Page 1: Electronic Control Box Manual -Y1958C

Octobre 08

BBooîîttiieerrdd’’AAuuttoommaattiissmmee

Réf. 261 93 – Réf. 261 94

Y1958C

Page 2: Electronic Control Box Manual -Y1958C
Page 3: Electronic Control Box Manual -Y1958C

Table des matieres

3

1. Caractéristiques générales . . . . . . . . . . 41.1 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . 41.2 Description . . . . . . . . . . . . . . . . . . . . . . . . 41.3 Applications . . . . . . . . . . . . . . . . . . . . . . . 41.4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . 41.5 Alimentation . . . . . . . . . . . . . . . . . . . . . . . . 4

2. Description de la façade . . . . . . . . . . . . 52.1 Touches de sélection . . . . . . . . . . . . . . . . . . 52.2 Sélection mesures . . . . . . . . . . . . . . . . . . . 62.3 Indicateurs à diodes . . . . . . . . . . . . . . . . . . 6

3. Modes de fonctionnement . . . . . . . . . . . 83.1 Mode reset (voyant touche RESET rouge) . . . . 83.2 Mode manuelle (voyant touche MAN rouge) . 93.3 Mode automatique (voyant touche AUT rouge) . 93.4 Mode test off-load (hors-charge) . . . . . . . . . . . 93.5 Mode test on-load (en charge) . . . . . . . . . . . 9

4. Applications . . . . . . . . . . . . . . . . . . . . . . 104.1 Application Secteur-Groupe . . . . . . . . . . . . . 104.2 Application Secteur-Secteur . . . . . . . . . . . . . . 10

5. Commande appareils . . . . . . . . . . . . . . 115.1 Avec feedback . . . . . . . . . . . . . . . . . . . . . 115.2 Sans feedback . . . . . . . . . . . . . . . . . . . . . 12

6. Contrôles de tension . . . . . . . . . . . . . . . 13

7. Programmation . . . . . . . . . . . . . . . . . . . 157.1 Programmation des paramètres . . . . . . . . . . . 157.2 Tableau des menus . . . . . . . . . . . . . . . . . . . 167.3 Menu P0 - Données nominale . . . . . . . . . . . . 167.4 Menu P1 - Données générales . . . . . . . . . . . 177.5 Menu P2 - Contrôle tension ligne principale . . 187.6 Menu P3 - Contrôle tension ligne secondaire . . 197.7 Menu P4 - Entrées programmables . . . . . . . . . 207.8 Menu P5 - Sorties programmables . . . . . . . . 207.9 Menu P6 - Communication série . . . . . . . . . . 21

8. Messages de diagnostic . . . . . . . . . . . . . 22

9. Alarmes . . . . . . . . . . . . . . . . . . . . . . . . . 23

10. Branchements . . . . . . . . . . . . . . . . . . . . 25

11. Caractéristiques techniques . . . . . . . . . . 26

Page 4: Electronic Control Box Manual -Y1958C

1. Caractéristiques générales

4

1.1 Versions• 261 93 - Version standard • 261 94 - Version évoluée + interface RS-485

1.2 Description• Commutateur automatique de secteur à micro-

processeur• Deux entrées de mesure de tensions triphasées• Alimentation CC 12-24-48 Vcc• Alimentation CA 220-240 Vca• 2 moniteurs à diodes, 3 chiffres de 7 segments • 20 diodes de visualisation états et mesures

• Clavier à membrane à 8 touches• Sortie série RS-232 (contrôle à distance et super-

vision)• Sortie RS-485 isolée pour protocole MODBUS

(261 94)• 2 entrées TOR (tout ou rien) programmables • 3 sorties à relais (1 NO + 2 NO/NF) program-

mables

1.3 Applications• Commutation entre ligne-ligne et ligne-groupe

électrogène• Commande des appareils motorisés • Marche/arrêt groupe électrogène• Relevé tensions sur lignes triphasés, biphasés ou

monophasés

• Relevé tensions phase-phase (ou sur les tensionsphase-neutre dans le cas des lignes monophasés)

• Contrôles de tension minimum, de tension maxi-mum, d’absence de phase, d’asymétrie, de fré-quence minimum et de fréquence maximum avecvalidation et retard indépendants

• Seuil de tension avec hystérésis programmable

1.4 Installation• Installer l’appareil en suivant les schémas de bran-

chement (voir dernières pages du manuel) • Utiliser le schéma de branchement correspondant

à l’application

• Programmer les paramètres en fonction du sché-ma de branchement adopté, en faisant particu-lièrement attention à la programmation desentrées/sorties

1.5 Alimentation• 261 93 et 261 94 ont un double circuit d’ali-

mentation ; ils peuvent être alimentés en CA etCC en même temps, ou seulement en CA ou enCC indifféremment

• Quand le boîtier est alimenté en CA et CC enmême temps, l’énergie est prélevé en CA

Page 5: Electronic Control Box Manual -Y1958C

2. Description de la façade

5

• La façade du boîtier dispose de deux afficheurs àdiodes pour indiquer les tensions des deuxsources d’alimentation avec les deux touches cor-respondantes: ligne principale (A) et ligne secon-daire (B) pour la sélection des mesures.

• Quatre touches SET (E) - AUT (F) - MAN (G) - RESET(H) permettent de sélectionner la mode de fonction-nement indiquée par le voyant correspondant.

• Au centre la façade est représenté un synoptiquequi indique l’état des appareils pour la connexionde la charge.

• Deux boutons (C) et (D) permettent d’ouvrir/fermerles appareils (boutons actifs uniquement aprèsavoir appuyé sur la touche MAN).

2.1 Touches de sélection

A B

E

F

G

H

C D

Page 6: Electronic Control Box Manual -Y1958C

6

• En appuyant à plusieurs reprises sur la touche situéesous chaque moniteur (A) et (B), il est possible devisualiser successivement les différentes mesures de laligne correspondante.

• Pour chaque ligne, sont disponibles les tensionsphase-phase et les tensions phase-neutre (en pré-sence de ligne monophasée).

• Les combinaisons des diodes rouges indiquent lesmesures sélectionnées. La liste des mesures varieselon que l’appareil est configuré pour le contrôletriphasé, biphasé ou monophasé.

• Au bout de 1 minute sans que la touche ait étéenfoncée, est rétablie la mesure par défaut quipeut être la première tension phase-phase ou lapremière tension phase-neutre en fonction de laconfiguration du contrôle de tension.

• En cas d’alarmes ou de messages, affichage du lemessage d’alarme. En appuyant sur la touche de sélection, il estpossible de masquer temporairement l’alarme etd’accéder aux mesures.

2.2 Sélections des mesures

Exemple de liste des mesures sur un boîtier configuré pour le contrôle

triphasé.

• Sur la façade sont présents un certain nombre de témoins qui indiquent l’état de l’appareil et/ou desappareils qu’il commandent.

2.3 Indicateurs à diodes

Diode ALARME(rouge)

Diode ALIMENTATION(verte)

Diode touche SET(rouge)

Diode touche AUT(rouge)

Diode touche MAN(rouge)

Diode touche RESET(rouge)

Diodes L1/L2/L3Présence tension ligne

principale (rouges)

Diode COMMANDESligne principale /ligne secondaire(bicolore)

Diode d’état int. ligne principale

Diode d’état int. ligne secondaire

Diodes L1/L2/L3Présence tension ligne

secondaire (rouges)

Page 7: Electronic Control Box Manual -Y1958C

7

• Dans le tableau ci-dessus est indiquée la signification des différents témoins.Certains d’entre eux sont bicolores à savoir que leur signification est différente selon la couleur.

✱ Si les contacts auxiliaires ont été branchés, le voyant représente l’état de l’appareil, sinon il reste éteint.✱✱ Si les contacts correspondants ont été branchés à cet effet, le voyant représente l’état de l’appareil, sinon les

voyants restent éteints.

Voyant Allumé Éteint Clignotant

ALARME Aucune alarme active Un ou plusieurs alarmes actives (ROUGE)

ALIMENTATION Boîtier alimentée (VERT) Absence alimentation

COMMANDE OUVERTURE/FERMETURE

Commande fermeture (ROUGE)

Commande ouverture (VERT)

Aucune commande

FERMÉ/OUVERT � Appareil fermé (ROUGE)Appareil ouvert (VERT)

Contacts auxiliaires non branchés

NON ENCLENCHÉ �� Appareil non enclenché sur la base

Appareil enclenché ou contrôle enclenchement

désactivé

DÉCLENCHÉ �� Appareil déclenchéAppareil non déclenché

ou contact SDnon connecté

PRÉSENCEL1/L2/L3 Présence tension Absence tension

1HZ = Temps présence absence en cours5HZ = Sélection mesures moniteur

Page 8: Electronic Control Box Manual -Y1958C

3. Modes de fonctionnement

8

• A l’aide des quatre touches SET / AUT / MAN/ RESET il est possible de sélectionner le modede fonctionnement voulu et indiqué par l’allumagedu voyant rouge correspondant.

• Si le voyant qui indique le mode de fonctionne-ment sélectionné clignote, cela indique que l’ap-pareil est en communication à travers l’interfacesérie et qu’il est susceptible d’effectuer des com-mandes transmises à distance (par exemple unecommande de changement de mode).

A B

E

F

G

H

C D

• Le boîtier n’effectue aucune opération et se limiteà afficher l’état des tensions et des appareils.

• Les sorties de commande de fermeture et ouvertu-re des appareils restent toutes ouvertes permettantla commande manuelle des motorisations. Si l’en-trée «arrêt d’urgence» est activée, le boîtier com-mande l’ouverture des appareils.

• La sortie de commande générateur se positionnepour l’arrêt du groupe.

• Les alarmes d’état des appareils sont désactivées. • Lorsqu’une alarme se déclenche, elle doit être

réarmée en appuyant sur la touche RESET. Dans lecas où l’on se trouverait déjà dans ce mode,appuyer à nouveau sur la touche RESET.

3.1 Mode reset (voyant touche RESET rouge)

Page 9: Electronic Control Box Manual -Y1958C

• En mode Automatique l’appareil effectue demanière autonome les opérations d’ouverture etde fermeture des appareils ainsi que la mise enmarche et l’arrêt de l’éventuel groupe électrogène.

• Quand la ligne principale (MAIN) se trouve horsdes limites, à l’issue des temps de retard program-més, l’appareil déconnecte la charge de la ligneprioritaire et la connecte à la ligne secondaire(SEC), en contrôlant aussi bien la mise en marche

de l’éventuel groupe électrogène que les temps decommande d’inter-verrouillage entre les appareils.

• Quand la ligne principale rentre à nouveau dansles limites, le boîtier commute à nouveau la chargesur la ligne principale et assure l’éventuel cycle derefroidissement du groupe électrogène.

• Les cycles de fonctionnement automatique varienten fonction du type d’application (secteur-secteurou secteur-groupe).

9

Attention:L’exécut ionde ce test pré-voit le trans-fert de lacharge, àsavoir unecoupure del’alimentationsur celle-cipendant lacommutationdue auxtemps d’inter-verrouillage.

3.2 Mode Manuel (voyant touche MAN rouge)• Le mode manuel permet à l’opérateur d’ouvrir/fer-

mer électriquement les appareils à l’aide destouches présentes sur la façade de l’appareil.

• Dans ce mode les tensions sont constammentcontrôlées mais le boîtier se limite à en visualiserl’état.

• En appuyant pendant au moins 300 ms sur unedes touches de commande, le boîtier commutel’état de l’appareil correspondant (d’ouvert àfermé et vice-versa).

• Dans le cas où serait commandé la fermetured’un appareil alors que l’autre est déjà fermé, le

boîtier ouvre initialement l’autre appareil, laisses’écouler le temps d’inter-verrouillage puis fermel’appareil voulu.

• En Manuel toutes les alarmes relatives à l’état desappareils (non enclenchés et déclenchés) sontdésactivées. L’alarme est indiquée sur le voyantcorrespondant mais n’est pas mémorisée.

• Il est possible de commander manuellement lamise en marche et l’arrêt du groupe électrogèneen maintenant enfoncée la touche (G) MAN pen-dant 5 secondes d’affilée. Tant que l’on reste enmode manuel, l’état du groupe reste celui voulu.

3.3 Mode Automatique (voyant touche AUT rouge)

• En partant du mode Automatique et en appuyant sur latouche (F) pendant 5 secondes, alors s’enclenche untest du groupe électrogène d’une durée de 5 minutes.

• Le groupe électrogène est mis en marche manuel-lement pour qu’en soit contrôlé le fonctionnement,mais les contrôles de tension restent actifs puisquele boîtier est en mode automatique.

• De la sorte il est possible de s’assurer du bonfonctionnement du groupe en maintenant la

couverture de la charge. En conditions nor-males, la charge reste connectée à la ligneprincipale, à savoir que le groupe fonctionnesans charge (off-load groupe électrogène).

• L’exécution du test off-load est signalée par l’indi-cation TES fixe sur le boîtier.

• Pour anticiper la fin du test, appuyer à nouveau surla touche (F) pendant 5 secondes ou bien passeren mode Reset.

• En partant du mode automatique et en appuyantsimultanément sur les touches (F) et (D) pendant5 secondes, alors est activé un test fonctionnel(test on-load) qui simule une coupure d’une duréed’une minute.

• Le boîtier si comporte ensuite exactement commesi le secteur était sorti des limites, en utilisantpour la commutation tous les temps et tous les

paramètres programmés, de façon à en contrô-ler la validité.

• L’exécution du test on-load est signalée par l’indi-cation TES clignotante sur le boîtier.

• Pour anticiper la fin du test, répéter la procédure àl’aide des touches (F) et (D) pendant 5 secondesou bien passer en mode Reset.

3.5 Mode test on-load

3.4 Mode test off-load

Page 10: Electronic Control Box Manual -Y1958C

4. Applications

10

4.1 Application Secteur-Groupe• Sur l’application secteur-groupe (U-G, configura-

tion par défaut) la charge est en principe connec-tée à la ligne principale. En présence d’une ano-malie sur le secteur ou en cas de signal de trans-fert imposé de l’extérieur, il est transmis un signalde mise en marche au groupe présent sur la lignesecondaire.

• Quand la tension du groupe rentre dans les limitesprogrammées, le boîtier commande la commuta-tion sur la ligne secondaire.

• Au retour de la ligne principale la charge estretransférée et le groupe est maintenu en marchesans charge pendant une durée préétablie defaçon à en permettre le refroidissement.

• Le boîtier envoie au groupe une commande destart/stop par l’intermédiaire d’une sortie à relaiset peut recevoir des signaux numériques du grou-pe qui en indiquent l’état à travers des entréesprogrammables.

4.2 Application Secteur-Secteur• Sur l’application secteur-secteur (U-U, utility-utili-

ty), la charge est en principe connectée au sec-teur prioritaire et le transfert sur le secteur secon-

daire intervient en cas d’anomalie sur le secteurprimaire ou de signal de transfert imposé del’extérieur.

Page 11: Electronic Control Box Manual -Y1958C

5. Commande appareils

11

• La commande de la motorisation des appareils estassurée par deux relais distincts, l’un pour la fer-meture et l’autre pour l’ouverture.

• En mode Reset, les deux relais de commande restentouverts, sauf en condition d’urgence dans laquellel’ouverture de l’appareil peut être commandée.

• Suite à une anomalie sur l’appareil provoquantune alarme, les sorties de commande sont toutesdeux ouvertes jusqu’à l’élimination de l’alarme.

• Ils existent deux modes distincts de contrôle desappareils, sélectionnables par l’intermédiaire duparamètre P1.03

Les contactsauxiliares CAde l’appareil

sont câblés surles entrées

respectives duboîtier.

En modalitéfeedback est

nécessaire d’utiliser pourl’ouverture du

DPX 250-630-1600

des déclencheures a

emition de courant ou a

minimum de tension.

Exemple de commande des appareilsavec feedback en supposant une

commutation secteur-secteur. En bleu estindiqué l’état des entrées de feedback.En vert l’état des sorties de commande.

En jaune le temps de commutation.

0.5 s

15 s

0.5 s

LED VMAIN OK

LED VSEC OK

46

115

18

3

1s

1s

15 s

5.1 Avec feedback • Les voyants bicolores frontaux indiquent l’état des

appareils en commutation grâce aux contactsauxiliaires CA.

• Les alarmes Timeout sont actives. Elles se déclen-chent si l’appareil ne se place en position requiseau bout d’une durée programmable P1.04 ouimmédiatement s’il change de position sansqu’une commande n’ait été envoyée.

• Les sorties de commande sont temporisées. Unefois que l’appareil a effectué l’opération voulue, la

sortie reste activée pendant une certaine durée(+1 seconde en phase de fermeture et +15secondes en phase d’ouverture pour permettre lechargement complet des ressorts) puis elle estdésactivée

• L’état normal des sorties de commande est l’étatouvert pour les deux sorties.

• Le temps d’inter-verrouillage est décompté à partirde l’ouverture effective du premier appareil, et ilest de 0,5 seconde.

Page 12: Electronic Control Box Manual -Y1958C

12

5.2 Sans feedback

Les contactsauxiliaires CA

de l’appareil nesont pas câbléssur les entrées

respectives,donc le boîtier

n’est pasinformée de leur

état effectif.

Exemple de commande des appareilssans feedback.

En bleu est indiqué l’état effectif desappareils.

En vert l’état des sorties de commande.En jaune le temps de commutation.

6 sec 6 sec

LED VMAIN OK

LED VSEC. OK

INT. MAIN

INT. SEC.46

13

• Les voyants d’état de l’appareil restent éteints. • Les alarmes de Timeout sont désactivées.• Les sorties des commandes Ouverture/Fermetu-

re restent constamment dans la position requisepour l’appareil.

• Les temps d’inter-verrouillage entre l’ouvertured’un appareil et la fermeture de l’autre estdécompté à partir de la commutation des sor-ties et il est de 6 secondes.

Page 13: Electronic Control Box Manual -Y1958C

6. Contrôles de tension

13

• Toutes les conditions, servant à établir si une sour-ce d’alimentation est appropriée ou non, sont défi-nies par l’utilisateur par l’intermédiaire du menuP0 (données nominales de l’installation) et desmenus P2 et P3 (respectivement contrôle tensionde la ligne principale et de la ligne secondaire).

• Par l’intermédiaire du menu P0 il est possible dedéfinir les données nominales telles que tension etfréquence nominale, utilisées ensuite comme réfé-rence pour la programmation des seuils (en pour-centage) des menus suivants.

• Il est possible de programmer un rapport de trans-formation TU dans le cas où serait appliquée auxentrées de tension du boîtier une tension inférieureà la tension effective de l’installation. Dans ce caségalement, la visualisation et la programmationdes seuils sont effectuées en grandeurs réelles parrapport à l’installation.

• Le boîtier peut être programmée pour effectuerles contrôles de tension sur secteurs triphasés,biphasés ou monophasés (par l’intermédiaire duparamètre P0.03).

Contrôle 261 93 261 94 Description

Tension minimum • • Une ou plusieurs phases trop basses

Tension maximum • Une ou plusieurs phases trop hautes

Absence phase • • Seuil en deçà duquel líappa reil intervient plus rapidement par rapport à un abaissement normal

Asymétrie(déséquilibrage) • Phases comprises sur l’intervalle Maximum-Minimum

mais trop différentes l’une de l’autre

Fréquence minimum • Fréquence trop basse

Fréquence maximum • Fréquence trop haute

Séquence phases • Rotation inverse des phases

Ci-après sont indiquées les anomalies dont la gestion est assuré par le contrôle de tension.Les colonnes 261 93 et 261 94 indiquent la présence de la fonction sur les différents modèles du boîtier.

Page 14: Electronic Control Box Manual -Y1958C

14

• Chacune des anomalies a un temps de retardindépendant. L’anomalie doit avoir une durée inin-terrompue supérieure au temps indiqué pour inva-lider le signal de présence tension.

• Tous les contrôles, exception faite du contrôle detension minimum, peuvent être exclus indépendam-ment les uns des autres en plaçant le paramètrecorrespondant sur OFF.

• Les limites de tension minimum et maximum sontdéfinies par la programmation de deux seuils spé-cifiques, l’un définissant le point au-delà duquel latension est considérée comme n’étant plus accep-table (ex. P2.01), l’autre, plus proche de la ten-sion nominale, définissant le point à partir duquel

elle est de nouveau acceptable (ex. P2.02). Ladistance entre ces deux points définit l’hystérésis.Par exemple, on peut établir qu’en deçà de 80%de la valeur nominale, la tension n’est plus utili-sable et qu’elle est à nouveau acceptable une foisqu’elle est à nouveau supérieure à 85%, l’hystéré-sis étant dans ce cas de 5%.Le même principe s’applique à la tension maximum.

• Pour les seuils de fréquence existe une hystérésisfixe de 1% de la fréquence nominale.

• Le rétablissement à l’issue d’une absence dephase est obtenue quand la tension repasse au-dessus du seuil de rétablissement de tensionminimum.

Exemple de variation de la tension de laligne principale à l’intérieur des seuils

minimum et maximum et compte tenu deshystérésis correspondantes,

avec indication des temps de retardprésence/absence. Sur l’exemple, la tension de ligne secondaire est

considérée comme absente et l’appareilcorrespondant ouvert, aussi les temps

d’inter-verrouillage ne sont pas indiqués.La barre INTERR. représente l’état voulu

de l’appareil de la ligne principale.

P2.04

P2.05

P2.02

V MAIN

P2.01

LED VOK

INTERR.P2.03 P2.15 P2.15P2.06 P2.05<

Page 15: Electronic Control Box Manual -Y1958C

7. Programmation

15

7.1 Programmation des paramètres

Touche E- Accès programmation - Quitter vers niveau supérieur

Touche ADéplacement au

même niveau

Touche B- Validation modification- Confirmation configuration

Touche FAugmenter valeur paramètre

Touche GAbaisser valeur paramètre

Touche HAccès au niveau inférieur

• Pour accéder à la programmation, appuyer sur lestouches H et E simultanément pendant 5 secondesd’affilée

• Le voyant de la touche E clignotant indique que laprogrammation est en cours

• L’afficheur de la ligne principale indique le para-mètre sélectionné par l’intermédiaire du code (parexemple P0.01)

• L’afficheur de la ligne secondaire indique la valeurde programmation du paramètre sélectionné (parexemple 400)

• Changement de paramètre d’un même groupe enappuyant sur la touche A

• Passage au groupe suivant avec la touche E• Passage au groupe précédent avec la touche H

• Validation de la modification du paramètre avecla touche B

• Augmentation de la valeur du paramètre sélection-né avec la touche F

• Diminution de la valeur du paramètre sélectionnéavec la touche G

• Confirmation en appuyant sur la touche B• Lors de la modification d’un paramètre, l’afficheur

de la ligne secondaire affiche la valeur actuelleclignotante du paramètre. Durant cette phase iln’est pas possible de se déplacer sur un autreparamètre avant d’avoir validé

• Pour quitter la programmation, appuyer simultané-ment sur les touches E et H

Page 16: Electronic Control Box Manual -Y1958C

16

7.2 Tableau des menus

7.3 Menu P0 - Données nominales

Menu Description

P0 Données nominales de l’installation

P1 Données générales

P2 Contrôle tension ligne principale

P3 Contrôle tension ligne secondaire

P4 Entrées programmables

P5 Sorties programmables

P6 Port de communication

Prog. Description Plage Par défaut

P0.01 B Tension nominale Ue 100 … 690 Vca 380 Vca

P0.02 B Rapport de transformation TU 1.00 … 9.99 1.00

P0.03 B Type de reseau3Ph = Triphasée2PH = Biphasée1Ph = Monophasée

3Ph

P0.04 B Fréquence nominale Fe 50H = 50Hz60H = 60Hz 50Hz

P0.05 B Tension nominale batterie

OFF = Sans batterie12 = 12 Vcc24 = 24 Vcc48 = 48 Vcc

OFF

P0.01 - Tension nominale utilisée pour le calcul des seuils P0.02 - Maintenir la programmation par défaut en cas de non-utilisation de TUP0.04 - Fréquence nominale utilisée comme référence pour le calcul des seuils de fréquence P0.05 - Utilisé pour les alarmes sur la tension de batterie

Page 17: Electronic Control Box Manual -Y1958C

17

7.4 Menu P1 - Données généralesProg. Description Plage Par défaut

P1.01 Type d’application U-G = Secteur-GroupeU-U = Secteur-Secteur U-G

P1.02 Contrôle séquence phaseOFF - Désactivé123 - Direct321 - Inverse

OFF

P1.03 Contrôle commutation FEE - Avec feedback NOF - Sans feedback FEE

P1.04 Temps maximum de commande appareil OFF / 1…900s 5 s

P1.05 Activation contrôle appareils extraits OFF (Contrôle désactivé)ON (Contrôle activé) OFF

P1.06 Temps maximum charge non alimentée (retard intervention alarme A07) OFF / 1…3600s OFF

P1.07 Temps de retard mise en marche groupe 0 …. 900 s 1 s

P1.08 Temps de refroidissement groupe 1…3600s 120 s

P1.09 Seuil minimum tension batterie OFF / 70…100% 75%

P1.10 Seuil maximum tension batterie OFF / 110…140% 130%

P1.11 Temps de retard seuils batterie 0…60 s 10 s

P1.01 - Définit le type de commutation (secteur-secteur / secteur-groupe)P1.04 - Dans le cas où après la transmission d’une commande d’ouverture ou de fermeture à un appareil, celui-ci ne se

positionnerait pas correctement avant que cette durée ne se soit écoulée, alors activation de l’alarme A03 ouA04

P1.05 - Activer le contrôle uniquement si les contacts correspondants sont câblésP1.06 - En mode Automatique, si aucune des deux sources n’est disponible avant la fin de cette temporisation, alors

activation de l’alarme A07P1.07 - Temporisation enclenchée lors de l’absence de tension sur la ligne principale, si fin de tempo ordre de démarrage

groupe.Il s’agit d’une durée indépendante du temps d’ouverture des appareils

P1.08 - Temps pendant lequel le groupe est maintenu en marche pour son refroidissement après qu’il ait été isolé de lacharge

Les paramètresen évidence

sont présentsuniquement

sur la version261 94

Page 18: Electronic Control Box Manual -Y1958C

18

7.5 Menu P2 - Contrôle tension ligne principaleProg. Description Plage Par défaut

P2.01 Seuil tension minimum - décrochage 70…98% Ue 85% Ue

P2.02 Seuil tension minimum - rétablissement 75…100% Ue 90% Ue

P2.03 Retard seuil tension minimum 0.1 …. 900 s 1.0 s

P2.04 Seuil tension maximum - décrochage 102…120% Ue / OFF 115% Ue

P2.05 Seuil tension maximum - rétablissement 100…115% Ue 110% Ue

P2.06 Retard seuil tension maximum 0.1 …. 900 s 1.0 s

P2.07 Seuil absence phase 60 … 85% Ue / OFF 70% Ue

P2.08 Retard seuil absence phase 0.1 … 30.0 s 0.1 s

P2.09 Seuil déséquilibrage tensions 1 … 20% Ue / OFF 10%

P2.10 Retard seuil déséquilibrage tensions 0.1 … 900 s 5.0 s

P2.11 Seuil minimum fréquence OFF / 80… 100% Fe 95% Fe

P2.12 Retard seuil minimum fréquence 0.1 … 900 s 5.0 s

P2.13 Seuil maximum fréquence 101 … 120% Fe / OFF 105% Fe

P2.14 Retard seuil maximum fréquence 0.1 … 900 s 3.0 s

P2.15 Retard retour tension ligne principale dans les limites (quand int. ligne secondaire ouvert) 1 … 3600 s 10 s

P2.16 Retard retour tension ligne principale dans les limites (quand charge sur ligne secondaire) 1 … 3600 s 60 s

Les paramètresen évidence

sont présentsuniquement

sur la version261 94

P2.01 - P2.02 - P2.03 - Les deux premiers paramètres définissent le seuil de tension minimum et l’hystérésis corres-pondante au rétablissement. P2.02 ne peut pas être programmé sur une valeur inférieure à P2.01. P2.03 définit le tempsde retard pour l’intervention de cette protection. Voir chapitre Contrôles de tensionP2.04 - P2.05 - P2.06 - Les deux premiers paramètres définissent le seuil de tension maximum et l’hystérésis corres-pondante au rétablissement. P2.05 ne peut être programmé sur une valeur supérieure à P2.04. En programmant P2.04sur OFF, le contrôle de tension maximum est désactivé. P2.06 définit le retard d’intervention de tension maximum. Voirchapitre Contrôles de tensionP2.07 - P2.08 - Seuil de tension en deçà duquel se déclenche une intervention pour absence de phase, géné-ralement plus rapide que l’abaissement. Le temps de retard pour l’absence phase est indiqué par P2.08P2.09 - P2.10 - P2.09 définit le seuil maximum de déséquilibre entre les phases, en rapport à la tension nominale,et P2.10 le retard d’intervention correspondant.Ce contrôle peut être désactivé en programmant P2.09 sur OFF P2.11 - P2.12 - Seuil (désactivable) et retard d’intervention de fréquence minimum P2.13 - P2.14 - Seuil (désactivable) et retard d’intervention de fréquence maximumP2.15 - Temps de retard retour ligne principale dans les limites, utilisé quand la source de la ligne secondaire n’est pasdisponible. Généralement plus court que P2.16, puisque, la charge n’étant pas alimentée, il est urgent de fournir unetensionP2.16 - Temps de retard retour ligne principale dans les limites, utilisé quand la charge peut être connectée à laligne secondaire. Généralement plus long que P2.15, puisque, la charge étant sous tension il est possible d’attendreplus longtemps avant de considérer la tension comme rétablie et stable

Page 19: Electronic Control Box Manual -Y1958C

19

7.6 Menu P3* - Contrôle tension ligne secondaireProg. Description Plage Par défaut

P3.01 Seuil tension minimum - décrochage 70…98 % Ue 85 % Ue

P3.02 Seuil tension minimum - rétablissement 75…100 % Ue 90 % Ue

P3.03 Retard seuil tension minimum 0.1 …. 900 s 1.0 s

P3.04 Seuil tension maximum - décrochage 102…120 % Ue / OFF 115 % Ue

P3.05 Seuil tension maximum - rétablissement 100…115 % Ue 110 % Ue

P3.06 Retard seuil tension maximum 0.1 …. 900 s 1.0 s

P3.07 Seuil absence phase 60 … 85% Ue / OFF 70 % Ue

P3.08 Retard seuil absence phase 0.1 … 30.0 s 0.1 s

P3.09 Seuil déséquilibrage tensions 1 … 20 % / OFF 10 %

P3.10 Retard seuil déséquilibrage tensions 0.1 … 900 s 5.0 s

P3.11 Seuil minimum fréquence 99 … 80 % Fe / OFF 95 % Fe

P3.12 Retard seuil minimum fréquence 0.1 … 900 s 5.0 s

P3.13 Seuil maximum fréquence 101 … 120% Fe / OFF 105 % Fe

P3.14 Retard seuil maximum fréquence 0.1 … 900 s 3.0 s

P3.15 Retard tension ligne secondaire dans les limites 1 … 3600 s 20 s

Les paramètresen évidence

sont présentsuniquement

sur la version261 94

Note: Pourl’explicationde la fonc-tion desparamètres,se reporter àla page pré-c é d e n t e(menu ligneprincipale).

* Commentaires identiques au Menu P2

Page 20: Electronic Control Box Manual -Y1958C

7.7 Menu P4 - Entrées programmablesProg. Description Plage Par défaut

P4.01 Fonction entrée - Programmable 1Voir liste

“Fonctions entrées programmables”

ForForçage sur ligne secondaire

P4.02 Fonction entrée - Programmable 2In.rInhibition sur ligne principale

Fonctions entrées programmables

Fonction Description Notes

OFF OFF Entrée non utilisée

ForCommutation forcée sur ligne secondaire (fonction EJP)

Quand elle est fermée, force la commutation sur la ligne secondaire y compris si la tension de la ligne principale est dans les limites. La commutation sur la ligne principale intervient quand l’entrée est libérée ou dans le cas où la tension de la ligne secondaire ne serait pas dans les limites

IN.R Inhibition retour sur ligne principale

En mode automatique, quand elle est fermée, elle bloque le retour en automatique sur la ligne principale après que la tension soit revenue dans les limites. Sert à éviter que la seconde interruption de courant due au re-transfert intervienne automatiquement à un moment imprévisible

S.GEMise en marche/arrêt volontaire groupe

En mode automatique, quand elle est fermée, provoque la mise en marche du groupe

EME Urgence Contact NF: si ouvert provoque l’ouverture des appareils et déclenche une alarme

G.rE Générateur prêtSi elle est fermée, indique que le générateur est en automatique et non en alarme. Si elle est ouverte, génère un code d’alarme

Loc Blocage total clavier Si elle est fermée bloque toutes les fonctions du clavier à l’exception des mesures

L.PA Blocage accès paramètres Si elle est fermée bloque l’accès aux configurations

20

7.8 Menu P5 - Sorties programmablesProg. Description Plage Par défaut

P5.01 Fonction sortie Programmable 1 Voir liste “Fonctions sorties programmables” S.GE

Start generator

P5.02 Fonction sortie Programmable 2 Voir liste “Fonctions sorties programmables” RDY

ATS Ready

P5.03 Fonction sortie Programmable 3 Voir liste “Fonctions sorties programmables” ALA

Alarme générale

Page 21: Electronic Control Box Manual -Y1958C

21

Fonctions sorties programmables

Fonction Description Notes

OFF OFF Sortie non utilisée

S.GE Validation mise en marche générateurQuand elle est fermée, le générateur doit être à l’arrêt.Contact ouvert pour mettre en marche le générateur.Si la boîtier n’est pas alimentée, le générateur se met en marche

RDY Commutation transfert automatique prêt Signal que le boîtier est en mode automatique et sans alarmes, prêt à intervenir

ALA Alarme générale Signalisation alarme à distance

MCMBobine à minimum de tensionLigne principale

Commande bobine à minimum de tension de l’appareil ligne principal

MCSBobine à minimum de tensionLigne secondaire

Commande bobine à minimum de tension de l’appareil ligne secondaire

L.SHDébranchement charges non prioritaires

Débranchement des charges non prioritaires qui ne sont pas alimentées par la ligne secondaire.Elle est également commandée sur ligne principale.Contact fermé avant la commande de fermeture ligne secondaire et ouvert avant la commande de fermeture ligne principale

7.9 Menu P6 - Communication sérieProg. Description Plage Par défaut

P6.01 Adresse sérielle RS-232 1…245 01

P6.02 Vitesse (bauds) RS-232

240 = 2400 480 = 4800960 = 9600 19.2 = 19200 38.4 = 38400

960

P6.03 Protocole RS-232 Rtu = Modbus RTUASC = Modbus ASCII RTU

P6.04 Parité RS-232No = AucuneEVE = Even (Paire)Odd = Odd (Impaire)

No

P6.05 Adresse série RS-485 1…245 01

P6.06 Vitesse (bauds) RS-485

240 = 2400 480 = 4800960 = 9600 19.2 = 19200 38.4 = 38400

960

P6.07 Protocole RS-485 Rtu = Modbus RTUASC = Modbus ASCII RTU

P6.08 Parité RS-485No = AucuneEVE = Even (Paire) Odd = Odd (Impaire)

No

P6.01…P6.04 - Définissent le format de transmission et le protocole utilisé sur le port de communication RS-232P6.05…P6.08 - Définissent le format de transmission et le protocole utilisé sur le port de communication RS-485,

disponible uniquement sur la version 261 94

Les paramètresen évidence

sont présentesuniquement

sur la version261 94

Page 22: Electronic Control Box Manual -Y1958C

8. Messages de diagnostic

22

Sur les afficheurs peuvent être visualisés à différents moments les messages suivants:

Code Description

- - -(Tirets) - La temporisation d’inter-verrouillage est active.S’affichent du côté vers lequel la charge est en cours de transfert

Sta (Start) - Commande de mise en marche générateur

Coo (Cooling) - Le générateur est maintenu en marche pour effectuer le refroidissement

Tes(Test) - Si fixe, test off-load en cours, à savoir un test du groupe électrogène avec les contrôles de tension actifs

Tes (Test) - Si clignotant, test on-load en cours, à savoir une simulation de l’absence secteur en automatique

Loc (Locked) - Indique que la fonction que l’on tente d’exécuter depuis le clavier est bloqué

Page 23: Electronic Control Box Manual -Y1958C

9. Alarmes

23

• Durant le fonctionnement du boîtier, peut se pré-senter toute une série de situations anormales, les-quelles sont signalées de différentes manières.

• Certaines alarmes (déclenché, non réarmé) ontun voyant spécifique qui en cas d’intervention semet à clignoter.

• D’autres alarmes sont signalées par l’intermédiaired’un code constitué d’un A (alarme) et d’une réfé-rence numérique qui indique de quelle alarme ils’agit. Ce code se visualise en clignotant sur undes afficheurs. Si le code est relatif à la ligne prin-cipale, l’alarme est visualisée sur l’afficheur degauche. En revanche, s’il se réfère à la lignesecondaire ou s’il s’agit d’une alarme générale (ex.batterie) il est visualisé sur l’afficheur de droite.

• Quand une alarme se déclenche, le voyant rouge“ALARME” clignote en synchronisation avec levoyant spécifique ou le code d’alarme.

• La sortie à relais Alarme générale est désactivéeen condition alarme, alors qu’elle est activée encondition normale. Le non-fonctionnement du boî-tier pour cause d’anomalie ou problème d’alimen-tation déclenche par conséquent la conditiond’alarme sur le contact correspondant.

• Certaines alarmes sont automatiquement désacti-vées lorsque les conditions qui ont donnés lieu àleurs déclenchements sont éliminées.

• D’autres alarmes, indiquées dans le tableau de lacolonne MEM, sont en revanche à retenue et sontmémorisées.

• Une fois que l’alarme a été mémorisée, pour êtredésactivée, il est nécessaire que les conditionsanormales soient éliminées et que l’opérateurappuie sur la touche RESET ou envoie un messagespécifique par l’intermédiaire de l’interface série.

Page 24: Electronic Control Box Manual -Y1958C

24

Liste alarmes

Code Voyant Description alarme Cause MEM RESET MAN AUT

A01 Tension batterie trop basse

Se déclenche si le paramètre P0.06 n’est pas sur OFF et si la tension de batterie mesurée reste inférieure au seuil % programmé sur P1.09 pendant la durée programmée sur P1.11

OUI OUI OUI OUI

A02 Tension batterie trop élevée

Se déclenche si le paramètre P0.06 n’est pas sur OFF et si la tension de batterie mesurée reste supérieure au seuil % programmé sur P1.10 pendant la durée programmée sur P1.11

OUI OUI OUI OUI

A03 Timeout appareil ligne principale

Se déclenche si l’appareil de ligne principale ne se place pas dans la position commandée par le boîtier avant que ne s’écoule la temporisation sur P1.04 ou s’il quitte de lui-même la position requise. L’alarme peut se déclencher aussi bien en fermeture qu’en ouverture. Si la tension est absente sur les deux lignes, l’alarme ne se déclenche pas

OUI NON NON OUI

A04 Timeout appareil ligne secondaire

Se déclenche si l’appareil de ligne secondaire ne se place pas dans la position commandée par la boitier avant que ne s’écoule la temporisation sur P1.04 ou s’il quitte de lui-même la position requise. L’alarme peut se déclencher aussi bien en fermeture qu’en ouverture. Si la tension est absente sur les deux lignes, l’alarme ne se déclenche pas

OUI NON NON OUI

A05Erreur séquence phase sur ligne principale

Si elle est activée par le paramètre P1.02, cette alarme se déclenche quand est détectée une séquence de phase différente de celle prévue par le paramètre P1.02, après un retard d’environ 500 ms. Pour que la séquence puisse être détectée, les trois phases doivent être > 50Vca

OUI OUI OUI OUI

A06Erreur séquence phase sur ligne secondaire

Idem alarme précédente en référence à la tension de la ligne secondaire OUI OUI OUI OUI

A07 Timeout charge non alimentée

La charge est restée sans tension pendant une durée supérieure à P1.06.Ligne principale et ligne secondaire sont restées indisponibles (absence tension ou appareil non fermé)

NON NON NON YES

A08 Générateur non disponible

Une des entrées programmables est programmée sur “Generator ready” et signale que le générateur n’est pas disponible NON OUI OUI OUI

A09 Urgence Une des entrées programmables est programmée sur bouton d’arrêt d’urgence et le contact correspondant est ouvert OUI OUI OUI OUI

A11Fréquence ligne principale hors limites

La fréquence de la ligne principale est hors des limites définies par P2.11 et P2.13 NON OUI OUI OUI

A12Fréquence ligne secondaire hors limites

La fréquence de la ligne secondaire est hors des limites définies par P3.11 et P3.13 NON OUI OUI OUI

A13 Asymétrie tensions ligne principale

La différence entre la tension phase-phase la plus haute et la plus basse de la ligne principale excède la limite définie par P2.09

NON OUI OUI OUI

A14 Asymétrie tensions ligne secondaire

La différence entre la tension phase-phase la plus haute et la plus basse de la ligne secondaire excède la limite définie par P3.09

NON OUI OUI OUI

Ligne principale/ secondaire non enclenché.Appareil extrait

Le contrôle des entrées de “non activé” est validé par le paramètre P1.05 et le contact correspondant d’entrée de ligne principale ou ligne secondaire est ouvert

OUI OUI OUI OUI

Ligne principale/secondaire déclenchement. Intervention protection. Appareil

Le contact d’entrée “déclenché” est fermé.Cette condition est ignorée pendant une durée de 15 sec. décomptée aussitôt après avoir commandé l’ouverture d’un appareil, pour éviter les erreurs de signal quand est utilisée une bobine de décrochage

OUI VIS VIS OUI

Les alarmes enévidence sont

présentes uniquement

sur la version261 94

Page 25: Electronic Control Box Manual -Y1958C

10. Branchements

25

Borne Fonction

1 Ouverture appareil ligne principale

2 Commun commande ligne principale

3 Fermeture appareil ligne principale

4 Ouverture appareil ligne secondaire

5 Commun commandes ligne secondaire

6 Fermeture appareil ligne secondaire

7 Relais programmable 1 (Fonction par défaut = Start/Stop générateur)

8 Commun relais programmable

9

Relais programmable 2/NF (Fonction par défaut = Boîtier prête)

10 Relais programmable 2/NO (Fonction par défaut = Boîtier prête)

11

Commun relais programmable 2

12

Relais de programmable 3/NF (Fonction par défaut = Alarme générale)

13Relais de programmable 3/NO (Fonction par défaut = Alarme globale - fermé quand ok)

14

Commun relais programmable 3

15 Entrée contact CA appareil ligne principale

Borne Fonction

16 Entrée contact SD appareil ligne principale

17 Entrée contact appareil débrochable ligne principale

18 Entrée contact CA appareil ligne secondaire

19 Entrée contact SD appareil ligne secondaire

20 Entrée contact appareil débrochable ligne secondaire

21 Entrée programmable 1 (Par défaut = Fonction EJP)

22 Entrée programmable 2 (Par défaut = Inhibition retour sur ligne principale)

23 + Alimentation CC

24 – Alimentation CC

25 Commun pour entrées (de 15 à 22)

26 Alimentation AC

27 Alimentation AC

MAIN L1 L2 L3 N

Entrée de mesure triphasée ligne principale

SEC. L1 L2 L3 N

Entrée de mesure triphasée ligne secondaire

Page 26: Electronic Control Box Manual -Y1958C

11. Caractéristiques techniques

26

Alimentation auxiliaireChamp d’alimentation CC 9...70Vcc (Us=12-24-48Vcc)Champ d’alimentation CA 187…264Vca (Us=220…240Vca)Fréquence 45…65HzPuissance absorbée max. 6VA (Us=240Vca)Puissance dissipée max. 4,8W (Us= 240Vca ou Us=48Vcc)Courant absorbé max. 420mA à 12Vcc; 200mA à 24Vcc; 100mA à 48VccTemps d’immunité à la micro-coupure 50msEntrées voltmétriquesTension nominale max. (Ue) 690Vca phase-phase (400Vca phase-neutre)Donnée d’utilisation UL 600Vca phase-phase (340Vca phase-neutre)Champ de mesure 80…800Vc phase--phaseChamp de fréquence 45…65HzType de mesure TRMS (valeur efficace réelle)Impédance de l’entrée de mesure >1,1M Ω phase-phase et > 0,5M Ω phase-neutreMode d’activation Monophasée, biphasée, triphaséeErreur de mesure Classe 0,5 ±0,25% f.s. ±1digitEntrées numériques Type d’entrée NégativeCourant d’entrée ≤10mASignal d’entrée état logique “0” ≤1,5 (type 2,9V)Signal d’entrée état logique “1” ≥5,3 (type 4,3V)Retard du signal d’entrée ≥50msecSorties à relais bornes 1-2 et 4-5Type de contact 1 NOPortée nominale à 250VAC 12APortée nominale contact 16A sur AC1 250V - B300Courant maximum sur la borne 1.2 12ASorties à relais bornes 2-3 et 5-6Type de contact 1 NO

Portée nominale contact 8A sur AC1 250V - B30030Vcc 1A Service auxiliaire

Courant maximum sur la borne 2.2 12ASorties à relais bornes 7-8Type de contact 1 NO

Portée nominale contact 8A sur AC1 250V - B30030Vcc 1A Service auxiliaire

Sorties à relais bornes 9-10-11 et 12-13-14 Type de contact 1 contact NO/NF

Portée nominale contact 8A sur AC1 250V - B30030Vcc 1A Service auxiliaire

Lignes de communication

Interface série RS232 Vitesse de transmission de 1200…38400 baudsConnexion par l’intermédiaire du connecteur RJ6/6

Interface série RS485(261 94 uniquement)

Isolée avec vitesse de transmission programmable 1200…38400 bauds. Connexion par l’intermédiaire de bornes extractibles

IsolationTension nominale d’isolation (Ui) 690VConditions ambiantes de fonctionnementTempérature d’utilisation -20…+60°CTempérature de stockage -30…+80°CHumidité relative <90% Pollution ambiante maximum Degré 3Catégorie de surtension 3BranchementsType de bornes ExtractiblesSection des conducteurs (min. et max.) 0,2…2,5 mm2 (24÷12 AWG)Couple de serrage 0,5 Nm (4,5 LBin)BoîtierMatériau Thermoplastique LEXAN 3412RType EncastréDimensions L x H x P 144 x 144 x 94mmDegré de protection IP41 sur partie frontale, IP20 sur partie arrièrePoids 950gRéférences normativesIEC/EN 61010-1, IEC/EN 61000-6-2, CISPR 11/EN 55011, IEC/EN 61000-3-2, IEC/EN 61000-3-3, IEC/EN 60068-2-61, IEC/EN 60068-2-27, IEC/EN 60068-2-6, UL508 C22.2-N°14-95

Page 27: Electronic Control Box Manual -Y1958C

October 08

EElleeccttrroonniiccCCoonnttrrooll BBooxx

Item 261 93 – Item 261 94

Y1958C

Page 28: Electronic Control Box Manual -Y1958C
Page 29: Electronic Control Box Manual -Y1958C

Contents

29

1. General features . . . . . . . . . . . . . . . . . . 301.1 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . 301.2 Description . . . . . . . . . . . . . . . . . . . . . . . . 301.3 Applications . . . . . . . . . . . . . . . . . . . . . . . 301.4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . 301.5 Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

2. Description of the front panel . . . . . . . . 312.1 Selection keys . . . . . . . . . . . . . . . . . . . . . . 312.2 Measurement selection . . . . . . . . . . . . . . . . 322.3 LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

3. Operating mode . . . . . . . . . . . . . . . . . . . 343.1 Reset mode (red LED of RESET key) . . . . . . . . 343.2 Manual mode (red LED of MAN key) . . . . . . 353.3 Automatic mode (red LED of AUT key) . . . . . . 353.4 Off-load test mode (without load) . . . . . . . . . . 353.5 On-load test mode (under load) . . . . . . . . . . . 35

4. Applications . . . . . . . . . . . . . . . . . . . . . . 364.1 Utility-to-generator Application . . . . . . . . . . . 364.2 Utility-to-utility Application . . . . . . . . . . . . . . . 36

5. Circuit breakers Control . . . . . . . . . . . . 375.1 With feedback (default setup) . . . . . . . . . . . 375.2 Without feedback . . . . . . . . . . . . . . . . . . . 38

6. Voltage controls . . . . . . . . . . . . . . . . . . . 39

7. Programming . . . . . . . . . . . . . . . . . . . . . 417.1 Setting the parameters . . . . . . . . . . . . . . . . . 417.2 Table of menus . . . . . . . . . . . . . . . . . . . . . . 427.3 P0 menu - Nominal data . . . . . . . . . . . . . . . 427.4 P1 menu - General data . . . . . . . . . . . . . . . 437.5 P2 menu - Main line voltage control . . . . . . . 447.6 P3 menu - Secondary line voltage control . . . . 457.7 P4 menu - Programmable inputs . . . . . . . . . . . 467.8 P5 menu - Programmable outputs . . . . . . . . . 467.9 P6 menu - Serial communication . . . . . . . . . . 47

8. Diagnostic messages . . . . . . . . . . . . . . . 48

9. Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . 49

10. Connections . . . . . . . . . . . . . . . . . . . . . . 51

11. Technical features . . . . . . . . . . . . . . . . . 52

Page 30: Electronic Control Box Manual -Y1958C

1. General features

30

1.1 Versions• 261 93 - Standard version • 261 94 - Evoluted version + interface RS-485

1.2 Description• Electronic Control Box - microprocessor• Two inputs of three-phase voltage measurement • Power supply DC 12-24-48 VDC• Power supply AC 220-240 VAC• 2 LED displays, 3 digits 7 segments • 20 status and measurement LED indicators

• 8-key membrane keypad• RS-232 serial interface for set-up, remote control

and supervision• RS-485 opto-isolated interface for MODBUS pro-

tocol (261 94)• 2 programmable digital inputs • 3 programmable relay outputs (1NO + 2 C/O)

1.3 Applications• Changeover between utility-to-utility, utility-to-

generator• Control of motorized circuit breakers, motorized

switches • Start/stop generator• Three-phase, two-phase or single-phase voltage

controls

• L-L voltage (or L-N voltage in case of monophaselines)

• Controls on minimum voltage, maximum voltage,phase loss, asymmetry, minimum frequency, max-imum frequency, with independent enabling anddelay

• Voltage thresholds with programmable hysteresis

1.4 Installation• Install the electronic control box according to the

wiring diagrams shown in the last pages of themanual

• Use the right wiring diagram for the application

• Set the parameters according to the requiredwiring diagram, paying special attention whenprogramming the inputs / outputs

1.5 Supply• 261 93 and 261 94 have a double power sup-

ply circuit, that means that they can operate withboth AC and DC supply or with only one of thetwo indifferently

• In presence of both power supplies, the energy istaken from the AC source

Page 31: Electronic Control Box Manual -Y1958C

2. Description of the front panel

31

• The front panel of the electronic control box hastwo LED displays showing the voltages of the twopower sources with their correspondent keys – (A)for Main line and (B) for Secondary line – whichallows to select the measurements.

• The following keys: SET (E) - AUT (F) - MAN (G) -RESET (H) allow to select the operating mode,which is indicated by the corresponding LED.

• A mimic diagram is located at the center of thefront panel; it shows the status of the circuit break-ers for load connection.

• Two keys – (C) and (D) – can open and close thecircuit breakers (buttons are active only after press-ing the MAN key).

2.1 Selection keys

A B

E

F

G

H

C D

Page 32: Electronic Control Box Manual -Y1958C

32

• When the key located under each display (A) and(B) is pressed several times, it will be possible to viewthe various measurements of the line sequentially.

• Line-to-line voltages, line-to-neutral voltages (in caseof single-phase lines) are available for each line.

• The combinations of the red LEDs indicate whichmeasurement is selected. The list of measurementsmay change depending on whether the electroniccontrol box is set up for the three-phase, two-phaseor single-phase control.

• After 1 minute without touching the key, the meas-urement returns to the default measurement, whichmay be the first voltage line-to-line or the first volt-age line-to-neutral, depending on how the voltagecontrol is set up.

• In case of alarms or messages, the display will beoccupied by the alarm code. By pressing the selection key, it is possible totemporarily hide the alarm and access the meas-urements.

2.2 Measurement selection

Example of a list of measurements on an electronic control box set up for a

three-phase control.

• The front panel has some LEDs which indicate the status of the circuit breakers controlled by the electroniccontrol box.

2.3 LEDs

ALARM LED(red)

POWER SUPPLY LED(green)

SET key LED(red)

AUT key LED(red)

MAN key LED(red)

RESET key LED(red)

Led L1/L2/L3Presence of voltage

on main line (red)

Main line / secondary line CONTROLS LED(two-colors)

Status LED, main line circuit breaker

Status LED, secondary line circuit breaker

Led L1/L2/L3Presence of voltage on

secondary line (red)

Page 33: Electronic Control Box Manual -Y1958C

33

• The following table describes the meaning of the various LEDs.Some of them are bicolor and have a different meaning according to the color.

✱ If the auxiliary contacts have been connected, the LED will represent the status of the circuit breakers, otherwise it willremain off.

✱✱ If the contacts have been connected properly, the LED will represent the status of the circuit breakers, otherwise theLEDs will remain off.

LED On Off Flashing

ALARM No alarm enabled One or more alarms enabled (RED)

POWER SUPPLY Device powered (GREEN) No power

OPEN/CLOSE CONTROL

Close control (RED)Open control (GREEN) No control

OPEN/CLOSED �Circuit breaker closed

(RED)Circuit breaker open

(GREEN)

Auxiliary contactsnot connected

DISCONNECTED �� Circuit breaker not inserted in its base

Circuit breaker inserted or not-inserted-control

disabled

TRIPPED �� Circuit breaker trippedCircuit breaker not

tripped or AL contact not connected

PRESENCEL1/L2/L3 Voltage present No voltage

1HZ = Time of presence/absence in progress5HZ = Display measurements selection

Page 34: Electronic Control Box Manual -Y1958C

3. Operating mode

34

• The four keys SET / AUT / MAN / RESET canbe used to select the required operating mode,which will be indicated when the correspondingred LED lights up.

• If the LED indicating the selected operating modeflashes, it means that the device is communicatingthrough the serial interface and that it could exe-cute remote commands, including the modechange as well.

A B

E

F

G

H

C D

• The electronic control box does not execute oper-ations but it just displays the status of the voltagesand the circuit breakers.

• The opening and closing control outputs of theswitches remain all open, hence allowing for themanual control from the front side of the motor con-trols. If the emergency input is activated, the unitwill in any case order the opening of the switches.

• The generator control output will set up for switch-ing off the group.

• The status alarms of the circuit breakers aredisabled.

• When an alarm occurs, it must be reset by press-ing the RESET key. If you are already in this oper-ating mode, press the RESET button again.

3.1 Reset mode (red RESET key LED)

Page 35: Electronic Control Box Manual -Y1958C

• In automatic mode, the device independently exe-cutes both opening and closing operations of thecircuit breakers as well as the startup and shut-down of the generator, if any.

• When the main line (MAIN) goes beyond the lim-its, after the set delay times, the device disconnectsthe load from the main line and connects it to thesecondary line (SEC), thus controlling both the

startup of the generator, if any, and thechangeover times between the circuit breakers.

• When the main line falls within the limits, the deviceswitches again the load on it and determines thecooling cycle, if required, of the generator.

• The automatic cycles of operation vary accordingto the type of application (utility-to-utility, utility-to-generator).

35

P l e a s enote: Theexecution ofthis testinvolves trans-ferring theload, hence apower failureduring thechangeoverdue to theinterlockingtimes.

3.2 Manual mode (red MAN key LED)• The manual mode allows the operator to electrical-

ly open/close the circuit breakers with the specialkeys located at the front side of the device.

• In this mode, the voltages are constantly monitoredbut the device just displays their status.

• When one of the control keys is pressed for atleast 300 ms, the electronic control box changesthe status of the circuit breakers from open toclosed and vice-versa.

• If a command is given to close a circuit breakerwhile the other is already closed, the unit will ini-tially open the other circuit breaker, wait for the

interlocking time and then it will close the requiredcircuit breaker.

• In manual mode, all the status alarms of the circuitbreakers (disconnected and tripped) are disabled.The anomalous condition is signaled on the LEDbut it will not be stored or dealt with as an alarm.

• It is possible to manually control the startup andshutdown of the generator by holding down thekey (G) MAN for 5 consecutive seconds. As longas the manual mode is kept, the status of the gen-erator will remain the one required.

3.3 Automatic mode (red AUT key LED)

• By starting from the automatic mode and by press-ing the (F) key for 5 seconds, it will be possible totest the generator for 5 minutes.

• The generator is manually started in order to checkits operation but since the electronic control box isin automatic mode, the voltage controls willremain active.

• By doing so, it is possible to verify the correctoperation of the generator, thus maintaining

the coverage of the load. Under normal condi-tions, the load remains connected to the mainline, hence the generator operates with noload (off-load generator).

• The execution of the off-load test is determined byTES written steadily on the display.

• To end the execution of the test in advance, pressthe (F) key again for 5 seconds or start the resetmode.

• By starting from the automatic mode and by press-ing the (F) and (D) key simultaneously for 5 con-secutive seconds, it will be possible to carry out anoperational test (on-load test) which will totally sim-ulate a lack of the power line voltage lasting oneminute.

• Hence, the unit behaves exactly as if the line hasfallen out of the limits, thereby using all pro-

grammed times and parameters for thechangeover so as to verify their adequacy.

• The execution of the on-load test is determined byTES flashing on the display.

• To end the execution of the test in advance, repeatthe procedure with keys (F) and (D) for 5 secondsor start the reset mode.

3.5 On-load test mode

3.4 Off-load test mode

Page 36: Electronic Control Box Manual -Y1958C

4. Applications

36

4.1 Utility-to-generator Application• In the Utility-to-generator application (U-G, default

setup) the load is normally connected to the mainline. If there is an anomaly on the line or in caseof a transfer signal set from the outside, a start sig-nal will be sent to the generator which supplies thesecondary line.

• When the voltage of the generator reaches theprogrammed limits, the electronic control box willorder the changeover on the secondary line.

• When the main line returns, the load is transferredagain and the generator is kept in operation withno load for a certain period of time so as to allowits cooling.

• The unit sends a start/stop command to the groupthrough a relay output and can receive digital sig-nals from the group indicating its status throughprogrammable inputs.

4.2 Utility-to-utility Application• In the utility-to-utility application (U-U), the load is

normally connected to the main line and thechangeover to the secondary line occurs if there is

an anomaly on the main line or in case there is atransfer signal set from the outside.

Page 37: Electronic Control Box Manual -Y1958C

5. Circuit breakers control

37

• The circuit breakers control is carried out throughtwo separate relays, one for closing and one foropening.

• In reset mode, both control relays remain open,except for the emergency condition where theopening can be controlled.

• In case of an anomaly on the switch, hence caus-ing an alarm, the control outputs will both beopened till the resetting of the alarm.

• There are two separate modes for controlling thecircuit breakers. These can be selected by usingthe parameter P1.03

The auxiliarycontacts of the

circuit breakersare wired intheir imputs.

With the feedback is

necessary to usefor the opening

operation ofDPX

250-630-1600the shunth trip

relay or theundervoltage

relay.

Example of a changeover with feedback, assuming a utility-to-utility commutation.

The feedback input status is shown in blue. The status of the control outputsis shown in green. The changeover time

is shown in yellow.

0.5 s

15 s

0.5 s

LED VMAIN OK

LED VSEC OK

46

115

18

3

1s

1s

15 s

5.1 With feedback (default setup)• The status indicated by the two-color front LED is

the one detected by the auxiliary contacts.• The timeout alarms are enabled. They are gener-

ated if the circuit breakers do not reach therequired position within a programmable timeP1.04 or immediately if they change positionwhen no command has been sent.

• The control outputs are timed. When the circuitbreaker has executed the required operation, the

output still remains energized for a certain periodof time (+1 second during closing and +15 sec-onds during opening, in order to allow the springsof the motor operators to be completely charged)and then it is released.

• The normal status of the control outputs is open. • The interlocking times start when the first circuit

breaker is actually opened, detected by the input,and last for 0.5 steady seconds.

Page 38: Electronic Control Box Manual -Y1958C

38

5.2 Without feedback

The auxiliarycontacts of the

circuit breakersare not wired in

their inputs,hence the electronic

control box isnot informed on

their actualstate.

Example of a changeover with no feedback. The actual status of the circuit

breakers is shown in blue. The status of the control outputs is shown in green.

The changeover time is shown in yellow.

6 sec 6 sec

LED VMAIN OK

LED VSEC. OK

INT. MAIN

INT. SEC.46

13

• The circuit breakers status LEDs remain off. • The timeout alarms are disabled.• The Opening/Closing control outputs remain

constantly in the required position for the circuitbreaker.

• The changeover times between the opening ofa switch and the closing of another start duringthe commutation of the outputs and are steadyat 6 sec.

Page 39: Electronic Control Box Manual -Y1958C

6. Voltage controls

39

• Any condition required to determine whether asupply source is or is not suitable is determined bythe user through the P0 menu (system nominaldata) and the P2 and P3 menus (voltage control,main line and secondary line, respectively).

• It is possible to set up the system nominal data,such as nominal voltage and frequency, throughthe P0 menu, which will be used as a referencefor setting up the percentage thresholds of the fol-lowing menus.

• It is possible to set up a TV transformation ratio incase a lower voltage, relative to the actual voltageof the system, is applied to the voltage inputs ofthe unit. Here, again, the display and the setup ofthe thresholds will be executed in actual sizesreferred to the system.

• The electronic control box can be programmedto perform voltage controls on three-phase, two-phase or single-phase nets (via the P0.03parameter).

Control 261 93 261 94 Description

Minimum voltage • • One or more phases too low

Maximum voltage • One or more phases too high

Phase failure • • Threshold under which the device can operate faster compared to a normal reduction

Asymmetry (unbalance) • Phases included in the Maximum-Minimum interval, yet too different between each other

Minimum frequency • Frequency too low

Maximum frequency • Frequency too high

Sequence of phases • Reverse rotation of phases

The following describes the anomalies monitored by the voltage control.Columns 261 93 and 261 94 point out the presence of the function within their unit models.

Page 40: Electronic Control Box Manual -Y1958C

40

• Each anomaly has an independent delay time.The anomaly must last consecutively longer thanthe time specified for invalidating the voltage pres-ence signal.

• All controls, except for the minimum voltage con-trol, can be excluded separately by setting therelated parameter to OFF.

• The minimum and maximum voltage limits arespecified by setting up two thresholds each, onewhich determines the point beyond which the volt-age is no longer considered acceptable (e.g.P2.01) and the other, closer to the nominal volt-age, which determines the point in which itbecomes compatible again (e.g. P2.02). The dis-

tance between these two thresholds determines thehysteresis. For instance, it may be considered thatwhen the nominal value is below 80%, the voltagemay no longer be useable and that in order to beconsidered useful, it must rise over 85%, therebydetermining a 5% hysteresis.The same concept applies to the maximumvoltage.

• As for the frequency thresholds, there is a fixed 1%hysteresis of the nominal frequency.

• The retrieval after a phase failure occurs when thevoltage rises above the minimum voltage retrievalthreshold.

Example of variation of the main line voltage within the minimum and maximum thresholds and relative hystereses, with indication of the

presence / absence delay times. Theexample considers the secondary linevoltage absent with its circuit breaker

open, hence the changeover times arenot shown. The INTERR. bar represents the required status

of the main line switch.

P2.04

P2.05

P2.02

V MAIN

P2.01

LED VOK

INTERR.P2.03 P2.15 P2.15P2.06 P2.05<

Page 41: Electronic Control Box Manual -Y1958C

7. Programming

41

7.1 Setting the parameters

Key E- Goes to Setup - Exits to higher level

Key AIt moves

at same level

Key B- Enable modification- Confirms setup

Key FIncreases parameter value

Key GDecreases parameter value

Key HGoes to lower level

• Press the H and E keys together for 5 consecutiveseconds to start programming

• The flashing LED of the E key indicates that pro-gramming is in progress

• Main line display indicates the parameter selectedvia the code (for instance P0.01)

• Secondary line display indicates the set value ofthe selected parameter (for instance 400)

• Changing of parameters of the same group bypressing the key A

• Movement to next group with key E• Movement to previous group with key H

• Enable modification of the parameter with key B• Increase the value of the selected parameter with

key F• Decrease the value of the selected parameter with

key G• Confirm by pressing key B• While modifying a parameter, the secondary line

display flashes with the current value of the param-eter. In this situation it is not possible to move toanother parameter without first confirming

• Exit from Setup by pressing E and H simultaneously

Page 42: Electronic Control Box Manual -Y1958C

42

7.2 Table of menus

7.3 P0 menu - Nominal data

Menu Description

P0 System nominal data

P1 General Data

P2 Main line voltage control

P3 Secondary line voltage control

P4 Programmable inputs

P5 Programmable outputs

P6 Communication port

Setup Description Range Default

P0.01 B Nominal voltage Ue 100 … 690 VAC 380 VAC

P0.02 B Transformation ratio TV 1.00 … 9.99 1.00

P0.03 B Type of Network3Ph = Three-phase2PH = Two-phase1Ph = Single-phase

3Ph

P0.04 B Nominal frequency Fe 50H = 50Hz60H = 60Hz 50Hz

P0.05 B Nominal battery voltage

OFF = No battery12 = 12 VDC24 = 24 VDC48 = 48 VDC

OFF

P0.01 - Nominal voltage used for calculating the thresholds P0.02 - Leave default setup in case a TV is not used P0.04 - Nominal frequency used as a reference for calculating the frequency thresholds P0.05 - Used for the alarms on the battery voltage

Page 43: Electronic Control Box Manual -Y1958C

43

7.4 P1 menu - General dataSetup Description Range Default

P1.01 Type of application U-G = Utility-to-GeneratorU-U = Utility-to-Utility U-G

P1.02 Control of phase sequenceOFF - Disabled123 - Direct321 - Opposite

OFF

P1.03 Changeover control FEE - With feedback NOF - Without feedback FEE

P1.04 Circuit breakers Timeout OFF / 1…900s 5 s

P1.05 Enable control of withdrawn OFF (Control disabled) ON (Control enabled) OFF

P1.06 Maximum time load not powered (A07 alarm delay) OFF / 1…3600s OFF

P1.07 Startup delay time, generator 0 …. 900 s 1 s

P1.08 Cooling time, generator 1…3600s 120 s

P1.09 Minimum battery voltage threshold OFF / 70…100% 75%

P1.10 Maximum battery voltage threshold OFF / 110…140% 130%

P1.11 Battery threshold delay time 0…60 s 10 s

P1.01 - Determines the type of commutation (utility-to-utility/utility-to-generator) P1.04 - If, after sending an opening or closing command to a switch, it does not place itself correctly within this time,

the A03 or A04 alarms will be generatedP1.05 - Enable the control only if their contacts are wiredP1.06 - If both sources are simultaneously unavailable in automatic mode for a period of time longer than P1.06, the

A07 alarm will be generatedP1.07 - Time between the line failure used below and transmission of the startup signal to the generator on the secondary

line.It is a time which is independent from the circuit breaker opening time

P1.08 - Time whereby the generator is left in operation in order to cool down after being disconnected from the load

The highlightedparameters are

included only inversion 261 94

Page 44: Electronic Control Box Manual -Y1958C

44

7.5 P2 menu - Main line voltage controlSetup Description Range Default

P2.01 Minimum voltage threshold - release 70…98% Ue 85% Ue

P2.02 Minimum voltage threshold - retrieval 75…100% Ue 90% Ue

P2.03 Minimum voltage threshold delay 0.1 …. 900 s 1.0 s

P2.04 Maximum voltage threshold - release 102…120% Ue / OFF 115% Ue

P2.05 Maximum voltage threshold - retrieval 100…115% Ue 110% Ue

P2.06 Maximum voltage threshold delay 0.1 …. 900 s 1.0 s

P2.07 Threshold of phase failure 60 … 85% Ue / OFF 70% Ue

P2.08 Phase failure threshold delay 0.1 … 30.0 s 0.1 s

P2.09 Voltage unbalance threshold 1 … 20% Ue / OFF 10 %

P2.10 Voltage unbalance threshold delay 0.1 … 900 s 5.0 s

P2.11 Threshold of minimum frequency OFF / 80… 100% Fe 95% Fe

P2.12 Minimum frequency threshold delay 0.1 … 900 s 5.0 s

P2.13 Threshold of maximum frequency 101 … 120% Fe / OFF 105% Fe

P2.14 Maximum frequency threshold delay 0.1 … 900 s 3.0 s

P2.15 Voltage return delay on main line within the limits (when circuit breaker secondary line open) 1 … 3600 s 10 s

P2.16 Voltage return delay on main line within the limits (when load on secondary line) 1 … 3600 s 60 s

The highlightedparameters are

included only inversion 261 94

P2.01 - P2.02 - P2.03 - The first two parameters determine the minimum voltage threshold and its hysteresis whenretrieved. P2.02 cannot be set to a value which is lower than P2.01. P2.03 determines the delay time for the activationof this protection. See chapter on Voltage controlsP2.04 - P2.05 - P2.06 - The first two parameters determine the maximum voltage threshold and its hysteresis whenretrieved. P2.05 cannot be set to a value which is higher than P2.04. Setting P2.04 to OFF will disable the maximumvoltage control. P2.06 determines the maximum voltage tripping delay. See chapter on Voltage controlsP2.07 - P2.08 - Voltage threshold under which there is an activation due to phase failure, usually faster than thereduction. The delay time for the phase failure is specified by P2.08P2.09 - P2.10 - P2.09 determines the maximum unbalance threshold between the phases, referred to the nominalvoltage; P2.10 determines the relative tripping delay. This control can be disabled by setting P2.09 to OFF P2.11 - P2.12 - Threshold (disabled) and minimum frequency tripping delay P2.13 - P2.14 - Threshold (disabled) and maximum frequency tripping delayP2.15 - Return delay time on main line within the limits, used when the source of the secondary line is not available.Normally shorter than P2.16: since the load is not powered, it is necessary to supply voltageP2.16 - Return delay time on main line within the limits, used when the load can be connected to the secondary line.Normally longer than P2.15: since the load is “covered”, it is possible to wait longer before considering the voltagestably retrieved

Page 45: Electronic Control Box Manual -Y1958C

45

7.6 P3 menu - Secondary line voltage controlSetup Description Range Default

P3.01 Minimum voltage threshold - release 70…98 % Ue 85 % Ue

P3.02 Minimum voltage threshold - retrieval 75…100 % Ue 90 % Ue

P3.03 Minimum voltage threshold delay 0.1 …. 900 s 1.0 s

P3.04 Maximum voltage threshold - release 102…120 % Ue / OFF 115 % Ue

P3.05 Maximum voltage threshold - retrieval 100…115 % Ue 110 % Ue

P3.06 Maximum voltage threshold delay 0.1 …. 900 s 1.0 s

P3.07 Threshold of phase failure 60 … 85% Ue / OFF 70 % Ue

P3.08 Phase failure threshold delay 0.1 … 30.0 s 0.1 s

P3.09 Voltage unbalance threshold 1 … 20 % / OFF 10 %

P3.10 Voltage unbalance threshold delay 0.1 … 900 s 5.0 s

P3.11 Threshold of minimum frequency 99 … 80 % Fe / OFF 95 % Fe

P3.12 Minimum frequency threshold delay 0.1 … 900 s 5.0 s

P3.13 Threshold of maximum frequency 101 … 120% Fe / OFF 105 % Fe

P3.14 Maximum frequency threshold delay 0.1 … 900 s 3.0 s

P3.15 Voltage delay of secondary line within the limits 1 … 3600 s 20 s

The highlightedparameters are

included only inversion 261 94

Note: Forexplanationson the opera-tion ofparameters,see previouspage con-cerning themain linemenu.

Page 46: Electronic Control Box Manual -Y1958C

7.7 P4 menu - Programmable inputsSetup Description Range Default

P4.01 Programmable input function 1See list ìP rogrammable

input functions”

ForForced changeover on secondary line

P4.02 Programmable input function 2In.rInhibition return on main line

Programmable input functions

Function Description Notes

OFF OFF Input not used

For Forced changeover on secondary line

When closed, it forces the changeover on the secondary line even if main line voltage is within the limits. Re-commutation occurs on the main line when the input is released or in case the secondary line voltage is not within the limits

IN.R Inhibition return on main line

In automatic mode, when closed, it blocks the automatic return on the main line after the main line voltage has returned within the limits. It is used for preventing the second power cutoff, due to the re-transferal, from occurring automatically in an unexpected moment

S.GE Generator voluntary Start/stop In automatic mode, when closed, it starts up the generator

EME Emergency NC contact which, if opened, opens both circuit breakers and generates an alarm

G.rE Generator ready If closed, it refers to a Generator in automatic mode and not in alarm mode. If opened, it generates an alarm code

Loc Keyboard total lock If closed, it locks all keyboard functions except for measurement views

L.PA Lock parameter access If closed, it locks the access to setups

46

7.8 P5 menu - Programmable outputsSetup Description Range Default

P5.01 Output functionProgrammable 1 See list “Programmable output functions” S.GE

Start generator

P5.02 Output functionProgrammable 2 See list “Programmable output functions” RDY

ATS Ready

P5.03 Output function Programmable 3 See list “Programmable output functions” ALA

Global alarm

Page 47: Electronic Control Box Manual -Y1958C

47

Programmable output functions

Function Description Notes

OFF OFF Output not used

S.GE Consent to start up the generatorWhen closed, the generator must be inactive. Contact opens to start generator. If the unit is not powered, the generator starts

RDY Automatic transfer switch ready Indicates unit automatically and without alarms, ready to start operating

ALA Global alarm De-energizes in case of an alarm

MCMMinimum coilMain line Main line switch voltage minimum opening coil command

MCSMinimum coilSecondary line

Secondary line switch voltage minimum opening coil command

L.SH Non-priority load disconnection

Disconnection of the non-priority loads that are not powered by the secondary line branch. It is also controlled on the secondary line.Contact which is closed before the secondary line closing command and opened before the main line closing command

7.9 P6 menu - Serial communicationSetup Description Range Default

P6.01 Serial address RS-232 1…245 01

P6.02 Speed (baudrate) RS-232

240 = 2400 480 = 4800960 = 9600 19.2 = 19200 38.4 = 38400

960

P6.03 Protocol RS-232 Rtu = Modbus RTUASC = Modbus ASCII RTU

P6.04 Parity RS-232No = NoneEVE = EvenOdd = Odd

No

P6.05 Serial address RS-485 1…245 01

P6.06 Speed (baudrate) RS-485

240 = 2400 480 = 4800960 = 9600 19.2 = 19200 38.4 = 38400

960

P6.07 Protocol RS-485 Rtu = Modbus RTUASC = Modbus ASCII RTU

P6.08 Parity RS-485No = NoneEVE = Even Odd = Odd

No

P6.01…P6.04 - They determine the transmission format and the protocol used on communication port RS-232P6.05…P6.08 - They determine the transmission format and the protocol used on communication port RS-485,

available only on 261 94

The highlightedparameters are

included only inversion 261 94

Page 48: Electronic Control Box Manual -Y1958C

8. Diagnostic messages

48

The following messages can be displayed, at different moments:

Code Description

- - -(Dashes) - The interlocking time is in progress.They are displayed from the side in which the load is being transferred

Sta (Start) - Indicates that the Start Generator command has been sent

Coo (Cooling) - Indicates that the generator is being left running for the cooling

Tes(Test) - When steady, it indicates that an off-load test - namely a power unit test with the voltage controls active - is currently in progress

Tes(Test) - When flashing, it indicates that an on-load test, namely an automatic net failure simulation, is currently in progress

Loc (Locked) - It indicates that the keyboard function one is trying to execute is locked

Page 49: Electronic Control Box Manual -Y1958C

9. Alarms

49

• When the unit is running, it is possible to verify anumber of abnormal situations which are signaledin different ways.

• Some alarms (tripped, withdrawn) have a dedi-cated LED which begins to flash when thealarms go on.

• Other alarms are signaled through a code whichconsists of an A (alarm) and a number indicatingwhich alarm it is. This code will be flashing on oneof the displays. If the code refers to the main linebranch, the alarm will be displayed on the left.Conversely, if the code refers to the secondary linebranch or if it is a generic alarm (e.g. battery), itwill be displayed on the right.

• When an alarm goes on, the red LED “ALARM”flashes in sync with the dedicated LED or with thealarm code.

• The Global alarm relay output is de-energized dur-ing alarm conditions whereas it is energized undernormal conditions. If the unit does not operate dueto a failure or power supply problems, it will gen-erate an alarm condition on its contact.

• Some alarms are automatically reset when theconditions generating them fail to work.

• Other alarms, described in the chart in the RIT col-umn, are retentive, thus they are stored.

• Once the alarm has been stored, the abnormalconditions must be eliminated in order to be reset.Also, the operator must press the RESET key orsend a special message via the serial interface.

Page 50: Electronic Control Box Manual -Y1958C

50

Alarm list

Code Led Description alarm Causes RIT RESET MAN AUT

A01 Battery voltage too low

This occurs if the P0.06 parameter is OFF and if the battery voltage measured remains lower than the threshold % set with P1.09 for the time set with P1.11

YES YES YES YES

A02 Battery voltage too high

This occurs if the P0.06 parameter is not OFF and if the battery voltage measured remains higher than the threshold % set with P1.10 for the time set with P1.11

YES YES YES YES

A03 Main line switch timeout

It is generated if the main line switch does not move to the position controlled by the unit within the time determined by P1.04 or if it comes out of the required position on its own. The alarm can be generated when closing and when opening. If there is no power on both lines, the alarm will not be generated

YES NO NO YES

A04 Secondary line switch timeout

It is generated if the secondary line switch does not move to the position controlled by the unit within the time determined by P1.04 or if it comes out of the required position on its own. The alarm can be generated when closing and when opening. If there is no power on both lines, the alarm will not be generated

YES NO NO YES

A05 Main line incorrect phase sequence

If enabled by parameter P1.02, it is generated when a phase sequence – different from what has been specified in P1.02 – is detected, after a delay of about 500 ms.In order for the sequence to be detected, all three phases must be > 50VAC

YES YES YES YES

A06Secondary line incorrect phase sequence

As the previous, referred to the secondary line voltage YES YES YES YES

A07 Timeout load not powered

The load was left with no voltage for a period of time longer than P1.06. The main line and the secondary line were not available (no power or switch not closed)

NO NO NO YES

A08 Generator not available

One of the programmable inputs is set to “Generator ready”, hence signaling that the generator is not available NO YES YES YES

A09 Emergency One of the programmable inputs is set to the emergency button and the corresponding input contact is open YES YES YES YES

A11Main line frequency outside limits

The frequency of the main line is not within the limits determined with P2.11 and P2.13 NO YES YES YES

A12Secondary line frequency outside limits

The frequency of the secondary line is not within the limits determined with P3.11 and P3.13 NO YES YES YES

A13 Main line voltage asymmetry

The difference between the higher and lower voltage between lines of the main line exceeds the limit determined with P2.09

NO YES YES YES

A14 Secondary line voltage asymmetry

The difference between the higher and lower voltage between lines of the secondary line exceeds the limit determined with P3.09

NO YES YES YES

•Main/secondary line withdrawn.Switch removed

The withdrawn input control is enabled by parameter P1.05 and the corresponding main line or secondary line input contact is open

YES VIS VIS YES

Main/secondary line tripped.Protection activation. Switch

The tripped input contact it is closed. This condition is ignored for 15 seconds which begins immediately after giving the command to open a switch so as to avoid false signalings when using a release coil

YES VIS VIS YES

The highlightedalarm are

included only inversion 261 94

Page 51: Electronic Control Box Manual -Y1958C

10. Connections

51

Mors. Function

1 Main line circuit breaker opening

2 Common main line commands

3 Main line circuit breaker closing

4 Secondary line circuit breaker opening

5 Common secondary line commands

6 Secondary line circuit breaker closing

7 Programmable relay 1 (Default function = Start/Stop generator)

8 Common programmable relay 1

9

Programmable relay 2/NC (Default function = Unit ready)

10 Programmable relay 2/NO (Default function = Unit ready)

11

Common programmable relay 2

12

Programmable relay 3/NC (Default function = Global alarm)

13Programmable relay 3/NO (Default function = Global alarm - closed when ok)

14

Common programmable relay 3

15 AUX input of Main line circuit breaker

Mors. Function

16 AL input of Main line circuit breaker

17 DISCONNECTED input of Main line circuit breaker

18 AUX input of Secondary line circuit breaker

19 AL input of Secondary line circuit breaker

20 DISCONNECTED input of Secondary line circuit breaker

21 Programmable input 1 (Default = Forcing on secondary line)

22 Programmable input 2 (Default = Inhibition return on main line)

23 + VDC supply

24 – VDC supply

25 Common for inputs (from 15 to 22)

26 AC supply

27 AC supply

MAIN L1 L2 L3 N

Main line three-phase measurement input

SEC. L1 L2 L3 N

Secondary line three-phase measurement input

Page 52: Electronic Control Box Manual -Y1958C

11. Technical features

52

Auxiliary power supplyDC power supply operating limits 9...70VDC (Us=12-24-48VDC)AC power supply operating limits 187…264VAC (Us=220…240VAC)Frequency 45…65HzMax. absorbed power 6VA (Us=240VAC)Max. dissipated power 4,8W (Us= 240VAC or Us=48VDC)Max. absorbed current 420mA to 12VDC; 200mA to 24VDC; 100mA to 48VDCMicro-breaking immunity time 50msVoltage inputsMax. rated voltage (Ue) 690VAC phase-phase (400VAC phase-neutral)UL usage data 600VAC phase-phase (340VAC phase-neutral)Measuring range 80…800VAC phase--phaseFrequency range 45…65HzType of measurement TRMS (true effective value)Measurement input impedance > 1,1 M Ω phase-phase and > 0,5 M Ω phase-neutralType of connection One, two or three phaseMeasurement error Class 0,5 ±0,25% f.s. ±1digitDigital inputsType of input NegativeInput current ≤10mAInput current “0” state ≤1,5 (typical 2,9V)Input current “1” state ≥5,3 (typical 4,3V)Input signal delay ≥50msecRelay outputs terminals 1-2 and 4-5Type of contact 1 NONominal range at 250VAC 12AContact nominal range 16A in AC1 250V - B300Maximum current on terminal 1.2 12ARelay outputs terminals 2-3 and 5-6Type of contact 1 NO

Contact nominal range 8A in AC1 250V - B30030VDC 1A Auxiliary service supply

Maximum current on terminal 2.2 12ARelay outputs terminals 7-8Type of contact 1 NO

Contact nominal range 8A in AC1 250V - B30030VDC 1A Auxiliary service supply

Relay outputs terminals 9-10-11 and 12-13-14Type of contact 1 change-over contact

Contact nominal range 8A in AC1 250V - B30030VDC 1A Auxiliary service supply

Communication interfaces

RS232 serial interface Programmable Baud-rate 1200…38400 bps Connection via RJ6/6 connector

RS485 serial interface(COM only)

Isolated with programmable Baud-rate 1200…38400 bpsConnection via removable terminals

InsulationRated insulation Voltage (Ui) 690VEnvironmental operating conditions Operating temperature -20…+60°CTemperature -30…+80°CRelative humidity <90% Maximum Pollution degree Degree 3Overvoltage category 3ConnectionsType of terminal RemovableConductor section (min. and max.) 0,2…2,5 mmq (24÷12 AWG)Tightening torque 0,5 Nm (4,5 LBin)HousingMaterial Thermoplastic LEXAN 3412RVersion Flush mountingDimensions L x H x D 144 x 144 x 94mmProtection degree IP41 on front, IP20 on backWeight 950gCertifications and compliance

IEC/EN 61010-1, IEC/EN 61000-6-2, CISPR 11/EN 55011, IEC/EN 61000-3-2, IEC/EN 61000-3-3, IEC/EN 60068-2-61, IEC/EN 60068-2-27, IEC/EN 60068-2-6, UL508 C22.2-N°14-95

Page 53: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

53

Alimentation boitier et moteurs en 12-24-48VdcElectronic Control Box and motors supply in 12-24-48Vdc

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

P0.05 24

ProgrammationSetting

~_

Pour DPX 125/160 ➞ 1000W filtréPour DPX 250/630/1600 et DMX ➞ 1000WFor DPX 125/160 ➞ 1000W filtredFor DPX 250/630/1600 et DMX ➞ 1000W

Moteurs Motors

230Vac / 24Vdc

ref. 04055

Principal Main

Secondaire Sec

23

+

24

-

25 26 27

ALIM. AUX.DC

DC AUXSUPPLY

ALIM. AUX.AC

AC AUXSUPPLY

0V~

220-

240V

~

Co

mm

un e

ntré

esC

om d

igita

l inp

uts

LG1B

Page 54: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

Alimentation boitier en 230Vac et 12Vdc et moteurs en 230VacElectronic Control Box supply 230Vac and 12Vdc and motor supply in 230Vac

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

P1.04 OFF

ProgrammationSetting

Moteurs Motors

ref. 04055

Principal Main

Secondaire Sec

23

+

24

-

25 26 27

ALIM. AUX.AC

AC AUXSUPPLY

0V~

220-

240V

~

Co

mm

un e

ntré

esC

om d

igita

l inp

uts

3A 3A

ALIM. AUX.DC

DC AUXSUPPLY

ref. 0421012Vcc 0,8A

54

LG3

Page 55: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

Relevé de tensions monophaséesSingle-phase voltage inputs

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

P0.03 1Ph

ProgrammationSetting

Principal Main

Secondaire Sec

N N100 - 690 Vac50/60 Hz

1A gG

1A gG

N L1 L2 L3 N L1 L2 L3

RELEVE DE TENSIONVOLTAGE INPUTS

100-690 Vac 50/60 Hz

PRINCIPALMAIN

SECONDAIRE SEC.

55

LG4

Page 56: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

Relevé de tensions monophaséesSingle-phase voltage inputs

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

P0.03 1Ph

ProgrammationSetting

Principal Main

Secondaire Sec

N N100 - 690 Vac50/60 Hz

1A

1A

N L1 L2 L3 N L1 L2 L3

RELEVE DE TENSIONVOLTAGE INPUTS

100-690 Vac 50/60 Hz

PRINCIPALMAIN

SECONDAIRE SEC.

56

LG5

Page 57: Electronic Control Box Manual -Y1958C

57

ParamètreParameter

SchémaWiring diagram

Relevé de tensions biphaséesTwo-phase voltage inputs

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

P0.03 2Ph

ProgrammationSetting

Principal Main

Secondaire Sec.

R S R S

1A gG

1A gG

N L1 L2 L3 N L1 L2 L3

RELEVE DE TENSIONVOLTAGE INPUTS

100-690 Vac 50/60 Hz

PRINCIPALMAIN

SECONDAIRE SEC.

100 - 690 Vac50/60 Hz

LG8

Page 58: Electronic Control Box Manual -Y1958C

58

ParamètreParameter

SchémaWiring diagram

Relevé de tensions biphaséesTwo-phase voltage inputs

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

P0.03 2Ph

ProgrammationSetting

100 - 690 Vac50/60 Hz

PrincipalMain

SecondaireSec.

SSR R

1A

1A

N L1 L2 L3

RELEVE DE TENSIONVOLTAGE INPUTS

N L1 L2 L3

100-690 Vac 50/60 Hz

PRINCIPALMAIN

SECONDAIRE SEC.

LG9

Page 59: Electronic Control Box Manual -Y1958C

59

ParamètreParameter

SchémaWiring diagram

Relevé de tensions triphaséesThree-phase voltage inputs

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

P0.03 3Ph

ProgrammationSetting

Principal Main

Secondaire Sec

N R S T N R S T

1A gG

1A gG

N L1 L2 L3 N L1 L2 L3

RELEVE DE TENSIONVOLTAGE INPUTS

100-690 Vac 50/60 Hz

PRINCIPALMAIN

SECONDAIRE SEC.

100 - 690 Vac50/60 Hz

LG6

Page 60: Electronic Control Box Manual -Y1958C

60

ParamètreParameter

SchémaWiring diagram

Relevé de tensions triphaséesThree-phase voltage inputs

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

P0.03 3Ph

ProgrammationSetting

Principal Main

Secondaire Sec

N R S T N R S T

1A

1A

N L1 L2 L3 N L1 L2 L3

RELEVE DE TENSIONVOLTAGE INPUTS

100-690 Vac 50/60 Hz

PRINCIPALMAIN

SECONDAIRE SEC.

100 - 690 Vac50/60 Hz

LG7

Page 61: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

DPX 125/160 sans feedbackDPX 125/160 without feedback

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

P1.03P1.04P1.05

NOFOFFOFF

ProgrammationSetting

34

53

45

12

12

Mo

teur

seco

urs

Sec

. mot

or

Mo

teur

norm

alM

ain

mot

or

Alim

enta

tio

nél

ectr

ique

des

mo

teur

sTe

nsio

nel

ectr

ic m

otor

s

Violet

Orange

BlueBlack

Red

Black

Red

Violet

Orange

Blue

1213

1415

1718

1920

2122

2324

2526

27N

L1L2

L3N

L1L2

L311

12

34

56

SE

CO

ND

AIR

ES

EC

.P

RIN

CIP

AL

MA

IN

0V~

220-240V~

Commun entréesCom digital inputs

-+

Aux. sec.

Trip sec.

Withdrawn sec.

Input prog. 1

Input prog. 2

Aux. main

Trip main

Withdrawn main

CA normal

SD normal

Contact débro normal

CA secours

SD secours

Contact débro secours

Entrée prog. 1

Entrée prog. 2

BO

ÎTIE

R D

’AU

TO

MA

TIS

ME

ELE

CTR

ON

IC C

ON

TRO

L B

OX

réf:

261

93/

94

RE

LAIS

PR

OG

RA

MM

AB

LE 3

PR

OG

. 3 R

ELA

Y10

0-69

0 Va

c

50/6

0Hz

RE

LEV

E D

E T

EN

SIO

NV

OLT

AG

E IN

PU

TSA

LIM

. AU

X.

AC

AC

AU

XS

UP

PLY

EN

TR

EE

S D

IGIT

ALE

SD

IGIT

AL

INP

UTS

RE

LAIS

SE

CO

UR

SS

EC

. RE

LAY

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

RE

LAIS

NO

RM

AL

MA

IN R

ELA

Y

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

R

ELA

IS P

RO

G.

1P

RO

G. 1

RE

LAY

RE

LAIS

PR

OG

RA

MM

AB

LE 2

PR

OG

. 2 R

ELA

Y

78

910

16

ALI

M. A

UX

.D

CD

C A

UX

SU

PP

LY

DPX 125: verrouillage mécanique non disponible

DPX 125: mechanical interlock not available

61

LG10

Page 62: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

DPX 125/160 avec feedbackDPX 125/160 with feedback

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

34

53

45

12

12

1213

1415

1718

1920

2122

2324

2526

27N

L1L2

L3N

L1L2

L311

12

34

56

Déb

ro s

eco

ndai

reW

ithd

raw

nse

c.

Déb

ro p

rinc

ipal

With

dra

wn

mai

n

3-White

1-Black

2-Red

3-White

1-Black

2-Red

SD

Sec

ond

aire

Trip

sec.

CA

Sec

ond

aire

Aux

. Sec

.C

A P

rinc

ipal

Aux

. mai

n

Mo

teur

seco

ndai

reS

ec. m

otor

Mo

teur

pri

ncip

alM

ain

mot

or

Alim

enta

tio

nél

ectr

ique

des

mo

teur

sTe

nsio

nel

ectr

ic m

otor

s

54-Red

51-Black

52-White

54-Red

51-Black

52-White

11-Black

14-White

12-Red

11-Black

14-White

12-Red

Violet

Orange

BlueBlack

Red

Black

Red

Violet

Orange

Blue

SE

CO

ND

AIR

ES

EC

.P

RIN

CIP

AL

MA

IN

0V~

220-240V~

Commun entréesCom digital inputs

-+

Aux. sec.

Trip sec.

Withdrawn sec.

Input prog. 1

Input prog. 2

Aux. main

Trip main

Withdrawn main

CA normal

SD normal

Contact débro normal

CA secours

SD secours

Contact débro secours

Entrée prog. 1

Entrée prog. 2

BO

ÎTIE

R D

’AU

TO

MA

TIS

ME

ELE

CTR

ON

IC C

ON

TRO

L B

OX

réf:

261

93/

94

RE

LAIS

PR

OG

RA

MM

AB

LE 3

PR

OG

. 3 R

ELA

Y10

0-69

0 Va

c

50/6

0Hz

RE

LEV

E D

E T

EN

SIO

NV

OLT

AG

E IN

PU

TSA

LIM

. AU

X.

AC

AC

AU

XS

UP

PLY

EN

TR

EE

S D

IGIT

ALE

SD

IGIT

AL

INP

UTS

RE

LAIS

SE

CO

UR

SS

EC

. RE

LAY

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

RE

LAIS

NO

RM

AL

MA

IN R

ELA

Y

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

R

ELA

IS P

RO

G.

1P

RO

G. 1

RE

LAY

RE

LAIS

PR

OG

RA

MM

AB

LE 2

PR

OG

. 2 R

ELA

Y

SD

Pri

ncip

alTr

ipm

ain

78

910

16

ALI

M. A

UX

.D

CD

C A

UX

SU

PP

LY

DPX 125: contact de condition “non enclenché” non disponible

DPX 125: not-inserted contact not available

DPX 125: verrouillage mécanique non disponible

DPX 125: mechanical interlock not available

62

P1.03P1.05

FEEON

ProgrammationSetting

LG11

Page 63: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

DPX 125/160 avec EJP + feedbackDPX 125/160 with EJP and feedback

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

EJP

34

53

45

12

12

1213

1415

1718

1920

2122

2324

2526

27N

L1L2

L3N

L1L2

L311

12

34

56

Déb

ro s

eco

ndai

reW

ithd

raw

nse

c.

Déb

ro p

rinc

ipal

With

dra

wn

mai

n

3-White

1-Black

2-Red

3-White

1-Black

2-Red

SD

Sec

ond

aire

Trip

sec.

CA

Sec

ond

aire

Feed

bac

kS

ec.

CA

Pri

ncip

alFe

edb

ack

mai

n

Mo

teur

seco

ndai

reS

ec. m

otor

Mo

teur

pri

ncip

alM

ain

mot

or

Alim

enta

tio

nél

ectr

ique

des

mo

teur

sTe

nsio

nel

ectr

ic m

otor

s

54-Red

51-Black

52-White

54-Red

51-Black

52-White

11-Black

14-White

12-Red

11-Black

14-White

12-Red

Violet

Orange

BlueBlack

Red

Black

Red

Violet

Orange

Blue

SE

CO

ND

AIR

ES

EC

.P

RIN

CIP

AL

MA

IN

0V~

220-240V~

Commun entréesCom digital inputs

-+

Aux. sec.

Trip sec.

Withdrawn sec.

Input prog. 1

Input prog. 2

Aux. main

Trip main

Withdrawn main

CA normal

SD normal

Contact débro normal

CA secours

SD secours

Contact débro secours

Entrée prog. 1

Entrée prog. 2

BO

ÎTIE

R D

’AU

TO

MA

TIS

ME

ELE

CTR

ON

IC C

ON

TRO

L B

OX

réf:

261

93/

94

RE

LAIS

PR

OG

RA

MM

AB

LE 3

PR

OG

. 3 R

ELA

Y10

0-69

0 Va

c

50/6

0Hz

RE

LEV

E D

E T

EN

SIO

NV

OLT

AG

E IN

PU

TSA

LIM

. AU

X.

AC

AC

AU

XS

UP

PLY

EN

TR

EE

S D

IGIT

ALE

SD

IGIT

AL

INP

UTS

RE

LAIS

SE

CO

UR

SS

EC

. RE

LAY

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

RE

LAIS

NO

RM

AL

MA

IN R

ELA

Y

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

R

ELA

IS P

RO

G.

1P

RO

G. 1

RE

LAY

RE

LAIS

PR

OG

RA

MM

AB

LE 2

PR

OG

. 2 R

ELA

Y

SD

Pri

ncip

alTr

ipm

ain

78

910

16

ALI

M. A

UX

.D

CD

C A

UX

SU

PP

LY

DPX 125: contact de condition “non enclenché” non disponible

DPX 125: not-inserted contact not available

DPX 125: verrouillage mécanique non disponible

DPX 125: mechanical interlock not available

63

P1.03P1.05

FEEON

ProgrammationSetting

LG12

Page 64: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

DPX 250/630 sans feedbackDPX 250/630 without feedback

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

13

5

24

6

1213

1415

1718

1920

2122

2324

2526

27N

L1L2

L3N

L1L2

L311

12

34

56

Alim

enta

tio

nél

ectr

ique

des

mo

teur

sTe

nsio

nel

ectr

ic m

otor

s

Bl

Rd

Wh

SE

CO

ND

AIR

ES

EC

.P

RIN

CIP

AL

MA

IN

0V~

220-240V~

Commun entréesCom digital inputs

-+

Aux. sec.

Trip sec.

Withdrawn sec.

Input prog. 1

Input prog. 2

Aux. main

Trip main

Withdrawn main

CA normal

SD normal

Contact débro normal

CA secours

SD secours

Contact débro secours

Entrée prog. 1

Entrée prog. 2

BO

ÎTIE

R D

’AU

TO

MA

TIS

ME

ELE

CTR

ON

IC C

ON

TRO

L B

OX

réf:

261

93/

94

RE

LAIS

PR

OG

RA

MM

AB

LE 3

PR

OG

. 3 R

ELA

Y10

0-69

0 Va

c

50/6

0Hz

RE

LEV

E D

E T

EN

SIO

NV

OLT

AG

E IN

PU

TSA

LIM

. AU

X.

AC

AC

AU

XS

UP

PLY

EN

TR

EE

S D

IGIT

ALE

SD

IGIT

AL

INP

UTS

RE

LAIS

SE

CO

UR

SS

EC

. RE

LAY

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

RE

LAIS

NO

RM

AL

MA

IN R

ELA

Y

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

R

ELA

IS P

RO

G.

1P

RO

G. 1

RE

LAY

RE

LAIS

PR

OG

RA

MM

AB

LE 2

PR

OG

. 2 R

ELA

Y

78

910

16

Bl

Rd

Wh

13

5

Mo

teur

pri

ncip

alM

ain

mot

or

24

6

Mo

teur

seco

ndai

reS

ec. m

otor

Bl

Rd

Wh

Bl

Rd

Wh

ALI

M. A

UX

.D

CD

C A

UX

SU

PP

LY

64

P1.03P1.04P1.05

NOFOFFOFF

ProgrammationSetting

LG13

Page 65: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

DPX 250/630 avec EJP + feedback + declencheur EMDPX 250/630 with EJP + feedback + shunt trip

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

1213

1415

1718

1920

2122

2324

2526

27N

L1L2

L3N

L1L2

L311

12

34

56

Alim

enta

tio

nél

ectr

ique

des

mo

teur

sTe

nsio

nel

ectr

ic m

otor

s

SE

CO

ND

AIR

ES

EC

.P

RIN

CIP

AL

MA

IN

0V~

220-240V~

Commun entréesCom digital inputs

-+

Aux. sec.

Trip sec.

Withdrawn sec.

Input prog. 1

Input prog. 2

Aux. main

Trip main

Withdrawn main

CA normal

SD normal

Contact débro normal

CA secours

SD secours

Contact débro secours

Entrée prog. 1

Entrée prog. 2

BO

ÎTIE

R D

’AU

TO

MA

TIS

ME

ELE

CTR

ON

IC C

ON

TRO

L B

OX

réf:

261

93/

94

RE

LAIS

PR

OG

RA

MM

AB

LE 3

PR

OG

. 3 R

ELA

Y10

0-69

0 Va

c

50/6

0Hz

RE

LEV

E D

E T

EN

SIO

NV

OLT

AG

E IN

PU

TSA

LIM

. AU

X.

AC

AC

AU

XS

UP

PLY

EN

TR

EE

S D

IGIT

ALE

SD

IGIT

AL

INP

UTS

RE

LAIS

SE

CO

UR

SS

EC

. RE

LAY

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

RE

LAIS

NO

RM

AL

MA

IN R

ELA

Y

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

R

ELA

IS P

RO

G.

1P

RO

G. 1

RE

LAY

RE

LAIS

PR

OG

RA

MM

AB

LE 2

PR

OG

. 2 R

ELA

Y

78

910

16

Mo

teur

pri

ncip

alM

ain

mot

orBl

Rd

Wh

Bl

Rd

Wh

Déb

ro s

eco

ndai

reW

ithd

raw

nse

c.

Déb

ro p

rinc

ipal

With

dra

wn

mai

n

3-White

1-Black

2-Red

3-White

1-Black

2-Red

SD

Sec

ond

aire

Trip

sec.

54-Red

51-Black

52-White

54-Red

51-Black

52-White

SD

Pri

ncip

alTr

ipm

ain

CA

Sec

ond

aire

Aux

. Sec

.C

A P

rinc

ipal

Aux

. mai

n

11-Black

14-White

12-Red

11-Black

14-White

Mo

teur

seco

ndai

reS

ec. m

otor

Bl

Rd

Wh

Bl

Rd

Wh

12-Red

C1 C2

C1 C2

Pri

ncip

al

Mai

nS

eco

ndai

re

Sec

EJP

ALI

M. A

UX

.D

CD

C A

UX

SU

PP

LY

13

5

24

6

13

5

24

6

66

P1.03P1.05

FEEON

ProgrammationSetting

LG15

Page 66: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

DPX 250/630 avec feedback + declencheur EM + arrêt d’urgenceDPX 250/630 with feedback + shunt trip + emergency stop

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

1213

1415

1718

1920

2122

2324

2526

27N

L1L2

L3N

L1L2

L311

12

34

56

Alim

enta

tio

nél

ectr

ique

des

mo

teur

sTe

nsio

nel

ectr

ic m

otor

s

SE

CO

ND

AIR

ES

EC

.P

RIN

CIP

AL

MA

IN

0V~

220-240V~

Commun entréesCom digital inputs

-+

Aux. sec.

Trip sec.

Withdrawn sec.

Input prog. 1

Input prog. 2

Aux. main

Trip main

Withdrawn main

CA normal

SD normal

Contact débro normal

CA secours

SD secours

Contact débro secours

Entrée prog. 1

Entrée prog. 2

BO

ÎTIE

R D

’AU

TO

MA

TIS

ME

ELE

CTR

ON

IC C

ON

TRO

L B

OX

réf:

261

93/

94

RE

LAIS

PR

OG

RA

MM

AB

LE 3

PR

OG

. 3 R

ELA

Y10

0-69

0 Va

c

50/6

0Hz

RE

LEV

E D

E T

EN

SIO

NV

OLT

AG

E IN

PU

TSA

LIM

. AU

X.

AC

AC

AU

XS

UP

PLY

EN

TR

EE

S D

IGIT

ALE

SD

IGIT

AL

INP

UTS

RE

LAIS

SE

CO

UR

SS

EC

. RE

LAY

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

RE

LAIS

NO

RM

AL

MA

IN R

ELA

Y

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

R

ELA

IS P

RO

G.

1P

RO

G. 1

RE

LAY

RE

LAIS

PR

OG

RA

MM

AB

LE 2

PR

OG

. 2 R

ELA

Y

78

910

16

13

5

Mo

teur

pri

ncip

alM

ain

mot

orBl

Rd

Wh

Bl

Rd

Wh

24

6

Déb

ro s

eco

ndai

reW

ithd

raw

nse

c.

Déb

ro p

rinc

ipal

With

dra

wn

mai

n

3-White

1-Black

2-Red

3-White

1-Black

2-Red

SD

Sec

ond

aire

Trip

sec.

54-Red

51-Black

52-White

54-Red

51-Black

52-White

SD

Pri

ncip

alTr

ipm

ain

CA

Sec

ond

aire

Aux

. Sec

.C

A P

rinc

ipal

Aux

. mai

n

11-Black

14-White

12-Red

11-Black

14-White

Mo

teur

seco

ndai

reS

ec. m

otor

Bl

Rd

Wh

Bl

Rd

Wh

13

5

46

12-Red

C1 C2

C1 C2

Pri

ncip

al

Mai

nS

eco

ndai

re

Sec

Arr

êtd

’urg

ence

Em

erge

ncy

stop

2

ALI

M. A

UX

.D

CD

C A

UX

SU

PP

LY

67

P1.03P1.05

FEEON

ProgrammationSetting

LG16

Page 67: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

DPX 1600 sans feedbackDPX 1600 without feedback

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

Alim

enta

tio

nél

ectr

ique

des

mo

teur

sTe

nsio

nel

ectr

ic m

otor

s

1213

1415

1718

1920

2122

2324

2526

27N

L1L2

L3N

L1L2

L311

12

34

56

SE

CO

ND

AIR

ES

EC

.P

RIN

CIP

AL

MA

IN

0V~

220-240V~

Commun entréesCom digital inputs

-+

Aux. sec.

Trip sec.

Withdrawn sec.

Input prog. 1

Input prog. 2

Aux. main

Trip main

Withdrawn main

CA normal

SD normal

Contact débro normal

CA secours

SD secours

Contact débro secours

Entrée prog. 1

Entrée prog. 2

BO

ÎTIE

R D

’AU

TO

MA

TIS

ME

ELE

CTR

ON

IC C

ON

TRO

L B

OX

réf:

261

93/

94

RE

LAIS

PR

OG

RA

MM

AB

LE 3

PR

OG

. 3 R

ELA

Y10

0-69

0 Va

c

50/6

0Hz

RE

LEV

E D

E T

EN

SIO

NV

OLT

AG

E IN

PU

TSA

LIM

. AU

X.

AC

AC

AU

XS

UP

PLY

EN

TR

EE

S D

IGIT

ALE

SD

IGIT

AL

INP

UTS

RE

LAIS

SE

CO

UR

SS

EC

. RE

LAY

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

RE

LAIS

NO

RM

AL

MA

IN R

ELA

Y

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

R

ELA

IS P

RO

G.

1P

RO

G. 1

RE

LAY

RE

LAIS

PR

OG

RA

MM

AB

LE 2

PR

OG

. 2 R

ELA

Y

78

910

16

46

8

Mo

teur

pri

ncip

alM

ain

mot

or

35

7

Mo

teur

seco

ndai

reS

ec. m

otor

46

8

57

1 221

3

ALI

M. A

UX

.D

CD

C A

UX

SU

PP

LY

68

P1.03P1.04P1.05

NOFOFFOFF

ProgrammationSetting

LG17

Page 68: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

DPX 1600 avec feedback + declencheur EM + arrêt d’urgenceDPX 1600 with feedback + shunt trip + emergency stop

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

1213

1415

1718

1920

2122

2324

2526

27N

L1L2

L3N

L1L2

L311

12

34

56

Alim

enta

tio

nél

ectr

ique

des

mo

teur

sTe

nsio

nel

ectr

ic m

otor

s

SE

CO

ND

AIR

ES

EC

.P

RIN

CIP

AL

MA

IN

0V~

220-240V~

Commun entréesCom digital inputs

-+

Aux. sec.

Trip sec.

Withdrawn sec.

Input prog. 1

Input prog. 2

Aux. main

Trip main

Withdrawn main

CA normal

SD normal

Contact débro normal

CA secours

SD secours

Contact débro secours

Entrée prog. 1

Entrée prog. 2

BO

ÎTIE

R D

’AU

TO

MA

TIS

ME

ELE

CTR

ON

IC C

ON

TRO

L B

OX

réf:

261

93/

94

RE

LAIS

PR

OG

RA

MM

AB

LE 3

PR

OG

. 3 R

ELA

Y10

0-69

0 Va

c

50/6

0Hz

RE

LEV

E D

E T

EN

SIO

NV

OLT

AG

E IN

PU

TSA

LIM

. AU

X.

AC

AC

AU

XS

UP

PLY

EN

TR

EE

S D

IGIT

ALE

SD

IGIT

AL

INP

UTS

RE

LAIS

SE

CO

UR

SS

EC

. RE

LAY

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

RE

LAIS

NO

RM

AL

MA

IN R

ELA

Y

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

R

ELA

IS P

RO

G.

1P

RO

G. 1

RE

LAY

RE

LAIS

PR

OG

RA

MM

AB

LE 2

PR

OG

. 2 R

ELA

Y

78

910

16

42

68

Mo

teur

pri

ncip

alM

ain

mot

or

31

57

Déb

ro s

eco

urs

With

dra

wn

sec.

Déb

ro n

orm

alW

ithd

raw

nm

ain

3-White

1-Black

2-Red

3-White

1-Black

2-Red

SD

Sec

our

sTr

ipse

c.

54-Red

51-Black

52-White

54-Red

51-Black

52-White

SD

No

rmal

Trip

mai

n

CA

Sec

our

sFe

edb

ack

Sec

.

CA

No

rmal

Feed

bac

km

ain

11-Black

14-White

12-Red

11-Black

14-White

Mo

teur

seco

ndai

reS

ec. m

otor

84

26

31

57

12-Red

C1 C2

C1 C2

Pri

ncip

al

Mai

nS

eco

ndai

re

Sec

Arr

êtd

’urg

ence

Em

erge

ncy

stop

6

ALI

M. A

UX

.D

CD

C A

UX

SU

PP

LY

70

P1.03P1.05

FEEON

ProgrammationSetting

LG19

Page 69: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

DPX 1600 avec EJP + feedbackDPX 1600 with EJP + feedback

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

1213

1415

1718

1920

2122

2324

2526

27N

L1L2

L3N

L1L2

L311

12

34

56

Alim

enta

tio

nél

ectr

ique

des

mo

teur

sTe

nsio

nel

ectr

ic m

otor

s

SE

CO

ND

AIR

ES

EC

.P

RIN

CIP

AL

MA

IN

0V~

220-240V~

Commun entréesCom digital inputs

-+

Aux. sec.

Trip sec.

Withdrawn sec.

Input prog. 1

Input prog. 2

Aux. main

Trip main

Withdrawn main

CA normal

SD normal

Contact débro normal

CA secours

SD secours

Contact débro secours

Entrée prog. 1

Entrée prog. 2

BO

ÎTIE

R D

’AU

TO

MA

TIS

ME

ELE

CTR

ON

IC C

ON

TRO

L B

OX

réf:

261

93/

94

RE

LAIS

PR

OG

RA

MM

AB

LE 3

PR

OG

. 3 R

ELA

Y10

0-69

0 Va

c

50/6

0Hz

RE

LEV

E D

E T

EN

SIO

NV

OLT

AG

E IN

PU

TSA

LIM

. AU

X.

AC

AC

AU

XS

UP

PLY

EN

TR

EE

S D

IGIT

ALE

SD

IGIT

AL

INP

UTS

RE

LAIS

SE

CO

UR

SS

EC

. RE

LAY

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

RE

LAIS

NO

RM

AL

MA

IN R

ELA

Y

Ferm

etur

eC

losi

ngC

om

Com

Ouv

ertu

reO

pen

ing

R

ELA

IS P

RO

G.

1P

RO

G. 1

RE

LAY

RE

LAIS

PR

OG

RA

MM

AB

LE 2

PR

OG

. 2 R

ELA

Y

78

910

16

42

68

Mo

teur

pri

ncip

alM

ain

mot

or

31

57

Déb

ro s

eco

ndai

reW

ithd

raw

nse

c.

Déb

ro p

rinc

ipal

With

dra

wn

mai

n

3-White

1-Black

2-Red

3-White

1-Black

2-Red

SD

Sec

ond

aire

Trip

sec.

54-Red

51-Black

52-White

54-Red

51-Black

52-White

SD

Pri

ncip

alTr

ipm

ain

CA

Sec

ond

aire

Aux

. Sec

.C

A P

rinc

ipal

Aux

. mai

n

11-Black

14-White

12-Red

11-Black

14-White

Mo

teur

seco

ndai

reS

ec. m

otor

84

26

31

57

12-Red

C1 C2

C1 C2

Pri

ncip

al

Mai

nS

eco

ndai

re

Sec

EJP

ALI

M. A

UX

.D

CD

C A

UX

SU

PP

LY

71

P1.03P1.05

FEEON

ProgrammationSetting

LG20

Page 70: Electronic Control Box Manual -Y1958C

ParamètreParameter

SchémaWiring diagram

DPX 125 �� 1600 avec declencheur MT + arrêt d’urgenceDPX 125 �� 1600 with UVR and emergency stop

Programmation des paramètres pour le schéma représenté sur la figure:Parameter setting for the wiring diagram in picture:

U < U <

12 13 1411

Tension électrique desbobinesTension

electric releases

RELAISPROGRAMMABLE 3

PROG. 3 RELAY

RELAISPROGRAMMABLE 2

PROG. 2 RELAY

9 10

Principal Main

Secondaire Sec

Arrêtd’urgenceEmergency

stop

P5.02P5.03P1.03

MCMMCSFEE

ProgrammationSetting

72

LG24B

L’alimentation des commandes motorisées doit être secours

Safety supply of the motor operators is required

Page 71: Electronic Control Box Manual -Y1958C

Programmation des paramètresSetting of parameters

Setup ValeurValue Setup Valeur

ValueP0.01 P3.01P0.02 P3.02P0.03 P3.03P0.04 P3.04P0.05 P3.05P1.01 P3.06P1.02 P3.07P1.03 P3.08P1.04 P3.09P1.05 P3.10P1.06 P3.11P1.07 P3.12P1.08 P3.13P1.09 P3.14P1.10 P3.15P1.11 P4.01P2.01 P4.02P2.02 P5.01P2.03 P5.02P2.04 P5.03P2.05 P6.01P2.06 P6.02P2.07 P6.03P2.08 P6.04P2.09 P6.05P2.10 P6.06P2.11 P6.07P2.12 P6.08P2.13P2.14P2.15P2.16

Schémas de branchement utilisés:Wiring diagram used:

...............................................................................................................................................................................................................

...............................................................................................................................................................................................................

...............................................................................................................................................................................................................

...............................................................................................................................................................................................................

A compléter et à retourner au Service clients en cas de besoinTo be filled in and sent to Customer Service, if needed

73