DISPLAY

    888888

    RESET( +)

    (-)

    MENU

    NOT USED

    SCROLL

    POWER ON

    CPU

    MAINS OK

    MAINS FAIL

    ROOM TEMP HIGH

    SMOKE / FIRE

    EMERGENCY

    OVER LOAD

    LCU FAIL

    L1-L2

    I

    MAINS VOLTAGE

    O/P CURRENT

    FREQUENCY

    DG

    MAINS

    DG FAIL TO START

    DG FAIL TO STOP

    ALTERNATOR FAULT

    LLOPDG FUEL LOW

    ENGINE TEMP HIGH

    NA

    DG BATTERY LOW

    CENTRAL SUPERVISIORY UNIT

  • 7/29/2019 Piu Basics

    16/23

    888888

    888888

    888888

    MAINS VOLTAGE

    O/P CURRENT

    FREQUENCY

    CENTRAL SUPERVISIORY UNIT

    POWER ON

    CPU

    MAINS OK

    MAINS FAILROOM TEMP HIGH

    SMOKE / FIRE

    EMERGENCY

    OVER LOAD

    LCU FAIL

    DG FAIL TO START

    DG FAIL TO STOP

    ALTER. FAULT

    LLOPDG FUEL LOW

    ENGINE TEMP

    HIGH

    OVER SPPED

    DG BATTERY LOW

    L1-L2

    I

    DG

    MAINS

    +yes

    -- NONO

    menu

    LOG

    Scroll

    Emergency OFF DisableON/OFF TIMER

    ON TIME 18:30

    OFF TIME 06:30

    HIGH ROOM TEMP. Cut off

    32OC

    DEFAULT FACTORYBHARTI 09:30:30

    T:0000000.5 VGEN:000VTEMP:25.0OC VDC:27.0V

    MAINS OK

    HIGH VOLT CUT OFF

    485V

    LOW VOLT CUT OFF

    240VHIGH VOLT CUT IN

    470V

    LOW VOLT CUT IN

    265V

    DG HIGH VOL CUT OFF

    250V

    DG LOW VOL CUT OFF

    195V

    OVER LOAD

    70A

    DG LOCK

    5 MIN

    DG LONG LOCK

    10 MIN

    TEMP LIMIT FORBATT

    34OC

    P.PBATT MIN VOLTAGE

    23.5V

    PP/ BATT NOR. VOLTAGE

    25.0V

    HIGH ROOM TEMP. CUT IN

    35OC

    FIRST START PULSE

    2 SEC

    SECOND START PULSE

    3 SEC

    THIRD START PULSE

    4 SEC

    DG STOP PULSE

    40 SEC

    DATE/ TIME SET

    11:30:30

    11.07.2004

    HIGH Engine Temp DisableBHARTI 09:30:30

    T:0000000.5 VGEN:000VTEMP:25.0OC VDC:27.0V

    MAINS OK

  • 7/29/2019 Piu Basics

    17/23

    START

    MAINS 240-480IN BEST OF

    2 PHASE

    MAINS OK

    LCU

    OP1

    180-250

    OK

    LCU FAIL

    NOT OK

    NO

    VDC =23.5V

    TEMP 340C

    BATT ON DG SENSE

    OKNOT OK

    CH

    E

    C

    K

    1

    2

    DG IS RUNNING

    DG STOP

    YES

    NOYES

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    START

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    DG SENSE

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    MAINS OK

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    BATT ON

  • 7/29/2019 Piu Basics

    18/23

    DG SENSE

    LLOP NO( PIU)

    LLOP NC(B

    C)HCT NC(PIU)

    DG START

    OK

    DG VOLTAGE

    195-250

    NOT OKOK

    NOT OK

    LLOP NC(PIU)

    LLOP NO (BC)

    DG LOCKFOR 5/10 MIN.

    DG STOP

    OK NOTOK

    DG FAULT

    ALARM

    3 TIMES

    RETRY

    DG FAULT

    WITH LLOP AL.

    AFTER 5/10 MIN

    DG ON

    DG FAULT

    DG FAIL TO

    START

    AFTER 3 RETRY

    DG CHECK

    DG IS RUNNING

    VOLTAGE

    YES

    NO

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    DG SENSE

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    DG FAULT

    BHARTI 09:30:30

    T:0000000.5 VGEN:000VTEMP:25.0OC VDC:27.0V

    DG START

    BHARTI 09:30:30

    T:0000000.5 VGEN:000VTEMP:25.0OC VDC:27.0V

    DG CHECK

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    DG LOCK

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    DG ON

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0O

    C VDC:27.0VDG STOP

    BHARTI 09:30:30T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    DG FAULT

  • 7/29/2019 Piu Basics

    19/23

    DG ON

    LLOP NC ( PIU)

    DG VOLTAGE

    MAINS VOLTAGE5 Hrs TIME

    LLOP NC

    DG VOLTAGEBEYOND 195-250

    MAINS OK

    240-480

    5 Hrs DG

    DG CONT. RUN

    DG STOPDG FAULT

    LLOP ALARM

    DG STOP DG FAULTALTER.FAIL

    DG STOP GOTO 1

    DG STOP GOTO 2

    WAIT MAINS

    & GOTO 1

    WAIT MAINS& GOTO 1

    SITE ON DG

    DG FAIL

    TO STOP ALM

    IF NOT

    1

    2

    DG DISC.

    DG DISC.

    DG DISC

    No load 5 min

    .

    DG DISC.

    DG VOLT=0

    LLOP NO(PIU)

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    DG ON

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    DG STOP

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    DG FAULT

    BHARTI 09:30:30

    T:0000000.5 VGEN:000V

    TEMP:25.0OC VDC:27.0V

    DG DISC

  • 7/29/2019 Piu Basics

    20/23

    Trouble Shooting

  • 7/29/2019 Piu Basics

    21/23

    Trouble Shooting Contines

  • 7/29/2019 Piu Basics

    22/23

    Dos and Donts

  • 7/29/2019 Piu Basics

    23/23

    Thank YouThank You

    ACME Tele Power LtdACME Tele Power Ltd