Transcript
Page 1: Sp725 uk perkins Groupe électrogène, Plantas Eléctricas,

DIESEL GENERATOR

Powered by Perkins Engine

STANDARD SPECIFICATION

ΔOil and fuel filter fitted,water separator

ΔLube-oil drain valve fitted

ΔElectric Starter Charge motor 24 VD.C

ΔWater-cooled

Δbaseskid

ΔAuto start

ΔOptional soundproof and weatherproof canopy

Δ3 pole MCCB Delixi breaker/Optional ABB,set mounted starting battery

ΔOperation & Maintenance manual

ΔSpecial Integrated Steel Base tank and sprayed overall in gloss enamel paint

Voltage regulation maintanined within ±0.5%

Between 0.8 and 1.0 lagging and unity

From no load to full load

At speed droop variation upto 4.5%

Frequency Adjustable Ratio

Frequency Undulation

load from 0-100%,frequency undulation within 0.25%

No load wire volts max undulation ration\ within 1.8%

Three Phrase balanced load in the order of 5%

Effect factor of Telecom

TIF better than 50

THF to IEC60034 Part 40 better than 2%

50HZ, 1500RPM,3-PHASE,400V/230V

PRP ESP PRP ESP

SP800 725 800 580 640 LSA49.1M6

Note:

Perkins EngineModel

Leroy somerAlternator

4006-23TAG2A

(1) Available in the following voltages:220V-240V AND 380V-415V(440V)-50HZ

Power output (KW)

(2) PRP:Prime Power-Continuous duty operation,under variable load 24/24-h-10% overload permissible 1hour/12hours.

(3) Rating Definitions (Operation at Altitude ≤1000m, Ambient temperature ≤ 40℃)Continuous Power.These ratingsare applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power.

Engine & Alternator

Three phase four wire,output voltage 400V/230V,50HZ,between 0.8 lagging,protection capability according with thestandard of NAME1 and IP23.

General Features:

ΔComposed of Perkins diesel engine and Leroy somer alternator

Voltage Regulation

Change load from 0-100%,within 1.0%( electric speedregulator),within 4.5%( mechanical speed regulator)

Gensetsmodel

Power output(KVA)

Page 2: Sp725 uk perkins Groupe électrogène, Plantas Eléctricas,

BrushlessCast alloy aluminumSingle,double shielded

100% copperReconnectable

Class H2/3Full

R448±0.5%

StandardIP23<50

AREP

Noise level dBA@7m ≤70dBA(canopy type) HQ container type

Alternator Technical data

Exhaust Gas Temperature ℃ 480 3380×1500×2100

Exhaust Gas flow m3/min 102.4 Enclosure type:L*W*H,mm

Battery Volatge 24VDC Gensets Dimensions & Weight

Governing Type Electrical (governor) Open type:L*W*H,mm

Displacement L 22.92 BS5514,AS1359,ICE34

Lubricant system Capacity L 73.8 CE Compliance

Coolant Capacity L 122.7 ISO9001:2000,ISO3046

Starting System Electric 24 volt DC ISO8528 BS4999

Rated Output kwb/HP 646/866 ΔTrailer type Gensets

Exhaust air flow (m3/min) 765 QUALITY STANDARDS

100% Load Fuel Consumption L/H 155 ΔRemote Control Panel

Engine Speed/Frequency RPM/Hz 1500/50HZ Δweatherproof/soundproof Canopy

Compress the ratio 14.5:1 ΔParallel control panels

Cooling system Water-cooled ΔCircuit Breaker MCCB & ACB

Aspiration Turbocharged ΔEngine oil feeding and drain pump

Bore/Stroke 160X190 ΔAuto Transfter Switch( ATS)

Engine Model: Perkins 4006-23TAG2A ΔLow fuel level alarm shutdown

Type 6 cylinder,4 cycle diesel ΔAutomatic Fuel Filling System

EXHAUST SYSTEM--Heavy duty industrial exhauset silencer with flexible piping.

Technical Data SheetGenerating sets model:

400V,50Hz,1500 rpm Genset Optional Features

ENGINE--Industrial 4 stroke cooled diesel engine complete with air,fuel and oil filters,electric starting and chargingequipment,engine protection against low water level.

ALTERNATOR--Brushless,self exciting,self regulation,sreen protected,drip proof rated in accordance withIEC60034.Voltage regulation maintainted within ±0.5% from no load to full load.between 0.8 lagging and unity.Allstandard voltages available.

COOLING--Radiator and colling fan complete with protection guards,designed to cool engine at specified output in airtemperatures upto 45 ℃,radiators suitable for higher temperatures are available.Low water level protection fitted asstandard.

ELECTRICAL SYSTEM--24V upto.Axial type starter motor,battery charging alternator,high capacity lead acidbattery,and battery tray mounted on the generator base frame,and heavy duty interconnecting cable with terminations.

LEROY SOMER

ΔBrushless,self excited Exciter

Δclass "H" insulation Cooling Fan

Δ Standard degree of protection is IP23 Bearing

Δself regulating Windings

Δ With fan cooling Connection Type

Δ Resist Humid grease Insulation Type

Overexcitation Protection

ΔAC excitation,roating rectification tube Pitch

Δ Stator grease insulation covered Amortisseur Winding

ΔRotator and exciation high polymer,Resist thecorruption of oil and acid

A.V.R modelVoltage Regulator NL-FL

Δ Rotator ballance is in accordance with BS5625standard 12.5

Underspeed Protection

Δ High-quality lubrication sealed long-time bearing TIF (1960 Weightings)

Δ Rotator sillicon steel close tight Exciation System

Page 3: Sp725 uk perkins Groupe électrogène, Plantas Eléctricas,

ΔEngine control,Generator protectionΔBuilt in alarms and warningsΔRemote Start operation availableΔDaily / weekly / monthly exerciserΔWeekly operation schedule programsΔFuel pump controlΔECU control and monitoring via J1940 CANBUSΔMains simulationΔBlock heater controlΔField adjustable parameters

FUZHOU SUNSHINE MACHINERY CO.,LIMITEDADD:NO.6 Gulouyuan, Juyuanzhou Industrial Zone, Jinshan Development Area, Fuzhou, Fujian, China.

TEL:86-591-88204179 FAX:86-591-87985719

Δbody made from steelcomponents treated withpolyester powder coating

Excellent Access for Maintenance

Δtwo large doors on each side

Δradiator fill access plate

ΔI/O expansion capability

Email:[email protected] http://www.sunshinemach.com

Δcooling fan and battery charging alternator fullyguardedΔexhaust silencing system totally enclosed for operator s

Δlube oil and cooling water drains pipes to exterior ofthe enclosureSecurity and SafetyΔcontrol panel viewing window in a lockable accessdoorΔemergency stop push buttom (red)mounted onenclosure interior

Sound Attenuated Enclosure/Option

Robust Corrosion Resustant Construction

Δ Black finish stainless stell lock and hinges

Control module ComAp AMF25 ΔFree MS-Windows Remote monitoringΔLED displaysΔConfigurable analogue inputs

c) Control module:Standard collocation is ComAp AMF25 Auto start with AMF.

Main Features:ΔAutomatic mains failure

Control Panel- ComAP

The base mounted control panel in a vibration isolated sheet steel enclosure.The control panel is equipped as follows:

a)Instruments:Analogue Volmeter,Hours Run Meter.Water pressure Meter.

b) Controls:Emergency Stop Pushbutton,Volmeter Phase Selector Switch.