K70P091Z “My coMfoRt MediUM” Régulation électronique à distance ou intégrée à affichage Lcd pour tWN. Pour Ventilo-convecteurs 2 tubes, 2 tubes froid + résistance électrique, 4 tubes. système “Maître / esclave” (jusqu’à 247 unités). Remote or built-in electronic controller with Lcd display for tWN. for 2-pipe fan coil units, 2-pipe cooling + electric heater element, 4-pipe. “Master / slave” system (up to 247 units). Regolazione elettronica remota o integrata con display Lcd per tWN. Per ventilconvettori a 2 tubi, a 2 tubi freddo + resistenza elettrica a 4 tubi. sistema “Maestro / schiavo” (“Master / slave”) (fino a 247 unità). Regulación electrónica a distancia o integrada con visualizador Lcd para tWN. Para ventilo-convectores de 2 tubos, 2 tubos frío + resistencia eléctrica, 4 tubos. sistema “Maestro / esclavo” (“Master / slave”) (hasta 247 unidades). ferngesteuerte oder integrierte elektronische Regelung mit Lcd-display für tWN. für gebläsekonvektoren in anlagen mit 2-Rohren, mit 2-Rohren für Kühlung + elektrisches heizelement oder mit 4 Rohren. Master-slave-system (bis zu 247 einheiten). Septembre 2012 10 11 537 - F.GB.I.E.D - 03 (Etiquette signalétique) f gb i e d Notice d’iNstaLLatioN iNstaLLatioN iNstRUctioN MaNUaLe d’iNstaLLaZioNe MaNUaL de iNstaLacióN aUfsteLLUNgs- haNdbUch

K70P091Z “My coMfoRt MediUM”

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: K70P091Z “My coMfoRt MediUM”

K70P091Z“My coMfoRt MediUM”

Régulation électronique à distance ou intégrée à affichage Lcd pour tWN.Pour Ventilo-convecteurs 2 tubes, 2 tubes froid + résistance électrique, 4 tubes.

système “Maître / esclave” (jusqu’à 247 unités).

Remote or built-in electronic controller with Lcd display for tWN. for 2-pipe fan coil units, 2-pipe cooling + electric heater element, 4-pipe.

“Master / slave” system (up to 247 units).

Regolazione elettronica remota o integrata con display Lcd per tWN.Per ventilconvettori a 2 tubi, a 2 tubi freddo + resistenza elettrica a 4 tubi.

sistema “Maestro / schiavo” (“Master / slave”) (fino a 247 unità).

Regulación electrónica a distancia o integrada con visualizador Lcd para tWN.Para ventilo-convectores de 2 tubos, 2 tubos frío + resistencia eléctrica, 4 tubos.

sistema “Maestro / esclavo” (“Master / slave”) (hasta 247 unidades).

ferngesteuerte oder integrierte elektronische Regelung mit Lcd-display für tWN. fürgebläsekonvektoren in anlagen mit 2-Rohren, mit 2-Rohren für Kühlung + elektrisches heizelement oder

mit 4 Rohren. Master-slave-system (bis zu 247 einheiten).

Septembre 2012 10 11 537 - F.GB.I.E.D - 03

(Etiquette signalétique)

f

gb

i

e

d

Notice d’iNstaLLatioN

iNstaLLatioN iNstRUctioN

MaNUaLe d’iNstaLLaZioNe

MaNUaL de iNstaLacióN

aUfsteLLUNgs-haNdbUch

Page 2: K70P091Z “My coMfoRt MediUM”

GB

2

CONTENTS

1 - OPERATION• LCD controller has been designed to govern the operation of

TWN units 9ith single-phase multispeed asynchronousmotor. In relation to the basic version, the MEDIUM versionsare equipped 9ith advanced humidity management and serialcommunication for a “Master / Slave” system.

• The MEDIUM version can be configured for “Master / Slave”operation (up to 247 secondary interior units). In this case,one of the microprocessor commands performs the “Master”function and as such controls all the other Secondaryelements.

• In this case as 9ell the connection is made via an RS485 bus,consisting of a simple shielded 2-conductor cable.

• The “Master” control (identified by address 255) transmits thefollo9ing information to the “Slave” commands:(1) Operating mode (Cooling or Heating).(2) Setpoint for room temperature.

• The speed selector of each “Slave” controller remains enabled and the room temperature can be adjusted 9ithin a range of P 2°C around the setpoint value transmitted by the “Master” controller.

1 - Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 - Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 - Main functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 - LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 - Keyboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 - Active Yey combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 - Board configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 - Parameter configuration procedure . . . . . . . . . . . . . . . . . . . . . . . 69 - Available configurations (parameter P00) . . . . . . . . . . . . . . . . . . 6

10 - Serial communication “Master / Slave” . . . . . . . . . . . . . . . . . . . . . 811 - “Summer / Winter” mode s9itching logic . . . . . . . . . . . . . . . . . . 1012 - Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1013 - “ON/OFF” valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1114 - Heating element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1215 - ECO” mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1216 - “Frost Protection” mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1217 - Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1318 - Alarm sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1419 - Self-diagnosis procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1420 - Electronic board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1521 - Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1522 - Installation of 9all-mounted controller . . . . . . . . . . . . . . . . . . . . 1723 - Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

MARKING This product marYed conforms to the essential requirements of the Directives:

- Lo9 voltage no. 2006/95/EC.- Electromagnetic Compatibility no. 2004/108/EC.

MasterSlave 1

Slave 2

Slave N

“Master / Slave” system

Page 3: K70P091Z “My coMfoRt MediUM”

GB

3

2 - PRECAUTIONS

Installation, commissioning and maintenance of this kit must be performed by qualified and authorised personnel, inaccordance with current standards and recogniRed trade practices.

Before doing any work on the installation, make sure it is switched off and all power supplies locked out.

IMPORTANT

Before each start-up operation, make sure that the it is properly configured for the application.

CAUTION

This appliance is not designed to be used by people (including children) whose physical, sensory or mental capacitiesare impaired, or who lack experience or knowledge, unless they are supervised or have received instructions on howto use the appliance by a person who is responsible for their safety. Children must be supervised to ensure that theydo not play with the appliance or its accessories.

IMPORTANT

3 - MAIN FUNCTIONS• Air temperature adjustment through automatic variation of fan speed.• Regulation of air temperature via fan ON-OFF control (fan runs at a fixed speed).• Control of ON-OFF valves for t9o or four-pipe systems.• Heating element management.• Cooling / Heating s9itching in the follo9ing modes:

- local manual s9itching,- remote manual,- automatic, depending on 9ater temperature,- automatic, depending on air temperature.

• Dehumidify Function.• Serial communication for the “Master / Slave” system.

Additional features include:• Clean contacts for external activation (e.g. 9indo9 contact, remote ON/OFF, occupancy sensor, etc.) 9hich may enable or

disable unit operation (contact logic: see configuration parameters of board).• Dry contact for remote Cooling / Heating s9itching (contact logic: see configuration parameters of board).• Dry contact for remote activation of the “ECO” function (contact logic: see configuration parameters of board).• Water temperature sensor (accessory).• Internal temperature sensor.• Air sensor (accessory). This sensor, if present, is used in place of the internal one for the measurement of room temperature.• Remote humidity sensor (accessory, to be used in combination 9ith the remote temperature sensor) 9ith ground.• The control panel is composed of:

- LCD display.- Keyboard.

Page 4: K70P091Z “My coMfoRt MediUM”

GB

4

4 - LCD DISPLAY Room temperature.

Room humidity.

Set temperature (set point).

Fan status. The flashing light indicates that the fanshave stopped pending a query from the thermostat. Ifthe symbol is steadily lit it means that the fans arerunning.

Fan status. Fan are off as speed is set to OFF or thecontrol is off.

Automatic ventilation logic.

Fan speed.

Cooling Mode. Flashes if the 9ater temperature is notsufficiently lo9 to authorise the fan to start.

Heating Mode. Flashes if the 9ater temperature is not sufficiently high to authorise the fan to start.

Dehumidification. When flashing it indicates that it is not enabled to dehumidification. The symbol displayed steadyindicates that this function is activated.

“ECO” mode activated.

Sensor alarm activated.

“FROST PROTECTION” mode activated.

Valve open

Electric heating element.The flashing symbol indicates that the heating function is provided by the electric heating element but it is not active.The fixed symbol indicates that the electric heating element is in operation (electric heating element active).

Serial communication active. The flashing symbol indicates that the command has the “Master” function in the net9orY.

32

1

1

2

3

AUTO

ON

OFF

5 - KEYBOARD ON/OFF Yey: Thermostat “ON/OFF”. During theprocedure of parameter modification, it permits to returnto normal operating conditions.

Up and Down Yeys: changing of thermostat settingtemperature (Heating: from 5°C to 30°C, Cooling: from10°C to 35°C). During the procedure of parametermodification, they are used to select the parameters orto change their value.

SEL Yey: in Heating mode, selects the electric heaterelement as the main heating mode (2-pipe cooling +heater element application).

Mode Yey: selection of the Heating / Cooling operatingmode (manual).

Fan Yey: selection of operating speed.

EC Yey: selection of the “ECO” mode.

Page 5: K70P091Z “My coMfoRt MediUM”

GB

5

7 - BOARD CONFIGURATION• The board can be configured according to the type of unit / system to be governed by changing some parameters.

7.1 - PARAMETER LIST (accessible at level 2)• P00 = controller configuration (see “Available configurations”) to select the type of unit to be governed.

Note: to configure in first before modifying the other parameters.

• P01 = type of controller installation (built-in or remote-controlled air sensor):- 000 : on the unit - provide for an “SA” air sensor (as an accessory),- 001 : 9all mounted - do not connect the air sensor.

• P02 = Modbus address, in order for the change in this parameter to become active, it is necessary to s9itch the po9eroff and bacY on again at the end of programming.

- 000 : serial communication disabled.- 1-247 : Secondary (Slave).- 255 : Master.

• P03 = neutral zone (20 to 50°C / 10); parameter used in case of configurations 9ith automatic Cooling / Heatingchangeover according to air temperature.

• P04 = 9ater sensor:- 000 : not available,- 001 : available provided (mandatory for 2-pipe Cooling + heating element) and dehumidification.Based on the set value, the sensor alarm and the heating element functions 9ill be controlled.

• P05 = Configuration logic for use of digital inputs 1 and 2:- 000 : DIN 1 = - DIN2 = -- 001 : DIN 1 = - DIN2 = On/Off- 002 : DIN 1 = Sum. / Win. DIN2 = -- 003 : DIN 1 = ECO DIN2 = -- 004 : DIN 1 = Sum. / Win. DIN2 = On/Off- 005 : DIN 1 = ECO DIN2 = On/Off- 006 : DIN 1 = Sum. / Win. DIN2 = ECO

• P06 = logic for use of digital input 1:- 000 : (open / closed) = (Cooling / Heating) = (- / ECO),- 001 : (open / closed) = (Heating / Cooling) = (ECO / -).

• P07 = logic for use of digital input 2:- 000 : (open / closed) = (Off/On) = (- / ECO),- 001 : (open / closed) = (On/Off) = (ECO / -).

• P08 = remote humidity sensor:- 000 : not available,- 001 : available (mandatory for the dehumidification function).

• Based on the set value, the associated sensor alarm 9ill be triggered accordingly.

6 - ACTIVE KEY COMBINATIONSThermostat set to “Off”: Allo9s access to the parameter configuration.Thermostat set to “On”: Momentary display of the 9ater temperature read by the sensor.

Thermostat set to “Off”: Selection of the “FROST PROTECTION” mode.

Selection of Dehumidify option.

Simultaneous pressing of the + , Yeys and entering the pass9ord 99 after validating by short pressing of, allo9s for the Yeyboard Yeys to be locYed. Proceed in the same 9ay for the release.

This combination is provided to s9itch from degrees Celsius to degrees Fahrenheit and vice versa.

Page 6: K70P091Z “My coMfoRt MediUM”

GB

6

• Set the thermostat to OFF .

• Push the Yeys at the same time.

• Use the Yeys to modify the value on the display tothe pass9ord value (PW) = 10, then validate by pressing

.

• If correct, you 9ill be able to access the level 2 parameters.

• Use Yeys to scroll the various parameters (P00 to

P08: see list above).

• Press to confirm the parameter change (the value 9illstart flashing).

• Use the Yeys to modify the initial value.

• Press to save the ne9 value setting or to cancel the modification.

• After completing the modification of the parameters concerned press Yey to exit the procedure.Note:The duration of the parameterisation is limited over time.Once a certain time has elapsed (around 2 minutes) the thermostat 9ill s9itch bacY into the OFF status and only the savedchanges 9ill be retained.

9 - AVAILABLE CONFIGURATIONS (PARAMETER P00)• The LCD controller can be configured in various 9ays according to the type of system. Various configurations can be obtained

through the “P00” parameter (refer to the parameter configuration procedure):

001- System pipes: 2-PIPE (Cooling or Heating)- Valve: NO- Heating element: NO- Summer / 9inter s9itching logic: LOCAL MANUAL

002- System pipes: 2-PIPE (Cooling or Heating)- Valve: NO- Heating element: NO- Summer / 9inter s9itching logic: REMOTE MANUAL

003- System pipes: 2-PIPE (Cooling or Heating)- Valve: NO- Heating element: NO- Summer / 9inter s9itching logic: AUTOMATIC WATER SIDE

004 (Do not use)

005 (Do not use)

006 (Do not use)

007 (Do not use)

008 (Do not use)

009 (Do not use)

010 (Do not use)

011 (Do not use)

012 (Do not use)

8 - PARAMETER CONFIGURATION PROCEDURE

User level indicator001 = Pass9ord entry (PW)

Level indicator:003 = Parameter valuemodification

Level indicator:002 = Access toparameters

Value ofselected

parameter

Selectedparameter: P00 to P08

Page 7: K70P091Z “My coMfoRt MediUM”

GB

7

013- System pipes: 2-PIPE (Cooling or Heating)- Valve: 3 WAYS- Heating element: NO- Summer / 9inter s9itching logic: LOCAL MANUAL

014- System pipes: 2-PIPE (Cooling or Heating)- Valve: 3 WAYS- Heating element: NO- Summer / 9inter s9itching logic: REMOTE MANUAL

015- System pipes: 2-PIPE (Cooling or Heating)- Valve: 3 WAYS- Heating element: NO- Summer / 9inter s9itching logic: AUTOMATIC WATER SIDE

016 (Do not use)

017 (Do not use)

018 (Do not use)

019- System pipes: 2-PIPE (Cooling + Heating element)- Valve: 3 WAYS- Heating element: YES- Summer / 9inter s9itching logic: LOCAL MANUAL

020- System pipes: 2-PIPE (Cooling + Heating element)- Valve: 3 WAYS- Heating element: YES- Summer / 9inter s9itching logic: REMOTE MANUAL

021- System pipes: 2-PIPE (Cooling + Heating element)- Valve: 3 WAYS- Heating element: YES- Summer / 9inter s9itching logic: AUTOMATIC AIR SIDE

022 (Do not use)

023 (Do not use)

024 (Do not use)

025 (Do not use)

026 (Do not use)

027 (Do not use)

028 (Do not use)

029 (Do not use)

030 (Do not use)

031- System pipes: 4-PIPE- Valve: 3 WAYS- Heating element: NO- Summer / 9inter s9itching logic: LOCAL MANUAL

032- System pipes: 4-PIPE- Valve: 3 WAYS- Heating element: NO- Summer / 9inter s9itching logic: REMOTE MANUAL

033- System pipes: 4-PIPE- Valve: 3 WAYS- Heating element: NO- Summer / 9inter s9itching logic: AUTOMATIC AIR SIDE

034 (Do not use)

035 (Do not use)

036 (Do not use)

037 (Do not use)

038 (Do not use)

Page 8: K70P091Z “My coMfoRt MediUM”

GB

8

10 - SERIAL COMMUNICATION “MASTER / SLAVE”• Connection to the RS 485 communication net9orY• The communication net9orY (Bus type) relies on a simple shielded 2-conductor cable, directly connected to the RS 485 serial

ports of the controllers (terminals A, B and GND).• For the net9orY use a cable AWG 24 (diam. 0.511 mm).• The communication net9orY must have the follo9ing general structure:

(1): shielded BUS.(5): Terminal units.9here LT represents the termination resistors at either end of the net9orY (120 Ohms - not included).

• Note 1: Comply 9ith the polarity of the connection: indicated 9ith A (-) and B (+).Note 2: Avoid ground loops (ground shield at one end only).

• An end resistance must be installed on both commands at the ends of the net9orY (120 Ohms value not included).

5 1 5

LT

D

A B

GNDR D

A B

AB

GND

GND

R

D R

(-)

(+)

(-)

(+)

5

LT LT

GNDBAGNDBA

(-)

(+)

(-)

(+)

GND

5

1

Not supplied

Slave 1 Slave NX

Master

Not supplied

g---------------- Slave ----------------h

Page 9: K70P091Z “My coMfoRt MediUM”

GB

9

• Suggested layout of network:- T1: Terminal 1- T2: Terminal 2- T3: Terminal 3- TN: Terminal N- B: Secondary branches (L j 20 m)- C: Main branch of net9orY (L j 1000 m)

• WARNING:- Maximum length of the main branch: 1000 m.- Maximum length of each secondary branch: 20 m.- Use a shielded cable AWG24 (diameter 0.511 mm).- Colours suggested for the communication net9orY:

A (-) Bro9n; B (+) kello9

• If several levels need to be 9ired, aSINGLE MAIN BRANCH line must beset up to guarantee a bus-type net9orY:

- T1: Terminal 1- T2: Terminal 2- T3: Terminal 3- T4: Terminal 4- TN: Terminal N- TN + 1: Terminal N + 1- A: 1st level main branch- B: 2nd level- C: 2nd level main branch- D: Secondary branches (L j 20 m)

T1

T3T2

B

C

TN

TN + 1

DC

TN

D

A

BTN

T3

T1

T2

T4

Page 10: K70P091Z “My coMfoRt MediUM”

GB

10

11 - “SUMMER / WINTER” MODE SWITCHING LOGIC11.1 - COOLING / HEATING SWITCHING

• Four logics are present to select the thermostat operating modes, 9hich are defined 9hen parameter “P00” is configured:- Local manual: user choice made through the Yey .- Remote manual: depending on the Digital Input 1 (DI1) status (contact logic: see configuration parameters of board).

- Automatic depending on water temperature (2-pipe).Note: in case of 9ater sensor alarm, the controller returns tothe Local mode temporarily (manual).

- Automatic depending on air temperature (4-pipe):9here

- Set is the set point programmed for the climate,- ZN is the neutral zone (parameter P03).

Note: the value displayed for parameter P03 is to bedivided by 10.

• The thermostat operating mode is indicated on the display bythe symbols (Cooling) and (Heating).

17°C 28°C

Watertemperature

Summer

Winter

Set - ZN/2 Set + ZN/2Set

Ambient airtemperature

Summer

Winter

12 - VENTILATION12.1 - OPERATING SPEED SELECTION

• Using Yey it is possible to select the follo9ing speeds:- AUTO Automatic fan speed: depending on the set temperature and the room air temperature.- 1 = lo9 speed.- 2 = medium speed.- 3 = maximum speed.

• Note:In the case of fixed speed, the fan on/off logic 9ill be equivalent to the automatic logic.

12.2 - ACTIVATION ACCORDING TO THE WATER TEMPERATURE (if sensor connected)• Fan operation may be connected to the installationls 9ater temperature control. Based on the operation mode, different

heating or cooling thresholds 9ill be enabled.

• The absence of this condition 9hen queried by the thermostat 9ill cause the symbol of the mode currently active ( or) to flash.

The enabling signal is ignored:- Water sensor not provided (P04 = 0) or in alarm status.- In the cooling mode 9ith 4-pipe configurations.

Ve

1

2

3

Set Set + 0.5°C Set + 2°C Set + 3°C

Ve

1

2

3

SetSet - 0.5°CSet - 2°CSet - 3°C

17°C

ON

OFF22°C

ON

OFF25°C 28°C

Air temperatureAir temperature

Air temperature Air temperature

COOLING HEATING

COOLING HEATING

Page 11: K70P091Z “My coMfoRt MediUM”

GB

11

12.3 - VENTILATION FORCING• The fan operating logic 9ill be ignored in particular override situations that may be necessary to ensure correct control of

the temperature or the unit!s operation. This may occur:

In the Cooling Mode:- On-board controller (P01 = 0) and configurations 9ith valve: the minimum speed 9ill be maintained even once the

temperature has been reached.- On-board controller and valveless configurations: every 10 minutes 9hen the fan is stopped, the ventilation operates for

2 minutes at medium speed to allo9 the air sensor to taYe a more precise reading of the ambient temperature.

In the Heating Mode:- While the heating element is on: the fan is forced to run at medium speed.- Once the heating element has gone off: a 2 minute post-ventilation cycle 9ill be run at medium speed. (Note: ventilation

is time delayed even if the thermostat is set to mOffm or if s9itched to cooling mode).

12.4 - DISPLAY• The display sho9s the fan status:

- ON flashing: fan in standby mode.- ON steady: fan on.- OFF: fan deactivated.

and fan speed (9ith indication of “automatic” logic if proper) enabled or selected:- 1 = Lo9 speed.- 2 = Medium speed.- 3 = High speed.

• Note:if the active speed is different from the one selected by the user (in the case of a forcedoverride), pressing the button once 9ill cause the latter to be displayed; pressing again 9illchange this setting.

13 - “ON/OFF” VALVE• The controller is able to manage the “ON/OFF” type 3-9ay valves, 9ith the valve being supplied at 230V/1/50.

13.1 - VALVE ACTIVATION ACCORDING TO AIR TEMPERATURE• The opening of the valve is controlled according to the setpoint and the ambient air temperature.

13.2 - VALVE ACTIVATION ACCORDING TO WATER TEMPERATURE• Monitoring of the 9ater temperature to activate opening is possible only in configurations 9ith Cold valve and an electric

heater element. In such configurations the 9ater temperature 9ill be checYed in the follo9ing cases: - Heating 9ith heat element: operation of the heating

element 9ill force the fan to s9itch on; it is thereforenecessary to prevent excessively cold 9ater frompassing through the unit.

- Post-ventilation due to s9itching off of the heatingelement: this function 9ill be maintained until the set timehas elapsed, even if the operating mode is changed.

13.3 - DISPLAY• The active valve indication on the display 9ill be sho9n by the symbol .

ON

OFFSet Set + 0.5°C

ON

OFFSetSet - 0.5°C

Ambient airtemperature

Ambient airtemperature

25°C 28°C Water temperature

COOLING HEATING

Yes

No

Page 12: K70P091Z “My coMfoRt MediUM”

GB

12

14 - HEATING ELEMENT• The electric heater element ensures the main heating function in the 2-pipe Cooling + heating element configuration.

Note: The presence of the 9ater sensor is compulsory for this operation.

14.1 - SELECTION• If provided for in the configuration, the heating element can be selected in the heating mode by pressing the Yey.

14.2 - ACTIVATION ACCORDING TO THE AMBIENT TEMPERATURE• If use of the heating element is selected by the user, it 9ill be

activated on a call from the thermostat based on the roomtemperature.

• Note: The activation involves forced ventilation at medium speed.

14.3 - DISPLAY• The display 9ill sho9 the follo9ing information:

Heating provided by the heating element:- Heating element in operation: steadily lit symbol .- Heating element not active at this point: flashing symbol .

ON

OFFSetSet - 0.5°C

Ambient airtemperature

15 - “ECO” MODE• The “ECO” mode foresees a correction of the setpoint by 2.5 °C and forcing of the fan at minimum speed to reduce the unitls

operation.• Cooling: setpoint + 2.5°C.• Heating: setpoint – 2.5°C.

15.1 - ACTIVATION• The “ECO” mode is activated by the Yey.• Proceed in the same manner to deactivate the “ECO” mode.

15.2 - DISPLAY• On the monitor, the “ECO” mode is activated: symbol .

16 - “FROST PROTECTION” MODE• With the thermostat being “OFF”, this logic prevents the ambient temperature from dropping too lo9; the unit is thus forced into

heating mode.If the electric heating is present, it 9ill be used only if it had been previously selected.

16.1 - SELECTION• To select the “Frost Protection” mode, 9ith the thermostat set to “OFF”, simultaneously press the Yeys .• The same Yey combination disables this function.

16.2 - ACTIVATION• If this control is selected, the unit 9ill s9itch on 9hen the room

temperature falls belo9 9°C.• When temperature exceeds 10°C the thermostat 9ill resume the

OFF status.• Note:

Any OFF command from digital input 9ill disable this logic.

16.3 - DISPLAY• The display sho9s the follo9ing information:

- “Frost Protection” mode control active: symbol .- “Frost Protection” mode control inactive: Defr indication.

ON

OFF10°C9°C

Ambient airtemperature

“Frost Protection” mode active

“Frost Protection”mode inactive

Page 13: K70P091Z “My coMfoRt MediUM”

GB

13

17 - DEHUMIDIFICATION• The dehumidification function, enabled only in the cooling mode, activates operation of the indoor unit in order to achieve a 10n

reduction in the level of humidity present in the room at the time the function itself 9as selected.

17.1 - SELECTION• Dehumidification can be selected / unselected in the Cooling mode by simultaneously pressing the buttons.• In the absence of a 9ater sensor (P04 = 0), or if the humidity sensor is not connected on the unit (P08 = 0), selection 9ill

not be enabled. If selected, the dead band for automatic s9itching on the air side 9ill be brought to 5°C.

17.2 - LOGIC• Once selected, the Dehumidification logic sets the target

humidity level as the humidity present at the time thefunction 9as selected minus 10n. Where the roomhumidity is less than 40n the target level 9ill be set at30n.The fan 9ill be forced to run at lo9 speed or, if thetemperature is much higher than the setpoint, at mediumspeed.

• To bring the humidity to the programmed value, theventilation (and the valve, if present) 9ill be activated inthe event the ambient temperature reaches the setpointvalue. Should the room temperature fall too far belo9 thisthreshold, the logic 9ill be temporarily inhibited.

17.3 - WATER CONTROL• Enabling of the dehumidification function is tied to the

9ater temperature. The activation logic is sho9nopposite.

• If enabling conditions do not exist, the Dehumidificationfunction 9ill be temporarily inhibited.The same 9ill occur in the event that the probe is disconnected.

• Note:As soon as the reference humidity level is reached (or after having set the control to Off), dehumidification 9ill bedeactivated.

17.4 - DISPLAY• The display sho9s the follo9ing information:

- Dehumidify ON: symbol lit .

- Dehumidification temporarily inhibited: flashing symbol .

Set + 0.5°C Set + 1.5°C Ambient airtemperature

Med. speed

Min. speed

Set - 2.0°C Set - 1.5°C Ambient airtemperature

Dehumidificationdeactivated

10.0°C Water temperatures

Yes

No

Page 14: K70P091Z “My coMfoRt MediUM”

GB

14

This procedure allo9s you to checY 9hether the individual outputs of the controller function correctly.To run the procedure, follo9 the directions belo9:

• S9itch the thermostat “OFF”:

• Push the Yeys at the same time.

• Use the Yeys to change the value on the display until arriving at the pass9ord for self-diagnosis 030, and press. The follo9ing message appears:

• Press the Yey to s9itch on the various thermostat outputs in sequence.

18 - ALARM SENSORSThe controller monitors t9o types of faults:

• Faults causing the thermostat to shut do9n.• Faults not causing the thermostat to shut do9n but 9hich prevent possible critical functions.• Code 01 = error on the remote ambient air temperature sensor (thermostat installed

on the unit) => Thermostat shut do9n.

• Code 02 = error on the internal air temperature sensor => Thermostat shut do9n.

• Code 03 = error on the 9ater temperature sensor (if connected) => Does not causethe thermostat to shut do9n.

• Code 04 = external humidity probe error (only if a remote temperature sensor isinstalled) => Does not cause the thermostat to shut do9n.

• Note: The alarm code is displayed only 9hen the thermostat is s9itched off.

Thermostat “OFF” Thermostat “ON”

19 - SELF-DIAGNOSIS PROCEDURE

User level indication001 = Pass9ord entry (PW)

• The electronic controller outputs can be checYed one by one either by observing the respective component (valve, fan..) orverifying 9hether a voltage of 230V is present at the corresponding terminals.

• To exit the self-diagnosis procedure press (after a fe9 minutes the thermostat 9ill automatically exit in any case).

Alarmcode

Symbol Action Terminals

Lo9 speed N - V1

Medium speed N - V2

High speed N - V3

Valve N - VcSecond valve

(or heating element) N - Vh

No symbol No active outlet

Page 15: K70P091Z “My coMfoRt MediUM”

GB

15

20 - ELECTRONIC BOARD

A-B-GND RS 485 (“Master / Slave” linY)CI12 Common DI1-2DI1 Digital input 1DI2 Digital input 2L PhaseN NeutralPE GroundSA Remote air sensorSU Humidity sensor (remote)SW Water sensorV0 -V1 Lo9 speedV2 Medium speedV3 High speedVc Cooling / Heating valve (2-pipe)Vh Heater valve / Heating element

Note:• For po9er connections use cable 9/ cross section size

of 1 mm2.• For digital inputs used AWG 24 cable.• For sensor extensions use AWG 24 shielded cable.

Vc

DI1CI12DI2

VhV0V1V2V3NNLPE

SWSUSUAGNDB

SWSASA

Configuration table / Diagrams.

Configurations Units Diagram

01-02-032-pipe Cooling or Heating 9ithout valve9ithout heating element

TWN FC66002554

13-14-152-pipe Cooling or Heating9ith valve9ithout heating element

TWN FC66002554

19-20-212-pipe Cooling9ith valve9ith heating element

TWN FC66002554

31-32-334-pipe9ith valves9ithout heating element

TWN FC66002554

21 - WIRING DIAGRAM FC66002554

Page 16: K70P091Z “My coMfoRt MediUM”

GB

16

Vc VTOG

RDBUBKWHWHBU

EXT

RHC

ECONOMY

ECONOMY

BNGNYE

BU

RDCN7

9108

654NL

N230V 1

1M

50HzL

F

PE

IL

BUBK

PVMVGV

WH

BNBN

+ +

VhV0V1V2V3

N

DI1

SW SW SR

SW SA

SR SU

SU

SU A GNDRS 485

B

CI12DI2

NLPE

-Heating valve

or heating element

(4-pipe)

Cooling or heating valve(2-pipe)or Cooling valve(4-pipe)

Diagram symbol key

..... Electrical connections to be made by installerA/B/GND RS 485 “Master / Slave” BU Blue (Medium speed)BK BlacY (High speed)CI12 Digital input commonCN Terminal board TWNDI1 Dig.1 input.DI2 Dig.2 input.ECONOMY COMFORT / ECONOMY remote selectorEXT Remote ON / OFF contactF Fuse (not supplied)GNYE Green / kello9 (Ground)IL Circuit breaYer (not supplied)L PhaseM Fan motor TWNN NeutralPE GroundRHC Heating / Cooling remote selecting s9itchRE Heating elementRD Red (Lo9 speed)SA Remote air sensor (accessory)SU Remote humidity sensor (accessory)SW Water sensor (accessory)V1 Lo9 speedV2 Medium speedV3 High speedVH Solenoid valve - HeatingVHC Solenoid valve - Cooling / HeatingWH White (common)

FC66002554

Page 17: K70P091Z “My coMfoRt MediUM”

GB

17

23 - TECHNICAL DATA

Power supply230 V / 1 / 50Electrical input 8 WProtection fuse 500 mA delayed

Operating temperature Range 0 to 50°CStorage temperature Range -10 to 60°C

Relay

NO (normal open) 5 A @ 240 V (Resistive)Insulation: coil-contact distance 8 mm4000 V coil-relay dielectricMax ambient temperature: 105°C

Connectors 230 V 10 A

Digital inputsClean contactClosing current 2 mAMax. closing resistance 50 Ohm

0 inputs Temperature and relative humidity sensorsPower outputs Relay (see above)

Temperature sensorsNTC sensors 10 K Ohm @25°CRange -25 to 100°C

Humidity sensorResistance type sensorsRange 25 to 90 n RH

22 - INSTALLATION OF WALL-MOUNTED CONTROLLER• For wall-mounted installation, an electrical box can be installed behind

the controller to house the wiring.• Note:

Prior to installation, carefully remove the protective film from the display;removal of the film may cause some darY streaYs to appear on the displaybut these 9ill disappear after a fe9 seconds and are not signs of a controllerdefect.

• Instructions for installation:- Remove the fastening scre9 of the controller.

- MaYe the holes in the 9all 9here the controller is to be installed,matching the mounting holes (5 x 8 mm) in the controllerls base plate;pass the cables through the slot on the base and scre9 it to the 9all(previously drilled).

- MaYe the electrical connections to the indoor unit terminal blocY as perthe 9iring diagram.

- Close the device 9ith the controllerls closing scre9.

86

89.3

130

57

2.816.2

817.7

9324

75

Ohmic values of the sensor

NTC 10 k! @ 25°C

Temperature in °C Value in k! Temperature

in °C Value in k!

3 28.30 40 5.335 25.61 45 4.367 23.18 50 3.6010 20.05 55 2.9815 15.90 60 2.4820 12.60 65 2.0825 10.03 70 1.7530 8.06 75 1.4835 6.55 80 1.26

Page 18: K70P091Z “My coMfoRt MediUM”

F

GB

D

I

E

Page 19: K70P091Z “My coMfoRt MediUM”

F

GB

D

I

E

REMARQUE : Ce symbole et ce système de recyclage s'appliquent uniquement aux pays del’UE. Ils ne s'appliquent pas aux pays des autres régions du monde.

NOTE: This symbol mark and recycle system are applied only to EU countries and not appliedto the countries in the other area of the world.

NOTA : Questo simbolo e il sistema di riciclaggio sono validi soltanto per i paesi dell’UnioneEuropea e non sono validi per i paesi nel resto del mondo.

NOTA : Este símbolo y el sistema de reciclaje solamente son para países de la UE y no son aplicables a países de otras áreas del mundo.

HINWEIS : Dieses Symbol und Recycle-System gelten nur für Länder der Europäischen Union,nicht für andere Länder der Welt.

F

GB

I

E

D

Votre produit est conçu et fabriqué avec des matériels et des composants de qualité supérieure qui peuvent être recyclés etréutilisés.En fin de vie, il doit être éliminé séparément des ordures ménagères.Nous vous prions donc de confier cet équipement à votre centre local de collecte/recyclage.Dans l’Union Européenne, il existe des systèmes sélectifs de collecte pour les produits électriques et électroniques usagés.Aidez-nous à conserver l’environnement dans lequel nous vivons !Les appareils contiennent fréquemment des matières qui, si elles sont traitées ou éliminées de manière inapropriées, peuvents’avérer potentiellement dangereuses pour la santé humaine et pour l’environnement.Cependant, ces matières sont nécessaires au bon fonctionnement de votre appareil ou de votre machine. Pour cette raison, ilvous est demandé de ne pas vous débarrasser de votre appareil ou machine usagé avec vos ordures ménagères.

Your product is designed and manufactured with high quality materials and components which can be recycled and reused.At end of livetime, it should be eliminated separately from your household waste.Please dispose of this equipment at your local community waste collection/recycling centre.In the European Union there are separate collection systems for used electrical and electronic products.Please help us to conserve the environment we live in!Some equipments contain substances that are considered dangerous to the environment and human health if they are disposedof carelessly.These substances, however, are required for your apparatus or machine to work properly. For this reason, it is requested thatit not be disposed of with other household waste at the end of its service life.

Il vostro prodotto è stato costruito da materiali e componenti di alta qualità, che sono riutilizzabili o riciclabili.Alla fine della sua vita utile deve essere smaltito separatamente dai rifiuti domestici.Vi preghiamo di smaltire questo apparecchio in un centro di raccolta differenziata locale.Nell'Unione Europea esistono sistemi di raccolta differenziata per prodotti elettrici ed elettronici.Aiutateci a conservare l'ambiente in cui viviamo!Gli apparecchi contengono spesso dei materiali che, se trattati od eliminati in modo non adeguato, possono dimostrarsipotenzialmente pericolosi per la salute umana e per l'ambiente.Tuttavia, questi materiali sono necessari per il corretto funzionamento del vostro apparecchio o della vostra macchina. Perquesto motivo, si richiede di non eliminare il proprio apparecchio o macchina usata assieme ai rifiuti domestici comuni.

Los productos están diseñados y fabricados con materiales y componentes de alta calidad, que pueden ser reciclados yreutilizados.Al final de su ciclo de vida, no se debe desechar con el resto de residuos domésticos. Por favor, deposite su viejo aparato enel punto de recogida de residuos o contacte con su administración local.En la Unión Europea existen sistemas de recogida específicos para residuos de aparatos eléctricos y electrónicos.Por favor, ayúdenos a conservar el medio ambiente!Los aparatos a menudo contienen materiales que, si son tratados o eliminados de forma inadecuada, pueden convertirse enpotencialmente peligrosos para la salud humana y para el medio ambiente.No obstante, estos materiales son necesarios para el buen funcionamiento de su máquina. Por esta razón, le rogamosencarecidamente que al final de la vida útil de su aparato, no lo tire junto con la basura doméstica, sino que lo recicleadecuadamente.

Ihr Produkt wurde entworfen und hergestellt mit qualitativ hochwertigen Materialien und Komponenten, die recycelt und wiederverwendet werden können.Am Ende ihrer Nutzungsdauer muss er getrennt vom Hausmüll eliminier werden sollen.Bitte entsorgen Sie dieses Gerät bei Ihrer örtlichen kommunalen Sammelstelle oder im Recycling Centre.In der Europäischen Union gibt es unterschiedliche Sammelsysteme für Elektrik- und Elektronikgeräte.Helfen Sie uns bitte, die Umwelt zu erhalten, in der wir leben!Die Geräte enthalten häufig Bestandteile aus bestimmten Werkstoffen, die bei einer nicht ordnungsgemäßen Behandlung oderEntsorgung eine Belastung für die menschliche Gesundheit und Umwelt darstellen.Diese Werkstoffe sind jedoch für die korrekte Funktionsweise Ihres Gerätes oder Maschine notwendig. Daher bitten wir Sie,Ihr(e) ausgediente(s) Gerät/Maschine nicht in den Hausmüll zu geben.

F

GB

I

E

D

Page 20: K70P091Z “My coMfoRt MediUM”

F

GB

D

I

E

Par souci d'amélioration constante, nos produits peuvent être modifiés sans préavis.Due to our policy of continuous development, our products are liable to modification without notice.

Per garantire un costante miglioramento dei nostri prodotti, ci riserviamo di modificarli senza preaviso.En el interés de mejoras constantes, nuestros productos pueden modificarse sin aviso prévio.

Unsere Produkte werden laufend verbessert und können ohne Vorankündigung abgeändert werden.

Z.I. Route départementale 28CS 40131 Reyrieux01601 TRéVoUx Cedex FRANCETél. 04 74 00 92 92 - Fax 04 74 00 42 00Tel. 33 4 74 00 92 92 - Fax 33 4 74 00 42 00R.C.S. Bourg-en-Bresse B 759 200 728