Powerware 9125 Installation Guide for IBM Applications Guide d’installation pour applications IBM Installationsanleitung fr IBM-Anwendungen

  • Published on
    04-May-2018

  • View
    214

  • Download
    2

Embed Size (px)

Transcript

  • Powerware 9125Installation Guide for IBM Applications

    Guide dinstallation pour applications IBM

    Installationsanleitung fr IBM-Anwendungen

    Guida allinstallazione per applicazioni IBM

    Gua de instalacin para aplicaciones IBM

    www.powerware.com

  • Powerware is a registered trademark and X-Slot is a trademark of Powerware Corporation.Powerware est une marque dpose et X-Slot est une marque commerciale de Powerware Corporation.Powerware ist ein eingetragenes Warenzeichen und X-Slot ist ein Warenzeichen der Powerware Corporation.Powerware un marchio di fabbrica depositato e X-Slot un marchio di fabbrica di Powerware Corporation.Powerware es una marca comercial registrada y X-Slot es una marca comerical de Powerware Corporation.

    Copyright 2000 Powerware Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may bereproduced in any way without the express written approval of Powerware Corporation.Copyright 2000 Powerware Corporation, Raleigh, NC, Etats-Unis. Tous droits rservs. Aucune partie de ce documentne peut tre reproduite dune quelconque manire sans laccord crit explicite de Powerware Corporation.Copyright 2000 Powerware Corporation, Raleigh, NC, USA. Alle Rechte vorbehalten. Kein Teil dieser Druckschrift darfohne ausdrckliche schriftliche Genehmigung von Powerware Corporation auf irgendeine Weise vervielfltigt werden.Copyright 2000 Powerware Corporation, Raleigh, NC, USA. Tutti i diritti riservati. Nessuna parte del presentedocumento pu essere riprodotta in alcun modo senza lesplicita autorizzazione scritta di Powerware Corporation.Copyright 2000 Powerware Corporation, Raleigh, NC, EE.UU. Todos los derechos reservados. Ninguna parte de estedocumento se puede reproducir sin la autorizacin expresa por escrito de Powerware Corporation.

  • iPowerware 9125 Installation Guide for IBM Applications 05146789 A Uncontrolled Copy

    TABLE OF CONTENTSInstallation 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Rack-Mount Setup 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Cabinet Setup 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Installing the UPS 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS Monitoring 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS Rear Panels 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Part Numbers 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Service and Support 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    TABLE DES MATIRESInstallation 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Configuration en baie 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Configuration autonome 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Installation de londuleur UPS 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Surveillance de londuleur UPS 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Panneaux arrires de londuleur UPS 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Numros de pices 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Service aprs-vente et assistance technique 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    INHALTSVERZEICHNISInstallation 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Montage im Gestell 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Montage im Schrank 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Installieren der USV 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .USV-berwachung 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Rckwnde der USV 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Teilenummern 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Kundendienst und Untersttzung 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • Table of Contents

    ii Powerware 9125 Installation Guide for IBM Applications 05146789 A Uncontrolled Copy

    SOMMARIOInstallazione 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Allestimento montaggio su rastrelliera 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Allestimento armadio 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Installazione della UPS 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Monitoraggio UPS 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Pannelli posteriori UPS 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Codici pezzo 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Assistenza e supporto 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    CONTENIDOInstalacin 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Configuracin de montaje de bastidor 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Configuracin del gabinete 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Instalacin del SIE 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Control del SIE 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Paneles posteriores del SIE 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Nmeros de las parte 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Servicio y soporte 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 1Powerware 9125 Installation Guide for IBM Applications 05146789 A Uncontrolled Copy

    INSTALLATIONThe Powerware 9125 UPS is designed for flexible configurations and canbe installed in a rack or as a standalone cabinet.

    If you are installing the UPS in a rack, continue to the following sectionRack-Mount Setup; otherwise, continue to Cabinet Setup onpage 2.

    Rack-Mount SetupThe UPS can be installed in 19- or 23-inch racks and needs only 2U ofvaluable rack space.

    NOTE Mounting rails are required for each cabinet. If rails are not already installed inyour rack, contact your local distributor to order a rail kit.

    Use the following procedure to install the UPS in a rack:

    1. Place the UPS on a flat, stable surface with the front of the UPSfacing toward you.

    2. Attach the mounting handles to the bracket with the screwsprovided in the accessory kit (see Figure 1).

    3. Align the mounting brackets with the screw holes on the side ofthe UPS and secure with the supplied screws (see Figure 1).

    4. If installing optional Extended Battery Modules (EBMs), repeatSteps 1 through 3 for each cabinet.

    MountingHandle

    MountingBracket

    Figure 1. Installing the Mounting Brackets

  • Installation

    2 Powerware 9125 Installation Guide for IBM Applications 05146789 A Uncontrolled Copy

    NOTE The EBMs must be installed below the UPS as shown in Figure 2.

    5. Slide the UPS and any optional EBMs into the rack. Continue toInstalling the UPS on page 4 to complete the installation.

    UPS

    OptionalEBMs

    Figure 2. Rack-Mount UPS with EBMs

    Cabinet SetupYou can position the UPS cabinets horizontally or vertically. Whenpositioning the cabinets horizontally, the EBMs must be placed belowthe UPS (see Figure 3).

    UPS

    OptionalEBMs

    Figure 3. Horizontal Cabinet Setup

  • Installation

    3Powerware 9125 Installation Guide for IBM Applications 05146789 A Uncontrolled Copy

    NOTE The air vents should be at the top of the unit when positioned vertically.

    Air Vents

    Figure 4. Vertical Cabinet Setup

    When a single UPS cabinet is positioned vertically, the UPS stands mustbe attached to the bottom of the cabinet tower:

    1. Place the UPS horizontally, so that the left end of the unit isaccessible.

    2. Slide and position the UPS stands over the end of the unit sothat the weight of the UPS is evenly distributed (see Figure 5).Secure the stands with the screws provided in the accessory kit.

    Figure 5. Installing the UPS Stands

    3. Carefully position the unit upright on the UPS stands (seeFigure 6).

    Continue to the following section, Installing the UPS.

  • Installation

    4 Powerware 9125 Installation Guide for IBM Applications 05146789 A Uncontrolled Copy

    Air Vents

    Figure 6. UPS Cabinet with Stands

    Installing the UPSThe following steps explain how to install the UPS. Figure 8 shows atypical installation only. See UPS Rear Panels on page 8 for the rearpanel of each model.

    C A U T I O NA small amount of arcing may occur when connecting an Extended Battery Module tothe UPS. This is normal and will not harm personnel. Insert the EBM cable into the UPSbattery connector quickly and firmly.

    NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occurto your equipment and void your warranty.

    1. If installing an optional EBM, continue to Step 2; otherwise,skip to Step 8.

    Steps 24 are not required for rack-mount installations.

    2. Remove the adjacent corner screws from the rear panels asshown in Figure 7 to install the EBM brackets.

    3. Align each EBM bracket with the screw holes and secure withthe screws removed in Step 2.

  • Installation

    5Powerware 9125 Installation Guide for IBM Applications 05146789 A Uncontrolled Copy

    4. If installing additional EBMs, repeat Steps 2 and 3 for eachcabinet.

    EBM Bracket EBM Bracket

    Figure 7. Installing the EBM Brackets

    5. Plug the EBM cable into the battery connector on the UPS rearpanel (see Figure 8).

    6. If additional EBMs are to be installed, plug the EBM cable of thesecond cabinet into the battery connector on the first EBM.Repeat for each additional EBM. Up to four EBMs may beconnected to the UPS.

    UPS BatteryConnector

    Power Cord

    EBM Cable

    Output Receptacles

    Load Segment 2

    Load Segment 1

    Communication Port

    EBM BatteryConnectors

    Figure 8. Typical UPS Installation (120V Model Shown)

  • Installation

    6 Powerware 9125 Installation Guide for IBM Applications 05146789 A Uncontrolled Copy

    7. Verify that the AS/400 and other equipment to be protected bythe UPS is powered off.

    8. Connect one of the supplied communication cables to the UPScommunication port according to your computer system:

    For the AS/400. Use the supplied AS/400 communication cable.The AS/400 end of the cable connects to the port markedJ14 or UPSon the AS/400 rear panel.

    For the RS/6000. If you are installing power managementsoftware, use the supplied RS/6000 communication cable.

    For PCs and workstations. Use the communication cablesupplied with the power management software CD.

    9. Plug your equipment into the appropriate UPS outputreceptacles using the equipment power cords supplied with theUPS.

    NOTE If you are using the Load Segment feature, see the Powerware 9125 UsersGuide for more information on controlling and assigning the load segments.

    DO NOT protect laser printers with the UPS because of theexceptionally high power requirements of the heating elements.

    10. Turn on the equipment that is connected to the UPS.

    11. Plug the power cord from the UPS into a power outlet.

    For 230V models (including P11 and P16). Use the AS/400 or RS/6000power cord to connect the UPS to the power outlet.

    All front panel indicators flash briefly and the UPS conducts aself-test.

    When the self-test is complete, the indicator flashes,indicating the UPS is in Standby mode with the equipmentoffline.

  • Installation

    7Powerware 9125 Installation Guide for IBM Applications 05146789 A Uncontrolled Copy

    12. Start the UPS by pressing the On button. The indicatorstops flashing and the bar graph indicators display thepercentage of load being applied to the UPS.

    The UPS is now in Normal mode and supplying power to yourequipment.

    NOTE The batteries charge to 80% capacity in approximately 2 hours. However, it isrecommended that the batteries charge for 24 hours after installation or long-termstorage.

    13. For the AS/400. Set the QUPSDLYTIM system value for the UPSMonitoring feature.

    UPS MonitoringUPS monitoring is a standard feature of the AS/400 operating system.QUPSDLYTIM is a timer in the AS/400 that tells the system how long torun on UPS power before shutting down. Each AS/400 system is initiallyassigned a default value for QUPSDLYTIM. A complete description ofQUPSDLYTIM is provided on the AS/400 Information Center InternetSite at http://publib.boulder.ibm.com/pubs/html/as400/ic2924/info/index.htm.

    C A U T I O N*NOMAX tells the AS/400 to use customized shutdown software, and if none isavailable it will begin shutdown immediately when utility power fails. Do not setQUPSDLYTIM to *NOMAX unless you understand the implications of the *NOMAXfunction as described at the AS/400 Information Center Internet Site.

  • Installation

    8 Powerware 9125 Installation Guide for IBM Applications 05146789 A Uncontrolled Copy

    UPS Rear PanelsThis section shows the rear panels of the Powerware 9125 models.

    REPO Port

    5-15 Receptacles

    Battery Connector

    Power Cordwith 5-15P

    Communication Port

    Network Transient Protector

    X-Slot

    Figure 9. 10001500 VA, 120V Rear Panel

    Network Transient Protector

    IEC-320Receptacles

    Battery Connector

    IEC-320 Input ConnectorCommunication Port

    X-Slot

    REPO Port

    Figure 10. 10001500 VA, 230V Rear Panel