Instruction ManualInstruction Manual
PL-548
33455480Rev 1.0
Pointek CLS 100Capacitance Liquids/Solids
hank you for purchasing Milltronics� products. We endeavour to design
equipment that is simple to use and reliable in its operation, with the aim
of satisfying our customers' needs.
Milltronics has been designing and manufacturing process equipment since
1954. Our fields of expertise include ultrasonic and capacitance level
measurement, in-line weighing of dry bulk solids and motion sensing.
Milltronics is established world wide through associate offices and
representatives. Our network is continually being refined to provide our
customers with first rate sales information, engineering assistance and after
sales support.
For more details on our products and service, please contact us and we will
provide you with a listing of the offices or representatives nearest you.
T
ABOUT POINTEK CLS 100
Pointek CLS 100 is to be used only in the manner outlined in this instruction manual.
The Pointek CLS 100 capacitance level switch provides 4 to 20 mA output and solid stateswitch contact for detection of high and low process material levels. When the measuredmaterial approaches or contacts the switch’s probe, an increase in capacitance is sensed anda high level alarm can be triggered. If a low level alarm is required then the lack of materialcontact is sensed and this condition triggers the low level alarm.
Pointek CLS 100 Features
✓ NPT, BSPT process connections
✓ Corrosion resistant construction, Kynar® and 316 stainless steel wetted parts✓ Non-polarized, solid-state switch✓ 4 or 20 and 20 or 4 loop alarm output
Pointek CLS 100 Applications
✓ Liquids, slurries, powders, granules, and solids✓ Foods and pharmaceuticals✓ Chemical and petrochemical✓ High pressure and temperature✓ Hazardous areas
PL-548 3
SPECIFICATIONS
Electrical/Instrument
» power: » standard: » 10 - 33 V dc» intrinsically safe: » 10 - 30 V dc
» alarm output: » mA: » 4 / 20 mA loop
» solid state switch: » standard: » 250 V ac / 300 V dc, 100 mA max
» 2 Watt
» intrinsically safe: » 25 V ac / 30 V dc
» repeatability: » 2 mm (0.08")
» mode: » high or low
Mechanical
» construction: » probe / wetted, 316 stainless steel process connection and Kynar® sensor
» body / housing, 316 stainless steel
» process connection, 3/4" NPT or 1" BSPT
» cable/ connection: » 1 m (3.3 ft) of 4 conductor, 22 AWG, shielded, polyester jacket
Environmental
» location: » indoor / outdoor
» altitude: » 2000 m max
» ambient temperature: » -40 to 85 °C (-40 to 185 °F)
» ingress protection: » Type 4X / NEMA 4X / IP65)
» installation category: » II
» pollution degree: » 4
Process
» dielectric constant (εr) » 1.5 min
» temperature » – 40 to 110 °C (–40 to 230 °F)
» pressure (vessel) » 0 absolute to 1000 kPa (10 bar or 146 psi) gauge, nominal
Approvals
» CSA, FM, CENELEC, KEMA, refer to device nameplate
® Kynar is a registered trade mark of ELF Atochem
PL-548 4
INSTALLATION
LOCATION
Installation shall only be performed by qualified personnel and in accordance with local governing regulations.
This product is susceptible to electrostatic shock.Follow proper grounding procedures.
The Pointek CLS 100 is normally mounted into the vessel top (high detection alarm) orthrough the tank wall at the detection level (high or low detection alarm).
verticalangle horizontal
PL-548 5
OUTLINE AND DIMENSION
∇ black » dust ignition proof and general purpose blue » intrinsically safe
cablerelief
green LED/ power
45 mm(11.5")
yellow LED/ sensor status
trimpot /sensitivity
ground post
red LED/ outputstatus
trimpot cap
cable Ø5 mm (0.2")∇
120 mm (4.7")
processconnection
36 mm(1.4")
PL-548 6
MOUNTING
DO’S AND DONT’S
STANDPIPES
MULTIPLE UNITS
> 100 mm (4") Ø
< 50 mm (2")
100 mm(4") min
100 mm(4") min
Sensors must be 100 mm apart. Mount diagonally if there isnot enough vertical space.
100 mm(4") min
PL-548 7
DO’S and DONT’S (cont’d)
WALL RESTRICTION
50 mm(2")min
50 mm(2")min
PL-548 8
DO’S and DONT’S (cont’d)
PROCESS CONCERNS
protect probe from falling material
consider material angle of repose
avoid areas where material build up occurs
keep out of path of falling material
PL-548 9
CLS 100 TERMINATION
solid state switch, normally open unpowered
V supply / mA loop modulator (4 or 20 mA)
ALARM OUTPUT STATUS
Definitions
Alarm Conditions as defined below can be detected in a fail-safe or non fail-safe mode.
Fail Safe » The sensor connection arrangement of the CLS 100 is fail-safe if the output status is in, or switches to the alarm status when power fails, which is an open contact state.
High Alarm » Condition in which the material has reached a maximum level for the users process (probe covered).
Low Alarm » Condition in which the material has reached a minimum level for the users process (probe uncovered).
Alarm Status CoveredYellow LED ON
UncoveredYellow LED OFF
Power Connection
High (fail safe) Red LED OFF4mA
SSS = open
Red LED ON20 mA
SSS = closed
Black wire + V
High (non fail safe) Red LED ON20 mA
SSS = closed
Red LED OFF4mA
SSS = open
Red wire + V
Low (fail safe) Red LED ON20 mA
SSS = closed
Red LED OFF4 mA
SSS = open
Red wire + V
Low (non fail safe) Red LED OFF4mA
SSS = open
Red LED ON20mA
SSS = closed
Black wire + V
PL-548 10
POWER / ALARM MODE
Standard Version - Non Intrisically Safe
LOW Alarm
HIGH Alarm
4 / 20 mA LOOP ALARM
SOLID STATE SWITCH
STANDARD VERSION - Non Intrisically Safe
When driving an external relay with either the solid state switch outputs using dc Power, a protection diode must be connectedin the correct polarity to prevent
possible switch damage due to inductive spikes generated by the relay coil.
+10 - 33 V dc
–
polarity as required fordesired operation
V supply10 - 33 V dc
See Power / Alarm Mode for polarity considerations.
Rmax = V supply – 10 V 20 mA
Rmax
–10 - 33 V dc
+
polarity as required fordesired operation
solid state switch,250 V ac / 300 V dc,100 mA maxsee CLS Termination
10 - 33 V dc
see Power / Alarm Mode for Vsupply polarity configuration
PL-548 11
PL-548 12
PL-548 13
OPERATION
SET UP
Set up can be done in the field with the Pointek CLS mounted into process, or in the shop prior to mounting.
START UP
After the CLS is properly mounted and wired, apply power to the unit. The green LED lights toindicate the unit is powered and operational.
INDICATORS
The Pointek CLS uses three LEDs for visual indication of the following:
yellow, sensor status: when the trim pot is properly set, this LED is on when the sensor is in contact with the process material (material capacitance is greater than the setpoint). It is offwhen the sensor is out of contact with the process material (material capacitance is less than the setpoint).
red, output status: this LED is an indication of the mA loop alarm and solidstate switch contact status. Refer to CLS Termination \ Alarm Output Status.
green, power: this LED is on when the Pointek CLS is properly powered.
Proceed with the set up of the alarm output.
ALARM OUTPUT
SETPOINT ADJUSTMENT
In order to assist you in properly adjusting the alarm setpoint for reliable and accuratedetection of the process material, we have categorized the materials and applications intothree cases. Follow the setup procedure associated to the case which covers your application.
Case 1: this is the general case encountered in most applications, characterized by the following:
- dry solids- low viscosity liquids
Case 2: demand applications, characterized by the following:- hygroscopic / wet solids - high viscosity and high conductivity liquids
Case 3: interface detection: - e.g. liquid A / liquid B, foam / liquid
PL-548 14
Case 1
Preamble: - insure that the green LED is ‘on ’- if the yellow LED is ’on’, turn the trimpot ccw (counterclockwise) until the yellow LED goes ‘off’, otherwise go to step 1 below.
1. With sensor uncovered and a minimum 100 mm free space all around, turn the trimpot cw until the yellow LED just goes ‘on ’.
2. Turn the trimpot ccw until the yellow LED just goes ‘off ’.
Case 2
Preamble: - insure that the green LED is ‘on ’- turn the trimpot ccw (counterclockwise), until the yellow LED just goes ‘off’.
1. Adjust the material level of the process so that the sensor is immersed, the yellow LED should be ‘on ’.
2. Adjust the material level of the process so that the sensor is uncovered, but retainssignificant (as much as possible) build up of material on the sensor.
3. Adjust the trimpot ccw until the yellow LED goes ‘off ’. To get the true feel of the correct position, it is wise to adjust the trimpot cw then ccw a couple of times to insure that the yellow LED is just ‘off ’.
Case 3
Preamble: - insure that the green LED is ‘on ’- turn the trimpot ccw (counterclockwise), until the yellow LED just goes ‘off’.
1. Immerse the sensor in the material that has the lowest dielectric constant.The yellow LED should be ‘on ’.
2. Adjust the trimpot ccw until the yellow LED goes ‘off ’.
3. Immerse the sensor in the material that has the highest dielectric constant, the yellow LED should come ‘on ’.
After completing the set up, replace the trimpot cap. The unit is now in service, providing level detection of your process.
20 turn trimpot
PL-548 15
TROUBLESHOOTING
MAINTENANCE
The Pointek CLS requires no maintenance or cleaning.
■
Symptom Observation Action
No switching action whensensor covered / uncovered
green LED OFF check power connectionsand voltage
green LED ONyellow LED continuously ON
Reduce the sensitivity byturning the trimpot CCW
green LED ONyellow LED continuously OFF
Increase the sensitivity byturning the trimpot CW
No switching action whensensor covered /
uncovered previous checks not effective
green LED is ONyellow LED doesn’t change
state as in 2 & 3 above
Possible failed sensor -check with supplier
PL-548 16