6
Thin-walled steel sheets with indentations in composite steel-concrete structure under different types of loading JOSEF HOLOMEK, RADEK KARÁSEK, MIROSLAV BAJER, JAN BARNAT Department of Metal and Timber Structures Brno University of Technology Veveří 95, Brno 602 00 THE CZECH REPUBLIC [email protected], [email protected], [email protected], [email protected] http://www.kdk.fce.vutbr.cz Abstract: This article is focused on a special type of thin-walled steel sheets with shear connection. These are especially suitable for roof and floor-bearing structures, allowing the building process to be easy and fast. The shear connection between the sheet and the concrete, which is realised by moulded dimples, ensures the composite action of the steel and concrete material without any need of additional reinforcement. In this article you can find a short review of thin-walled sheets, which are manufactured in Western Europe, and results from our experimental testing of specimens. These specimens were tested by vacuum loading and by cyclic loading in four-point bending tests. Key-Words: thin-walled, steel, connection members, vacuum, loading, shear connection 1 Introduction Steel structures have a greater load capacity than those made of concrete, but have lower spatial stiffness. By contrast, concrete structures are sufficiently rigid, but with very low tension bearing capacity. Combining these two materials can maximize their advantages and suppress their disadvantages. In a combined cross section the concrete takes the pressure and the steel takes the tensile stress. For these structures, a shear connection between steel and concrete is a prerequisite [1]. 2 Type of shear connection The profiled steel sheet must be capable of transmitting horizontal shear at the interface between the sheet and the concrete; pure bond between the steel sheeting and the concrete is not considered effective for composite action. Composite behavior between profiled sheeting and concrete should be ensured by one or more of the following means; see Fig. 1: a) mechanical connection using hitch elements pre-pressed into dimples in the sheets; b) frictional connection via profiled self-locking sheeting; c) connection by terminal headed studs in combination with (a) or (b); d) end anchorage by deformation of the ribs at the end of the sheeting; only in combination with (b). Fig. 1: Typical forms of interlock in composite slabs. The text below describes the thin-walled corrugated sheets which are used in shear connections where possible to realize composite behaviour via mechanical connections using hitch elements pre-pressed (moulded) into dimples in the sheets; see Fig 1a. This type of combined structure stands out above all for its simplicity and the speed at which it can be constructed. The coupling between the sheeting and the concrete provides sufficient load capacity without further reinforcement of the concrete. The system also adds just structural reinforcement. The bearing capacity of this type of connection is determined by the stress concentration near the dimples, which can be assessed using experimental research [2]. Computational Engineering in Systems Applications (Volume II) ISBN: 978-1-61804-014-5 177

Thin-walled steel sheets with indentations in composite ...wseas.us/e-library/conferences/2011/Iasi/IAASAT/IAASAT-29.pdfCOFRAPLUS 60 steel sheets with a thickness of 1.0 mm (Fig. 3)

  • Upload
    others

  • View
    1

  • Download
    1

Embed Size (px)

Citation preview

  • Thin-walled steel sheets with indentations in composite steel-concrete

    structure under different types of loading

    JOSEF HOLOMEK, RADEK KARÁSEK, MIROSLAV BAJER, JAN BARNAT Department of Metal and Timber Structures

    Brno University of Technology Veveří 95, Brno 602 00

    THE CZECH REPUBLIC [email protected], [email protected], [email protected], [email protected]

    http://www.kdk.fce.vutbr.cz Abstract: This article is focused on a special type of thin-walled steel sheets with shear connection. These are especially suitable for roof and floor-bearing structures, allowing the building process to be easy and fast. The shear connection between the sheet and the concrete, which is realised by moulded dimples, ensures the composite action of the steel and concrete material without any need of additional reinforcement. In this article you can find a short review of thin-walled sheets, which are manufactured in Western Europe, and results from our experimental testing of specimens. These specimens were tested by vacuum loading and by cyclic loading in four-point bending tests.

    Key-Words: thin-walled, steel, connection members, vacuum, loading, shear connection

    1 Introduction Steel structures have a greater load capacity

    than those made of concrete, but have lower spatial stiffness. By contrast, concrete structures are sufficiently rigid, but with very low tension bearing capacity. Combining these two materials can maximize their advantages and suppress their disadvantages. In a combined cross section the concrete takes the pressure and the steel takes the tensile stress. For these structures, a shear connection between steel and concrete is a prerequisite [1].

    2 Type of shear connection The profiled steel sheet must be capable of

    transmitting horizontal shear at the interface between the sheet and the concrete; pure bond between the steel sheeting and the concrete is not considered effective for composite action. Composite behavior between profiled sheeting and concrete should be ensured by one or more of the following means; see Fig. 1: a) mechanical connection using hitch elements pre-pressed into dimples in the sheets; b) frictional connection via profiled self-locking sheeting; c) connection by terminal headed studs in combination with (a) or (b);

    d) end anchorage by deformation of the ribs at the end of the sheeting; only in combination with (b).

    Fig. 1: Typical forms of interlock in composite

    slabs.

    The text below describes the thin-walled corrugated sheets which are used in shear connections where possible to realize composite behaviour via mechanical connections using hitch elements pre-pressed (moulded) into dimples in the sheets; see Fig 1a.

    This type of combined structure stands out above all for its simplicity and the speed at which it can be constructed. The coupling between the sheeting and the concrete provides sufficient load capacity without further reinforcement of the concrete. The system also adds just structural reinforcement. The bearing capacity of this type of connection is determined by the stress concentration near the dimples, which can be assessed using experimental research [2].

    Computational Engineering in Systems Applications (Volume II)

    ISBN: 978-1-61804-014-5 177

  • 3 Characteristics of selected thin

    sheets 3.1 Materials 3.1.1 Characteristics of sheeting

    It is a soft steel sheet, cold rolled, galvanized continuously with a surface of Z275 according to P 34.310, or galvanized pre-painted B 15 / E prepared according to Standard P 34-401.

    Another production process is identical to that used in the production of classic trapezoidal sheets with a smooth surface. A track rolling mill is used to roll the sheet into the desired final shape. Sheets are manufactured as trapezoidal sheets or wavy sheets. The most commonly-used sheets of this type are for example COFRASTA, COFRAPLUS or HAIRCOL sheets manufactured in several modified versions. COFRASTA and COFRAPLUS sheets are produced in the Czech Republic, while HAIRCOL sheets are imported from France [3]. 3.1.2 Other steel parts

    The concrete slabs of every specimen were reinforced by Ø8/100/100 mm reinforcing mesh, which should prevent concrete shrinkage cracks in the upper surface. This reinforcement is not considered as a load bearing part of the structure. 3.1.3 Concrete

    We used C20/25 concrete. 3.2 Geometry of thin-walled sheets

    We used COFRAPLUS 60 steel sheets with a plate thickness of 1.0 mm (Fig. 2).

    Fig. 2: Geometry of COFRAPLUS 60

    Fig. 3: Geometry of a COFRAPLUS 60 steel sheet 3.3. Description of assembly

    - the individual components are placed and fixed on the beams using appropriate pistols and fillings, or self-tapping screws, or nuts and bolts; - sheets are supported only at the ends; no middle abutments; - over the whole area of the sheet there must be reinforcing mesh, which should prevent concrete shrinkage cracks in the upper surface; - the concrete is poured using traditional methods; - it is necessary to vibrate the concrete moderately due to the fact that the metal transfers vibrations better than traditional formwork.

    4 Current design methods 4.1 Longitudinal shear for slabs without end

    anchorage [4] The design resistance against longitudinal shear

    should be determined by the m-k method, or by the partial connection method. The partial connection method should only by used for composite slabs with ductile longitudinal shear behavior.

    The longitudinal shear behavior may be considered as ductile if the failure load exceeds the load, causing a recorded end slip of 0,1 mm by more than 10%. If the maximum load is reached at a midspan deflection exceeding L/50, the failure load should be taken as the load at the midspan deflection of L/50.

    If the m-k method is used it should be shown that the maximum design vertical shear VEd for a slab width b does not exceed the design shear resistance V1,Rd determined from the following expression:

    Computational Engineering in Systems Applications (Volume II)

    ISBN: 978-1-61804-014-5 178

  • +

    ⋅⋅= k

    Lb

    AmdbV

    s

    p

    Vs

    p

    Rd γ,1 (1)

    where: b, dp are in mm; Ap is the nominal cross-section of the sheeting

    in mm2; m, k are design values for the empirical factors

    in N/mm2 obtained from slab tests meeting the basic requirements of the m-k method;

    Ls is the shear span in mm; γVs is the partial safety factor for the ultimate

    limit state.

    If the behaviour is ductile, the representative experimental shear force Vt should be taken as 0.5 times the value of the failure load Wt. If the behaviour is brittle this value shall be reduced, using a factor of 0.8.

    From all the test values of Vt the characteristic shear strength should be calculated as the 5% fractile by using an appropriate statistical model and drawn as a characteristic linear regression line, as shown in Fig. 4.

    Fig. 4: Evaluation of test results

    4.2 Manufacturers’ documentation

    In the documentation for these types of structures, their manufacturers and suppliers limit the burden on ceilings or floors for the static scheme and the range, thickness and number of assembly supports. Reported values (for COFRASTA and COFRAPLUS elements) are based on scientific and technical reports prepared by the "Center Scientifique et Technique du Batiment" located in France. This collection of technical expertise defines relations for the determination of marginal deflection and load torque. The effectiveness of the shear connection between steel and concrete in the technical report (CSTB 3/93-390, 2004) is defined as follows:

    RS ττ ≤ (2) where τS is acting shear stress and τR is shear resistance.

    ( )els

    szb

    V

    ⋅=τ (3)

    ( )klhm

    R +⋅⋅

    τ (4)

    where: Vs is the shear force acting in the connection

    after the concrete hardens, l is the span of the structure, b is the width of the element, zel is the arm of the internal forces, (dp-x/3) , dp is the average thickness of the floor, x is the thickness of the compressed part of

    the RC slab, m, k are coefficients determined from

    experiments (CSTB 3/93-390, 2004), h is the total thickness of the floor, ρ is the ratio between metal and concrete in

    the cross section (b.dp).

    Static and dynamic load

    Static load Dynamic load

    m m1=3228 m2=1775 m3=1420 k k1=0.1286 k2=0.5302 k3=0.4242

    Table 1: Experimental coefficients “m” and “k”

    from [1]

    Fig. 5: Diagram of the problem

    The studies were prepared according to French

    standards and regulations. There is no widespread methodology for calculating these types of structures in Central and Eastern Europe, nor is there such a methodology in EC4.

    5 Experiments verifying deflection

    and shear connection The first series of experiments verifying the

    actual behaviour of thin-walled sheets combined

    Computational Engineering in Systems Applications (Volume II)

    ISBN: 978-1-61804-014-5 179

  • with a concrete slab were performed in March 2010. The second series were performed in December 2010. These experiments were focused mainly on the deflection of the samples tested and on verification of the effectiveness of the shear connection between the steel sheet and the concrete slab [5].

    The test specimens were prepared with the following dimensions: width 1.08 m and span 2.0 m. The total thickness "h" of all specimens was 110 mm (50 mm of concrete above the top edge of the steel sheet). The slabs were made without any support in the middle of the span during the concreting. The concrete slabs of each specimen were reinforced by Ø8/100/100 mm reinforcing mesh, which should prevent concrete shrinkage cracks in the upper surface. This reinforcement is not considered as a load bearing part of the structure. We used C20/25 concrete and COFRAPLUS 60 steel sheets with a thickness of 1.0 mm (Fig. 3). After the concreting of the slabs, the test samples were moved to the laboratory and fitted with measuring devices (Fig. 8, Fig 10).

    Fig. 6: Test specimen set-up in the mould for the pouring of concrete

    Fig. 7: Test specimen after pouring of concrete

    5.1 Ideal uniformly distributed load In the experiment the specimens were loaded by

    an ideal uniformly distributed load. This was provided by the use of a unique vacuum loading system, Fig. 9, Fig. 10 [6].

    Fig. 8: Configuration of the measuring device for monitoring sliding on the contact between the

    concrete and the steel sheet

    Fig. 9: Arrangement of formwork around the support structure for the vacuum loading

    experiment

    Fig. 10: Vacuum loading. Configuration of the measuring devices for monitoring slab deflection

    Computational Engineering in Systems Applications (Volume II)

    ISBN: 978-1-61804-014-5 180

  • Fig. 11 and Fig. 12 show the specimen after the

    failure. The failure occurred because the ultimate strength of the connection between the steel sheet and the concrete was reached. The slip of the concrete slab and the steel sheet is shown in Fig. 12.

    Fig. 11: The specimen after the test. Total loss of load carrying capacity

    Fig. 12: Mutual sliding between the concrete and the steel sheet after the failure

    5.2 Four-point bending tests

    Tests should be carried out on simply supported slabs. The test set-up should be shown in Fig. 13 or equivalent. Two equal concentrated line loads, placed symmetrically at L/4 and 3L/4 on the span, should be applied to the specimen.

    Fig. 13: Geometry of test specimens and loading by four-point bending

    The distance between the centre line of the

    supports and the end of the slab should not exceed 100 mm. The width of the bearing plates and the line loads should not exceed 100 mm.

    When the tests are used to determine m and k factors, for each variable to be investigated two groups of three tests (indicated in Fig. 4 by regions A and B) or three groups of two tests should be performed. For the specimens in region A, the shear span should be as long as possible while still providing failure in longitudinal shear and for the specimens in region B, the shear span should be as short as possible while still providing failure in longitudinal shear, but not less than 3ht in length. The following figure, Fig. 14, shows the four-point bending test setup, including the location of sensors recording the vertical deformation of the test specimen. Loading was carried out in repeated press-and-release cycles. 5000 load cycles were performed. After these cycles the specimen was subjected to increasing static loading until it collapsed.

    Fig. 14: Four-point bending test setup, with tested specimen.

    Computational Engineering in Systems Applications (Volume II)

    ISBN: 978-1-61804-014-5 181

  • 6 Conclusions

    Fig. 15: Slip between steel sheet and concrete desk at the edge of the specimen in 4-point bending

    (black dashed lines – static test, red lines – cycling, blue lines – static test after cycling)

    Fig. 16: Comparison of edge slip in 4-point bending (values on left) and vacuum testing (values

    on right)

    Longitudinally profiled thin-walled sheeting with a concrete slab (without any load-carrying reinforcement) is a modern ceiling structure system. The main advantage of this type of structure is in particular its very simple and fast construction process. However, its use is not widespread in Central and Eastern Europe. One of the reasons why this type of structure is not so often used is that there is no generally known and widespread methodology for its design. Test results from uniformly distributed loading are on average 35% higher in comparison to static 4-point bending. Using cyclic loading significantly

    influences the profile of the load deflection curve in comparison to static loading. The deflection grows more uniformly from low loading values without any clear level of major deformations. Acknowledgement These results were achieved with the financial assistance of Ministry of Education, Youth and Sports project No. 1M0579, within the activities of the CIDEAS research centre and projects GAČR 103/09/1258 and GAČR 103/09/H085

    References:

    [1] Ducháček, J., Bajer, M., Barnat, J.: Thin-Walled Steel Plates with Moulded Connection Members in Composite Steel-Concrete Structures, Selected papers from 10th International Conference Modern Buildings Materials, Structures

    and Techniques, Vilnius Gediminas Technical University, 19-21. May 2010, Lithuania, pp. 880-885, ISBN 978-9955-28-594-6

    [2] Ducháček J., Bajer M., Barnat J., 2009; Tenkostěnné profilované plechy s prvky zabezpečujícími spřažení, contribution to the 11th WTA conference 2009, “Sanace a

    rekonstrukce staveb 2009’’ December 2009, Prague, ISBN 978-80-02-02190-2, pp. 253-256

    [3] CSTB Technical report Cofraplus 60, 3/03-390, PAB, ARCELOR Group, 32 rue Gambetta BP 62, F-59264 Onnaing, 2004, pp. 27-34

    [4] EN 1994-1-1; 2004, Eurocode 4 – Design of composite steel and concrete structures – Part 1.1: General rules and rules for buildings

    [5] Z. Kala, J. Kala, Variance-Based Sensitivity Analysis of Stability Problems of Steel Structures using Shell Finite Elements and Nonlinear Computation Methods, In Proc. of the 2nd WSEAS Int. Conf. on Engineering

    Mechanics, Structures and Engineering

    Geology (EMESEG ’09), Rodos Island (Greece), 2009, pp. 89-94.

    [6] MELCHER, J. Full-Scale Testing of Steel and Timber Structures: Examples and Experience, In Structural Assessment - The Role of Large

    and Full Scale Testing, Edited by K.S. Virdi et. al., London: E&FN SPON, 1997, pp. 301 – 308, ISBN 0 419 22490 4.

    Computational Engineering in Systems Applications (Volume II)

    ISBN: 978-1-61804-014-5 182