equations importants.pdf

Embed Size (px)

Citation preview

  • Documentazione Tecnica CIB Unigas - Campodarsego (PD)

    ConformeEMC 79/336/CEE

    LV 73/23/CEE

    MANUEL- INSTALLATION- UTILISATION- ENTRETIEN

    BRULEURS A FIOUL

    G4 G6G10 G18

    VERSION A 1 ALLURE

    M03964EC Rev. 02 06/02

  • INSTRUCTIONS2

    INSTRUCTIONSCE MANUEL DINSTALLATION, DUTILISATION ET DENTRETIEN FAIT PARTIE INTEGRANTE ET ESSENTIELLE DUPRODUIT ET DOIT ETRE REMIS A LUTILISATEUR.LES INSTRUCTIONS CONTENUES DANS CE CHAPITRE SERONT UTILES A LUTILISATEUR ET AU PERSONNELCHARGE DU MONTAGE ET DE LENTRETIEN DES APPAREILS.LUTILISATEUR TROUVERA DES INFORMATIONS SUPPLEMENTAIRES SUR LE FONCTIONNEMENT ET LES LIMITESDUTILISATION DES APPAREILS DANS LA 2ME PARTIE DE CE MANUEL QUE NOUS RECOMMANDONS DE LIREAVEC ATTENTION.CONSERVER LE MANUEL POUR LE CONSULTER EN CAS DE BESOIN.

    1) INSTRUCTIONS GENERALES Linstallation doit tre effectue par un professionnel quali-

    fi, daprs les instructions du constructeur et conform-ment aux normes en vigueur.

    Par professionnel qualifi, on entend un professionnelayant acquis la comptence technique dans le domainedapplication de lappareil (civil ou industriel), notammentles techniciens des services aprs-vente agrs par le con-structeur.

    Le constructeur dcline toute responsabilit pour les dom-mages causs aux personnes, aux animaux ou aux chosesdrivant dune installation non correcte.

    Retirer lemballage et vrifier le bon tat du contenu.Au moindre doute, sadresser au fournisseur avant dutiliserlappareil.Pour des motifs de scurit, les lments de lemballage(caisse en bois, clous, agrafes, sacs en plastique, polystyrneexpans, etc.) ne doivent pas tre laisss la porte desenfants. Avant de procder toute opration de nettoyage ou

    dentretien, dbrancher lappareil du rseau de distributiondlectricit au moyen de linterrupteur de linstallation et/ou des organes de coupure.

    Veillez ce que les grilles daspiration ou de ventilation nesoient pas bouches.

    En cas de panne ou de mauvais fonctionnement de lappa-reil, nessayez pas de corriger vous-mme le problmemais adressez-vous un professionnel qualifi.

    La rparation des appareils ne devra tre effectue que parun service aprs-vente agr par le constructeur et exclusive-ment avec les pices dorigine.Le non respect de ces prescriptions peut compromettre lascurit de lappareil.Pour obtenir un fonctionnement correct et un bon rendementde lappareil, il est indispensable:de faire effectuer un entretien priodique par un personnelqualifi daprs les instructions du constructeur. Au cas o lappareil ne serait plus utilis, dsactiver les

    parties susceptibles de devenir des sources de danger. Le brleur doit toujours tre accompagn du livret

    dinstructions. Au cas o lappareil serait vendu ou passe-rait un autre propritaire, ou sil devait rester en placepour cause de dmnagement, ne pas oublier de remettrele manuel au nouveau propritaire et/ou linstallateur.

    Pour tous les appareils dots doptions ou de kits (lectri-ques inclus) utiliser exclusivement des accessoires dori-gine.

    Cet appareil devra tre destin lusage pour lequel il at prvu. Tout autre usage doit tre considr commeimpropre et par consquent dangereux.

    Le constructeur dcline toute responsabilit contractuelle etextra contractuelle pour les dommages drivant dune instal-lation et dune utilisation non correctes et du non respect desinstructions.

    2) PRECAUTIONS PARTICULIERES POUR BRULEURS Le brleur doit tre install dans une pice convenable

    avec des ouvertures minimales de ventilation dictes parles normes en vigeur et de toute faon suffisantes pourobtenir une combustion parfaite.

    Utiliser exclusivement des brleurs construits conform-ment aux normes en vigueur.

    Ce brleur devra tre destin lutilisation pour laquelle il at prvu.

    Avant deffectuer les connexions, vrifier que les donnesindiques sur la plaque correspondent celles du rseaudalimentation (lectrique, gaz, fuel ou autre combustible).

    Ne pas toucher les parties chaudes du brleur situeshabituellement en proximit de la flamme ou du systmede prchauffage du combustible; elles chauffent durant lefonctionnement du brleur et ne se refroidissent quaprsun arrt prolong.

    En cas de non utilisation dfinitive du brleur, faire effectuerpar un professionnel qualifi les oprations suivantes:a) Dbrancher lalimentation lectrique en enlevant le cble

    dalimentation de linterrupteur gnral.b Fermer lalimentation du combustible au moyen de la

    vanne manuelle de fermeture en retirant les poignes decommande de leur logement.

    Prcautions particulires Vrifier que linstallateur ait solidement fix le brleur au

    gnrateur de chaleur de manire que la flamme se pro-duise lintrieur de la chambre de combustion du gnra-teur.

    Avant de mettre en route le brleur, et au moins une foispar an, faire effectuer par un professionnel qualifi lesoprations suivantes:

    a) Rgler le dbit du combustible du brleur selon la puis-sance requise par le gnrateur de chaleur.

    b) Rgler le dbit dair comburant afin dobtenir une valeur derendement de combustion au moins gale au minimumprescrit par les normes en vigueur.

    c) Excuter le contrle de combustion afin dviter la forma-tion dlments nuisibles ou polluants au del des limitesconsenties par les normes en vigueur.

    d) Vrifier le bon fonctionnement des dispositifs de rglage etde scurit.

    e) Vrifier le bon fonctionnement du conduit dvacuation desproduits de la combustion.

    f) Aprs avoir effectu tous les rglages, contrler que tousles systmes de blocage mcaniques des dispositifs derglage soient bien serrs.

    g) Vrifier que les instructions relatives lutilisation et lentretien du brleur se trouvent dans la chaufferie.

    En cas de mises en scurit rptes du brleur, viter demultiplier les tentatives de rarmement manuel. Pourremdier lanomalie, faire appel un technicien qualifi.

    Lutilisation et lentretien de lappareil doivent tre confis un professionnel qualifi, aux termes des dispositions envigueur.

  • INSTRUCTIONS 3

    3) INSTRUCTIONS GENERALES EN FONCTION DU TYPE DALIMENTATION3a) ALIMENTATION ELECTRIQUE Seule une mise la terre correcte, conforme aux prescrip-

    tions des normes en vigueur, est en mesure de garantir lascurit de lappareil.

    Il est ncessaire de vrifier que cette prescription fonda-mentale ait t respecte. Dans le doute, sadresser unpersonnel qualifi et faire procder un contrle rigoureuxde linstallation lectrique car le constructeur dcline touteresponsabilit relative aux dommages causs dfaut demise la terre de linstallation.

    Demander un professionnel qualifi de vrifier quelinstallation lectrique -et notamment la section des cbles-soit adapte la puissance maximum (indique sur laplaque) absorbe par lappareil.

    Pour lalimentation gnrale de lappareil en lectricit, ilest interdit dutiliser des adapteurs, des prises multiples et/ou des rallonges.

    Pour la connexion au rseau lectrique, utiliser un interrup-teur omnipolaire comme le prescrivent les normes de scu-rit en vigueur.

    Lutilisation de tout appareil plac sous tension impliqueque quelques rgles fondamentales soient observes: ne jamais toucher lappareil si certaines parties du corpssont mouilles ou humides et/ou si lon est a pieds nus ne pas tirer les cbles lectriques ne pas exposer lappareil aux intempries atmosphri-ques (pluie, soleil, etc.), sauf disposition contraire. interdire lutilisation de lappareil aux enfants ou aux per-sonnes inexpertes.

    Le cble dalimentation de lappareil ne doit pas tre rem-plac par lutilisateur. Au cas o il serait endommag,teindre lappareil et faire appel un professionnel qualifi.

    Lorsque lappareil nest pas utilis pendant une certainepriode, il convient de mettre hors circuit les composants utili-sant lnergie lectrique (pompes, brleur, etc.).

    3b) ALIMENTATION AU GAZ, FIOUL OU AUTRES COMBUSTIBLESInstructions gnrales Linstallation doit tre effectue conformment aux nor-

    mes et aux dispositions en vigueur par un professionnelqualifi; le constructeur dcline toute responsabilit desdommages causs aux personnes, aux animaux et auxchoses drivant dune installation non correcte.

    Avant linstallation, il est recommand de nettoyer avec leplus grand soin la partie interne des conduits dalimenta-tion en combustible afin dliminer tout dpt qui risqueraitde compromettre le bon fonctionnement du brleur.

    Avant la premire mise en service du brleur, faire effec-tuer par un professionnel qualifi les contrles suivants:

    a) ltanchit interne et externe de linstallation dalimenta-tion en combustible,

    b) la rgulation du dbit du combustible selon la puissancerequise par le brleur

    c) le type de combustible, qui doit tre celui pour lequel lebrleur est prvu;

    d) la pression dalimentation du combustible, qui doit trecomprise dans les valeurs indiques sur la plaque;

    e) que linstallation dalimentation du combustible soit dimen-sionne pour le dbit ncessaire au brleur et quelle soitmunie de tous les dispositifs de scurit et de contrle pre-scrits par les normes en vigueur.

    Lorsque le brleur nest pas utilis pendant une certainepriode, fermer le (les) robinet(s) dalimentation du combu-stible.

    Prcautions particulires pour lemploi du gazFaire effectuer par un professionnel qualifi les contrles sui-vants:a) que la ligne dalimentation et la rampe gaz soient confor-

    mes aux normes et aux prescriptions en vigueurb) que tous les raccords gaz soient tanchesc) que les ouvertures daration du local chaudire soient

    conformes aux prescriptions des normes en vigueur etquelles garantissent une parfaite combustion.

    Ne jamais utiliser les tuyaux du gaz pour la mise la terredappareils lectriques.

    Ne pas laisser le brleur inutilement sous tension lorsquilnest pas utilis et ne jamais oublier de fermer le robinet dugaz.

    En cas dabsence prolonge de lutilisateur, fermer le robi-net principal dalimentation en gaz du brleur.

    Sil se dgage une odeur de gaz:a) ne pas actionner dinterrupteurs lectriques, le tlphone

    ou tout autre appareil qui pourrait provoquer des tincelles;b) ouvrir immdiatement portes et fentres afin de crer un

    courant dair pour ventiler le local;c) fermer les robinets du gaz,d) faire appel un professionnel qualifi. Ne jamais obstruer les ouvertures de ventilation du local o

    est install un appareil gaz afin dviter tout danger dri-vant de la formation de mlanges toxiques et explosifs.

  • PARTIE I: MANUEL D'INSTALLATION4

    DONNES TECHNIQUES

    IDENTIFICATION DES BRULEURSLa denomination du brleur est identifie par le type et le modle. La description du modle est explique ci-dessous:

    Type: G4 Modle: G-. TN. S. FR. A. P(1) (2) (3) (4) (5) (6) (7)

    (1) BRULEUR TYPE(2) COMBUSTIBLE G - Fioul(3) REGLAGE versions disponibles TN - 1 allure(4) LONGUEUR BUSE (Voir ctes d'encombrement)

    versions disponibles S - StandardL - Rallonge

    (5) PAYS DE DESTINATION FR - France(6) VERSION A - Standard

    B - Four de boulangerieC - Four de boulangerie avec prise dair exterieurD - ChefF - Chef specialN - Rglage air interieur (G4)S - Rglage air interieur et sans connecteur (G4)Y - SpecialZ - Sans capot

    (7) EQUIPMENT M - Verin hydrauliqueP - RechaffeurL - Rechaffeur plus verin hydraulique

    BRULEURS SERIE POLYMATIC G4 G4....PPuissance mini. kcal/h 18.000 12.000

    maxi. kcal/h 35.000 35.000mini. kW 21 14maxi. kW 41 41

    Dbit Kg/h mini. 1.8 1.2Kg/h maxi. 3.5 3.5

    Combustible fioul fioulAlimentation lectrique 230 V - 50 Hz 230 V - 50 HzMoteur 2800 t/m W 75 75A absorbs 0.65 0.65Puissance lectrique W 375 475Poids Kg ca. 12.5 12.5Regolazione 1 allure 1 allureRchauffeur non oui

    BRULEURS SERIE MINIFLAM G6 G10 G18Puissance mini. kcal/h 25.000 50.000 90.000

    maxi. kcal/h 60.000 100.000 180.000mini. kW 29 58 105maxi. kW 70 116 209

    Dbit Kg/h mini. 2.5 5 9Kg/h maxi. 6 10 18

    Combustible fioul fioul fioulAlimentation lectrique 230 V - 50 Hz 230 V - 50 Hz 230 V - 50 HzMoteur 2800 t/m W 100 150 200A absorbs 0.75 1.1 1.4Puissance lectrique W 400 450 500Poids Kg ca. 14.5 16 17Regolazione 1 allure 1 allure 1 allureRchauffeur non non non

    PARTIE I: MANUEL D'INSTALLATION

  • PARTIE I: MANUEL D'INSTALLATION 5

    COTES DENCOMBREMENT EN mm

    Fig. 1

    PLAGES DE TRAVAIL

    A B BL C CL D E G K H P MG4 - G4P 230 35 55 35 130 285 360 295 230 80 175 90 85 134 M8

    A B BL C CL D E G K H P MG6 290 35 60 170 350 - 310 230 80 190 90 85 134 M8

    G10 275 80 200 355 475 340 255 90 230 125 121 134 M8G18 275 80 200 355 475 340 255 115 230 125 121 134 M8

    CON

    TRE-

    PRES

    SIO

    N EN

    CHA

    MBR

    ED

    E CO

    MBU

    STIO

    N EN

    mba

    r

    kW

    Fig. 2

    CONT

    RE-P

    RES

    SIO

    N EN

    CHA

    MBR

    ED

    E C

    OM

    BUST

    ION

    EN m

    bar

    kW

    Fig. 3

    0

    0,1

    0,2

    0,3

    0,4

    8 12 16 20 24 28 32 36 40

    G4G4P

    00,20,40,60,8

    11,21,4

    10 30 50 70 90 110 130 150 170 190 210 230

    G6 G10 G18

  • PARTIE I: MANUEL D'INSTALLATION6

    MONTAGE ET RACCORDEMENTSEmballageLes brleurs sont livrs dans des emballages en carton aux dimensions:G4..S 330 - 320 - 300 mm (L x A x P)G4..L 390 - 320 - 300 mm (L x A x P)G6 360 - 300 - 450 mm (L x A x P)G10..S - G18..S 420 - 350 - 420 mm (L x A x P)G10..L - G18..L 420 - 350 - 620 mm (L x A x P)Les emballages en carton craignent lhumidit et ne sont pas adapts pour tre empils.Contenu de chaque emballage:1 brleur2 tuyaux flexibles1 filtre1 joint interposer entre le brleur et la chaudire1 enveloppe contenant le manuel.Pour lliminiation des anciens brleurs, se conformer aux procdures prescrites par les lois en vigueur en matire dliminiationdes dchets.

    Montage brleur la chaudireFixer la bride dattache du brleur la chau-dire en suivant les indications de la Fig. 4 afindobtenir une inclinaison correcte de la busevers la chambre de combustion.

    Fig. 4

    Schma connexions lectriques.! retirer le capot du brleur;! tablir les connexions lectriques sur le bornier dalimentation selon les indications des schmas de la Fig. 5a et Fig. 5b;! remettre en place le capot du brleur.

    Seulement G4 G-.TN.x.xx.S.x

    Fig. 5a

    Tous les models sauf G4 G-.TN.x.xx.S.x

    Fig. 5b

    RESPECTER LES REGLES FONDAMENTALES DE SECURITE, CONTROLER LA MISE A LA TERRE, NE PAS INVERSER LES CONNEXIONS DE PHASE ET DE NEUTRE, PREVOIR UN INTERRUPTEUR DIFFERENTIEL

    MAGNETO THERMIQUE DE PUISSANCE ADAPTEE POUR LE RACCORDEMENT AU RESEAU ELECTRIQUE.

  • PARTIE I: MANUEL D'INSTALLATION 7

    SCHEMA DINSTALLATION DES CONDUITS DALIMENTATION EN FIOUL

    Fig. 6Lgende1 Brleur2 Tuyaux flexibles (fourni)3 Filtre fioul (fourni)4 Vanne darrt (*)5 Clapet anti-retour (*)6 Vanne7 Vanne fermeture rapide ( lextrieur des locaux rservoir et chaudire)(*) Obligatoire uniquement pour les installations alimentation par gravit, siphon ou circulation force

    Installation monotubeLes brleurs que nous construisons sont prvus pour lalimentation 2 tubes.Il est toutefois possible de les adapter aux installations monotube (que lon conseille en cas dalimentation par gravit).Consulter lappendice qui illustre en dtail les oprations excuter.

    Dterminiation du diamtre des conduits dalimentation en fioul

    Fig. 7

    Tab. 1 Tab. 2 Tab. 3H

    (m)L (m) H

    (m)L (m) H

    (m)L (m)

    6 8 10 6 8 10 12 6 8 10 120 41 100 100 0 19 77 100 100 0 18 73 100 100

    0.5 70 100 100 1 24 90 100 100 0.5 15 66 100 1001 100 100 100 2 30 100 100 100 1 13 59 100 100

    1.5 100 100 100 3 34 100 100 100 1.5 10 52 100 1002 100 100 100 4 39 100 100 100 2 7 44 100 100

    2.5 100 100 100 5 44 100 100 100 2.5 5 44 100 1003 100 100 100 6 48 100 100 100 2.5 - 37 100 100

    3.5 100 100 100 7 52 100 100 100 3 - 30 85 1004 100 100 100 8 56 100 100 100 3.5 - 23 68 100

    4.5 100 100 100 9 55 100 100 100 4 - - - 1005 100 100 100 10 51 100 100 100 4.5 - - - -

    De la cuve

    A la cuve

  • PARTIE I: MANUEL D'INSTALLATION8

    REGLAGESRglage du dbit fioulPour rgler le dbit du fioul, choisir un gicleur de dimension adquate et rgler la pression de refoulement de la pompe (voirschma gnral du circuit fioul sur la Fig. 8).Pour le choix du gicleur, se reporter au Tab. 4; pour le rglage de la pression de la pompe, voir les indications Page 9 etPage 10. Des informations supplmentaires sur les caractristiques des pompes fioul se trouvent dans lappendice.Amorage pompeAvant deffectuer les rglages, il est ncessaire damorcer la pompe du fioul en procdant de la manire suivante:! Avant de mettre en fonctionnement le brleur, contrler que le conduit de retour la cuve ne soit pas obstru. Tout obstacle

    provoquerait la rupture de lorgane dtanchit de la pompe.! Mettre en route le brleur, clairer la cellule photorsistante aprs louverture de llectrovanne et vacuer lair travers le

    raccord du manomtre.

    Tab. 4 - Choix du gicleur fioul

    LgendeEV Electrovanne fioulM ManomtreP Pompe

    Fig. 8

    10 bar 12 bar 14 barG.P.H. Kg/h kcal/h kW Kg/h kcal/h kW Kg/h kcal/h kW

    0.40 1.52 15.500 18 1.67 17.100 19.8 1.80 18.400 21.40.50 1.90 19.400 22.5 2.08 21.200 24.6 2.25 22.900 26.60.60 2.28 23.250 27 2.50 25.500 29.6 2.70 27.500 31.90.65 2.47 25.200 29.2 2.71 27.600 32 2.92 29.800 34.60.75 2.85 29.100 33.8 3.12 31.800 36.9 2.7 34.400 400.85 3.23 33.000 38.3 3.54 36.100 41.9 3.82 39.000 45.31.00 3.80 38.800 45 4.16 42.400 49.2 4.50 45.800 53.21.10 4.18 42.600 49.5 4.58 46.700 54.2 4.95 50.500 58.61.20 4.56 46.500 54 5.00 51.000 59.2 5.40 55.500 64.41.25 4.75 48.400 56.2 5.20 53.00 61.5 5.60 57.100 66.31.35 5.13 52.300 60.7 5.62 57.000 66.2 6.07 62.000 721.50 5.70 58.000 67.3 6.24 63.600 73.9 6.75 69.000 80.11.65 6.27 64.000 74.4 6.86 69.900 81.3 7.42 76.000 88.31.75 6.65 68.000 79 7.28 74.200 86.3 7.87 80.000 932.00 7.60 77.500 90.1 8.32 84.800 98.6 8.99 92.000 106.92.25 8.55 87.200 101.4 9.36 95.400 111 10.12 103.000 119.72.50 9.50 97.000 112.8 10.40 106.000 123.3 11.24 115.000 133.73.00 11.40 116.000 134.9 12.48 127.200 148 13.49 137.000 159.33.50 13.30 135.800 157.9 14.56 148.750 173 15.74 160.700 186.94.00 15.20 155.200 180.4 16.65 170.000 197.7 17.99 183.700 213.64.50 17.10 174.600 203 18.73 191.250 222.4 20.24 206.650 240.3

  • PARTIE I: MANUEL D'INSTALLATION 9

    POMPES FIOUL SERIE POLYMATIC

    Lgende1 Rgulateur de pression2 Prise manomtre3 Prise vacuomtre4 Electrovanne5 Vers le gicleur7 Aspiration8 Retour

    Pompe Suntec AS47 A

    Fig. 9

    Viscosit 2 - 12 mm/s (cSt)Temprature du fioul 0 - 60 C dans la pompe.Pression d'arrive 2 bar maxi.Pression de retour 2 bar maxi.Hauteur d'aspiration 0,45 bar maxi. de vide pour viter le

    dgazage du fioul.Vitesse de rotation 3600 t/min. maxi.

    Pompe DELTA VM1RL2

    Fig. 10

    Viscosit 2 - 50 mm/s (cSt)Temprature du fioul 0 - 60 C dans la pompe.Pression d'arrive 2 bar maxi.Pression de retour 2 bar maxi.Hauteur d'aspiration 0,5 bar maxi. de vide pour viter le

    dgazage du fioul.Vitesse de rotation 3500 t/min. maxi.

    Pompe DANFOSS BFP21R3

    Fig. 11

    Viscosit 1.3 - 12 mm/s (cSt)Temprature du fioul 70 C dans la pompe.Pression d'arrive 2 bar maxi.Pression de retour 2 bar maxi.Hauteur d'aspiration 0,35 bar maxi. de vide pour viter le

    dgazage du fioul.Vitesse de rotation 3600 t/min. maxi.

    Pompe Suntec AS47 C

    Fig. 12

    Viscosit 2 - 12 mm/s (cSt)Temprature du fioul 0 - 60 C dans la pompe.Pression d'arrive 2 bar maxi.Pression de retour 2 bar maxi.Hauteur d'aspiration 0,45 bar maxi. de vide pour viter le

    dgazage du fioul.Vitesse de rotation 3600 t/min. maxi.

  • PARTIE I: MANUEL D'INSTALLATION10

    Lgende1 Rgulateur de pression2 Prise manomtre3 Prise vacuomtre4 Electrovanne5 Vers le gicleur7 Aspiration8 Retour

    REGLAGE DEBIT AIR

    Pompe DELTA VM1LR2

    Fig. 13

    Viscosit 2 - 50 mm/s (cSt)Temprature du fioul 0 - 60 C dans la pompe.Pression d'arrive 2 bar maxi.Pression de retour 2 bar maxi.Hauteur d'aspiration 0,5 bar maxi. de vide pour viter le

    dgazage du fioul.Vitesse de rotation 3500 t/min. maxi.

    Pompe DANFOSS BFP21L3

    Fig. 14

    Viscosit 1.3 - 12 mm/s (cSt)Temprature du fioul 70 C dans la pompe.Pression d'arrive 2 bar maxi.Pression de retour 2 bar maxi.Hauteur d'aspiration 0,35 bar maxi. de vide pour viter le

    dgazage du fioul.Vitesse de rotation 3600 t/min. maxi.

    Fig. 15 Fig. 16 Fig. 17

    Type G4 mod. G-.TN...N.x et G-.TN...S (rglage air interieur)! Desserrer la vis VBS.! Rgler le dbit de lair en dplaant la

    vis VBS le long de la fente de rglage.! Serrer de nouveau la vis VBS.

    Type G4 mod. G-.TN.x.FR.A.x (rglage air exterieur)! Rgler le dbit de lair en tournant la vis

    VBS.

    Type G6 - G10 - G18! Desserrer la vis VBS et tourner

    manuellement le clapet daircomme lindiquent les flches.

    ! Serrer de nouveau la vis VBS.

    VBSVBS VBS

  • PARTIE I: MANUEL D'INSTALLATION 11

    REGLAGE DE LA TETE DE COMBUSTIONAvec un tournevis, tourner la vis VRT dans le sens horaire ou anti-horaire afin dobtenir respectivement la puissance maximumou minimum. Au cas o la tte de combustion devrait tre remplace, rtablir la position indique sur les figures Fig. 21a et Fig.21b par rapport lextrmit du gicleur.

    Type G4 - G4....P Fig. 18

    Type G6 Fig. 19

    Type G10 - G18Avec un tournevis, tourner la vis VRT dans le senshoraire ou anti-horaire afin dobtenir respective-ment la puissance minimum ou maximum (+/-). Aucas o la tte de combustion devrait tre rem-place, rtablir la position indique sur la Fig. 20 (etTab. 9) par rapport lextrmit du gicleur.

    Fig. 20

    VRT

    VRT

    VRT

  • PARTIE I: MANUEL D'INSTALLATION12

    REGLAGE DE LA COMBUSTION

    Tab. 5 -Type G4

    Tab. 5a - Type G4 avec rchaffeur

    Tab. 6 - Type G6

    Tab. 7 - Type G10

    Tab. 8 -Type G18

    GICLEURG.P.H. 60

    PRESSION POMPEBAR

    DEBITKg/h 10%

    REGLAGE INDEX TETE

    REGLAGE INDEX CLAPET

    0.40 10 - 12 1.52 - 1.66 1 - 1.5 3.5 - 3.50.50 10 - 12 1.90 - 2.08 1.5 - 1.5 4.5 - 50.60 10 - 12 2.28 - 2.50 2.5 - 2.5 5 - 60.65 10 - 12 2.47 - 2.70 2.5 - 3 6.5 - 80.75 10 - 12 2.85 - 3.12 4.5 - 5 6.5 - 8.5

    GICLEURG.P.H. 60

    PRESSION POMPEBAR

    DEBITKg/h 10%

    REGLAGE INDEX TETE

    REGLAGE INDEX CLAPET

    0.40 10 - 12 1.25 - 1.36 1.5 - 1.5 3 - 3.50.50 10 - 12 1.70 - 1.86 2 - 2 3.5 - 40.60 10 - 12 2.22 - 2.41 2 - 2 5.5 - 70.65 10 - 12 2.31 - 2.46 2.5 - 3 5 - 5.50.75 10 - 12 2.76 - 3 3.5 - 3.5 5.5 - 7

    GICLEURG.P.H. 60

    PRESSION POMPEBAR

    DEBITKg/h 10%

    REGLAGE INDEX TETE

    REGLAGE INDEX CLAPET

    0.60 10 - 12 2.35 - 2.60 1.5 - 1.5 4 - 40.75 10 - 12 3.00 - 3.30 2 - 2.5 5.2 - 60.85 10 - 12 3.40 - 3.85 3 - 4 5.5 - 61.00 10 - 12 3.90 - 4.20 3.5 - 4.5 7 - 71.10 10 - 12 4.10 - 4.50 4 - 6 7 - 71.20 10 - 12 4.70 - 5.20 6.5 - 7.5 7.5 - 81.35 10 - 12 5.40 - 5.80 9 - 10 8 - 8

    GICLEURG.P.H. 60

    PRESSION POMPEBAR

    DEBITKg/h 10%

    REGLAGE INDEX TETE

    REGLAGE INDEX CLAPET

    1.20 10 - 12 4.80 - 5.10 0 - 0 1.5 - 1.81.35 10 - 12 5.35 - 5.80 1 - 1 2 - 2.31.50 10 - 12 5.95 - 6.60 2 - 2 2.3 - 2.71.75 10 - 12 7.00 - 7.40 3 - 5 3 - 3.52.00 10 - 12 7.80 - 8.60 6 - 8 3.7 - 42.25 10 - 12 8.90 - 9.60 8 - 8.5 4 - 52.50 10 - 12 9.40 - 10.50 8.5 - 10.5 5 - 6

    GICLEURG.P.H. 60

    PRESSION POMPEBAR

    DEBITKg/h 10%

    REGLAGE INDEX TETE

    REGLAGE INDEX CLAPET

    2.25 10 - 12 8.95 - 9.40 5 - 5.5 4 - 52.50 10 - 12 9.50 - 10.40 5.5 - 7 5 - 52.75 10 - 12 10.70 - 11.75 7 - 9.5 5 - 53.00 10 - 12 11.80 - 12.85 10 - 11 5 - 53.50 10 - 12 13.85 - 15.00 12 - 14 6 - 74.00 10 - 12 15.35 - 16.65 15 - 17 7 - 84.50 10 - 12 17.00 - 18.00 18 - 20 8 - 8

  • PARTIE II: MANUEL DUTILISATION 13

    LIMITES DUTILISATION

    LE BRULEUR EST UN APPAREIL CONU ET CONSTRUIT POUR NE FONCTIONNER QUAPRES AVOIR ETE COR-RECTEMENT ACCOUPLE A UN GENERATEUR DE CHALEUR (EX. CHAUDIERE, GENERATEUR DAIR CHAUD, FOUR,ETC.). TOUTE AUTRE UTILISATION DOIT ETRE CONSIDEREE COMME IMPROPRE ET PAR CONSEQUENT DANGE-REUSE.

    LUTILISATEUR DOIT GARANTIR LE MONTAGE CORRECT DE LAPPAREIL EN SADRESSANT A UN PERSONNELQUALIFIE POUR LA REALISATION DE LINSTALLATION. LE PREMIER ALLUMAGE DEVRA ETRE EFFECTUE PAR UNTECHNICIEN DUN SERVICE APRES-VENTE AGREE PAR LE CONSTRUCTEUR.A CE PROPOS, LA CONNEXION ELECTRIQUE AUX ORGANES DE REGLAGE ET DE SECURITE DU GENERATEUR(THERMOSTATS DE TRAVAIL, SECURITE, ETC.) ASSUME UNE IMPORTANCE FONDAMENTALE ET GARANTIT UNFONCTIONNEMENT CORRECT ET SANS DANGER DU BRULEUR.

    LA MISE EN SERVICE DE LAPPAREIL EST ASSUJETTIE AU RESPECT DES MODALITES DINSTALLATION PRESCRI-TES PAR LE CONSTRUCTEUR. TOUTE MANIPULATION (EX. DECONNEXION TOTALE OU PARTIELLE DE CON-DUCTEURS ELECTRIQUES, OUVERTURE DE LA PORTE DU GENERATEUR, DEMONTAGE DE PARTIES DU BRULEUR)VISANT A APPORTER, TOTALEMENT OU EN PARTIE, CERTAINES MODIFICATIONS EST FORMELLEMENT INTER-DITE.

    NE JAMAIS OUVRIR OU DEMONTER AUCUN COMPOSANT DE LAPPAREIL.

    AGIR EXCLUSIVEMENT SUR LINTERRUPTEUR GENERAL (ON-OFF) QUI SERT EGALEMENT POUR LARRETDURGENCE ETANT DONNE SON ACCES FACILE ET LA RAPIDITE DE LA MANOEUVRE ET EVENTUELLEMENT SURLE BOUTON DE DEVERROUILLAGE.

    EN CAS DE BLOCAGES REPETES, EVITER DE MULTIPLIER LES TENTATIVES DE REMISE EN MARCHE EN APPU-YANT SUR LE BOUTON DE DEVERROUILLAGE. FAIRE APPEL A UN TECHNICIEN QUALIFIE QUI SE CHARGERA DEREMEDIER A LANOMALIE.

    ATTENTION: DURANT LE FONCTIONNEMENT DE LAPPAREIL, LES PARTIES DU BRULEUR PROCHES DU GENERA-TEUR (BRIDE DACCOUPLEMENT) CHAUFFENT. NE PAS LES TOUCHER AFIN DEVITER TOUT RISQUE DE BRULURE.

    FONCTIONNEMENT! Mettre le brleur sous tension au moyen de linterrupteur gnral de la chaudire.! Contrler que lappareil ne soit pas bloqu; au besoin, le dbloquer en agissant sur le bouton de dverrouillage accessible

    travers le trou pratiqu sur le capot du brleur.! Vrifier que la srie de thermostats (ou pressostats) donne lordre de mise en service du brleur.! Le cycle de mise en route du brleur dmarre: lappareil met en fonction le ventilateur du brleur et met en circuit le transfor-

    mateur dallumage.! Au terme de la prventilation, llectrovanne du fioul est alimente et le brleur sallume.! Le transformateur dallumage reste branch quelques secondes aprs lallumage de la flamme (temps de post-allumage),

    aprs quoi il est exclu du circuit.

    PARTIE II: MANUEL DUTILISATION

  • PARTIE III: ENTRETIEN14

    Au moins une fois par an, effectuer les oprations dentretien illustres ci-aprs. En cas de fonctionnement saisonnier, il estrecommand de procder lentretien la fin de chaque priode de chauffage. En cas de fonctionnement continu, lentretiendoit tre effectu tous les six mois.

    OPERATIONS PERIODIQUES! Nettoyer et examinier la cartouche du filtre fioul; si ncessaire, la remplacer;! contrle de ltat des flexibles du fioul, vrifier sil y a des fuites ventuelles.;! Nettoyage et contrle du filtre lintrieur de la pompe du fioul (voir les instructions reportes dans l'appendice);! Dmonter, contrler et nettoyer la tte de combustion; lors du remontage, respecter scrupuleusement les mesures indiques

    en Tab. 9;! Contrler les lectrodes dallumage et les isolateurs en porcelaine: nettoyer, rgler et si ncessaire, remplacer (voir Fig. 21a

    et Fig. 21b).! Dmonter et nettoyer le gicleur fioul (Important: le nettoyage doit tre effectu avec des solvants; ne jamais utiliser doutils

    mtalliques). Une fois lentretien termin, remonter le brleur, allumer, et contrler la forme de la flamme; au moindre doute,remplacer le gicleur. En cas demploi intensif du brleur, il est conseill de remplacer le gicleur au dbut de chaque priodede fonctionnement;

    ! Contrler et nettoyer soigneusement la cellule photorsistante de dtection flamme; au besoin, la remplacer. Dans le doute,vrifier le circuit de dtection aprs avoir remis en fonction le brleur en suivant les indications du schma de la Fig. 22.

    N.B. Toutes les interventions sur le brleur doivent tre effectues avec linterrupteur lectrique gnral ouvert.

    Position correcte des lectrodes et de la tte de combustion ! Pour avoir accs la tte de combustion et aux

    lectrodes, desserrer la vis VB situe sur la busedu brleur et dgager ce dernier de la buse (quireste fixe la chaudire);

    ! prvoir un plan dappui stable sur lequel poser lebrleur durant lentretien.

    ! Il est ncessaire de respecter les mesures indi-ques sur la Tab. 9, afin dobtenir un bon allu-mage.

    ! Ne pas oublier de fixer la vis de mise en scuritdu groupe lectrodes avant de remonter le br-leur.

    Fig. 21a - Brleurs G4 et G6 Fig. 21b - Brleurs G10 et G18

    Contrle du courant de dtectionPour mesurer le signal de dtection, suivre les indications duschma de la Fig. 22. Si le signal ne rentre pas dans lesvaleurs indiques, vrifier les contacts lectriques, la propretde la tte de combustion, la position de la cellule photorsi-stante et au besoin remplacer cette dernire.

    Intensit minimum de courant avec flamme: 65 AIntensit maximum de courant sans flamme: 5 AIntensit max. de courant possible avec flamme: 200 A

    Fig. 22

    PARTIE III: ENTRETIEN

    Tab. 9 GICLEUR A B C D

    G4 - G4....P 60 4 3 2 3 645 6 3 2 3 6

    G6 60 5 3 4 645 8 4 4 6

    G10 - G18 60 6 4 4 645 10 5 4 6

    11 12

    Echelle A DC

    APPAREIL

  • PARTIE III: ENTRETIEN 15

    SCHEMAS ELECTRIQUESSchema electrique cod. 01-361 Rev. 1 - Brleurs G4 - G6 - G10 - G18 Versions standard

    LgendeCO CompteurEVG Electrovanne fioulF FusibleFR PhotorsistanceIL Interrupteur de ligneL1 PhaseLF Voyant de signalisation service brleurLB Voyant signalisation de mise en scuritLOA24/LMO24 Coffret LANDIS contrle flammeMA Bornier dalimentation brleurMV Moteur ventilateurN NeutreST Srie de thermostats ou de pressostatsTA Transformateur dallumageTS Thermostat/Pressostat de scurit chaudire

    ATTENTION:1 Alimentation lectrique 230V 50 Hz, 2N a.c.2 Ne pas inverser la phase avec le neutre3 Assurer au brleur une bonne mise terre

  • PARTIE III: ENTRETIEN16

    Schema electrique cod. 01-142/2 - Brleurs G4 - G6 - G10 - G18Version avec reglage air interieur et sans connecteur

    LgendeEVG Electrovanne fioulF FusibleFR PhotorsistanceIL Interrupteur de ligneLB Voyant signalisation de mise en scuritLOA24/LMO24 Coffret LANDIS contrle flammeMA Bornier dalimentation brleurMV Moteur ventilateurN NeutrePH PhaseST Srie de thermostats ou de pressostatsTA Transformateur dallumage

    ATTENTION:1 Alimentation lectrique 230V 50 Hz, 2N a.c.2 Ne pas inverser la phase avec le neutre3 Assurer au brleur une bonne mise terre

  • PARTIE III: ENTRETIEN 17

    Schema electrique cod. 01-362 Rev. 1 - Brleurs avec rechaffeur

    LgendeCO CompteurEVG Electrovanne fioulF FusibleFR PhotorsistanceIL Interrupteur de ligneL1 PhaseLB Voyant de signalisation de mise en scuritLF Voyant de signalisation service brleurLOA24/LMO24 Coffret LANDIS contrle flammeMA Bornier dalimentation brleurMV Moteur ventilateurN NeutreP Rechaffeur fioulR Rsistance rchauffeurST Srie thermostats ou pressostatsTA Transformateur dallumageTP Thermostat rchauffeurTS Thermostat - pressostat chaudire

    ATTENTION:1 Alimentation lectrique 230V 50 Hz, 2N a.c.2 Ne pas inverser la phase avec le neutre3 Assurer au brleur une bonne mise terre

  • PARTIE III: ENTRETIEN18

    PIECES DETACHEESType G4

  • PARTIE III: ENTRETIEN 19

    POS. DESCRIPTION G4 G4....P1 APPAREIL LOA24 2020445 20204452 SOCLE APPAREIL LOA24 2030409 20304094 EQUERRE DE SUPPORT APPAREIL 2430062 24300625 TRANSFORMATEUR COFI E820 2170117 21701176 PORTE-GICLEUR STANDARD 2850037 28500376 PORTE-GICLEUR LONGUE 2850059 2850059

    RALLONGE RECHAUFFEUR (G4 - G4..P) 2850109 28501096A RECHAUFFEUR (G4 - G4..P) 2850040 28500407 GICLEUR 261 2618 CABLE D'ALLUMAGE 6050119 6050119

    8A CABLE D'ALLUMAGE LONGUE 6050122 60501229 ELECTRODE D'ALLUMAGE 2080232 208023210 BUSE NORMALE 30900E3 30900E3

    10A BUSE LONGUE 30900E4 30900E411 BRIDE 2100025 210002512 GARNITURE 2110027 211002713 TTE DE COMBUSTION 3060180 306018014 FOND 3190101 201011516 CARCASSE DROITE 2050267 1010022

    16A CARCASSE GAUCHE 2050268 205026317 TURBINE 2150020 215002019 RALLONGE PORTE-GICLEUR 2850113 285011320 SOCLE PHOTORESISTANCE LANDIS --- ---21 PHOTORESISTANCE LANDIS QRB1B 2510008 251000822 CAPOTE 3010043 301003223 TUBE POUR VM1 RL2 2220141 222014123 TUBE POUR AS47A 2220141 222014123 TUBE POUR BFP21R3 2220141 222014124 VIS DE REGLAGE TETE 2320023 232002325 VIS INDICE 2350095 235009526 BRIDE PULVERISATEUR 2100065 210003727 BOBINE POUR DELTA VM1 RL2 2580406 258040627 BOBINE POUR SUNTEC AS47A 2580402 258040227 BOBINE POUR DANFOSS BFP21 R3R 2580701 258070128 POMPE DELTA VM1RL2 2590012 259001228 POMPE SUNTEC AS47A 2590130 259013028 POMPE DANFOSS BFP21 R3 2590309 259030929 MOTEUR SIMEL 75W 2180052 218005229 MOTEUR AEG 75W 2180701 218070130 CONDENSATEUR 6030013 6030013

    TUYAUX FLEXIBLES 2340055 2340055FILTRE 2090001 2090001

  • PARTIE III: ENTRETIEN20

    Type G6 - G10 - G18

  • PARTIE III: ENTRETIEN 21

    POS. DESCRIPTION G6 G10 G181 CAPOTE 3010018 3010019 30100192 CONDENSATEUR 6030003 6030005 60300053 MOTEUR SIMEL 2180013 2180005 21800143 MOTEUR AEG 2180702 2180703 ---4 APPAREIL LOA24 2020445 2020445 20204455 ENBASE APPAREIL 2030409 2030409 20304096 EQUERRE DE SUPPORT APPAREIL 2430004 2430004 2430004

    6A EQUERRE 2060002 2060002 20600027 TRASFORMATEUR COFI 1020 2170106 2170106 21701068 CARCASSE COMPLETE 2050239 2050239 20502398 CARCASSE COMPLETE (VERSION AVEC VERIN) 2050237 2050236 20502369 TURBINE 2150003 2150004 215000410 GROUPE PORTE-GICLEUR 3020047 --- ---10 GROUPE PORTE-GICLEUR (VERSION BL) 3020069 --- ---11 GLICLEUR 26100.. 26100.. 26100..12 PORTE-GICLEUR 2280032 2280006 228000613 FOND 2010112 2010102 201010214 KIT RECHAUFFEUR DANFOSS --- --- ---15 CABLE D'ALLUMAGE 6050119 6050122 605012216 ELECTRODE D'ALLUMAGE 2080232 --- ---17 TTE DE COMBUSTION 3060139 --- ---18 BUSE NORMALE 30900A2 --- ---

    18A BUSE LONGUE 30900A1 --- ---19 GARNITURE 2110027 --- ---20 BRIDE 2100025 --- ---21 PHOTORESISTANCE LANDIS QRB1B 2510008 2510008 251000822 BASE PHOTORESISTANCE 2030222 --- ---23 TIROIR MOBILE 2320012 2320012 232001224 TUBE POUR AS47C 2220113 2220125 222012524 TUBE POUR VM1RL2 2220145 2220146 222014624 TUBE POUR BFP21L3 2220113 2220125 222012525 VIS DE REGLAGE TETE 2320011 2320011 232001126 BOBINE POUR SUNTEC AS47C 2580402 2580402 258040226 BOBINE POUR DELTA VM1RL2 2580406 2580406 258040626 BOBINE POUR DANFOSS BFP21L3 2580701 2580701 258070127 CONNECTEUR POUR SUNTEC AS47C 6200008 6200008 620000827 CONNECTEUR POUR DANFOSS BFP21L3 6200009 6200009 620000928 POMPE DELTA VM1RL2 2590014 2590014 259001428 POMPE SUNTEC AS47C 2590011 2590011 259001128 POMPE DANFOSS BFP21L3 2590308 2590308 259030828 POMPE DELTA VM1RL2-2P (VERSION AVEC VERIN) 2590019 2590019 2590019

    BRIDE POUR POMPE DELTA 2690015 2690015 2690015BRIDE POUR POMPE DANFOSS 2590503 2590503 2590503

    29 FLEXIBLES 2340001 2340001 234000130 FILTRE 2090001 2090001 209000131 TUBE (VERIN - POMPE) 2220115 2220116 222011632 CAPLET D'AIR 1010704 1010002 101000234 BASE PHOTORESISTANCE (VERSION SANS VERIN) 2030219 2030219 203021934 BASE PHOTORESISTANCE (VERSION AVEC VERIN) 2030227 2030220 203022035 ACCOUPLEMENT LP 2540002 2540002 254000236 ACCOUPLEMENT 2540007 2540007 254000737 ACCOUPLEMENT LV 2540003 2540003 254000338 VERIN HYDRAULIQUE 2330010 2330015 233001539 ELECTRODE D'ALLUMAGE --- 2080203 208020340 BRIDE --- 2100007 210001141 GARNITURE --- 2110031 211003142 BUSE --- 3090005 309000642 BUSE LONGUE --- 3090008 309000943 TTE DE COMBUSTION --- 3060102 306010344 GROUPE PORTE-GLICEUR --- 3020016 302001644 GROUPE PORTE-GLICEUR LONGUE --- 3020020 3020020

  • APPENDICE: CARACTERISTIQUES DES COMPOSANTS22

    COFFRET DE SECURITE POUR BRULEURS FIOUL LANDIS LOA24 23

    POMPE DELTA TYPE VM 25

    POMPE SUNTEC TYPE AS 47-57-67 26

    INSTRUCTIONS POUR L'EMPLOI ET LA MANUTENTION DES POMPES POUR LE COMBUSTIBLE 27

    APPENDICE: CARACTERISTIQUES DES COMPOSANTS

  • APPENDICE: CARACTERISTIQUES DES COMPOSANTS 23

    COFFRET DE SECURITE POUR BRULEURS FIOUL LANDIS LOA24EmploiLes coffrets de scurit de la srie LOA... sont destins - associsaux cellules photorsistantes QRB...- la mise en service et la sur-veillance du gicleur automatique des brleurs fioul air souffl depuissance rduite, dun dbit de 30 kg/h maxi conformment aux nor-mes DIN 4787.La mise en service peut tre effectue -selon le raccordement lectri-que- avec ou sans post-allumage et pour un fonctionnement 1 ou 2allures. Pour les brleurs de gnrateurs air chaud (WLE selon DIN 4794),utiliser LOA 44.Excution des coffretsLes coffrets sont embrochables et peuvent tre monts en toute posi-tion: sur le brleur, sur le tableau lectrique ou le tableau de com-mande. Leur botier en matire plastique rsistant aux chocs et lachaleur contient:- le programmateur thermique qui agit sur un systme de commande commutation multiple, avec compensation de la tempratureambiante- lamplificateur du signal de flamme avec le relais de flamme - levoyant de signalisation de mise en scurit et le bouton de dverrouil-lage (tanche).Le socle embrochable, galement en matire plastique rsistant auxchocs et la chaleur, comprend plus de 12 bornes de connexion:! 3 bornes de neutre, prcbles la borne 2! 4 bornes de mise la terre pour la mise la terre du brleur! 2 bornes - relais numrotes 31 et 32.Le socle est dot sur le fond de deux ouvertures dfonables pour lepassage des cbles; 5 autres ouvertures dfonables avec raccordfilet pour passe-cble PG11 ou 3/4 UNP pour douilles non mtalli-ques sont situes sur le support de pressetoupe amovible (une dechaque ct et 3 sur la partie frontale).De chaque ct du socle se trouvent deux languettes lastiques pourfixer le coffret. Pour le dmontage, il suffit dexercer une lgre pres-sion laide dun tournevis dans la fente de guidage.Les dimensions de la base du socle correspondent exactement auxdimensions du socle LAB/LAI. Restent inchanges: la position et lediamtre du bouton de dverrouillage, des deux vis de fixation et dela languette de mise la terre du brleur.Scurit aux basses tensionsLes coffrets possdent un circuit lectronique particulier: lors de ten-sions

  • APPENDICE: CARACTERISTIQUES DES COMPOSANTS24

    Caractristiques techniquesTension 220V - 15%... 240V + 10% ou bien

    100V - 15%... 110V +10%Frquence 50...60 Hz, 6%Fusible externe 10A maxi, action lenteCharge des contacts- borne 1 5A- borne 3 5A (y compris consommation du

    moteur et du rchauffeur de fioul)Charge des bornes- bornes 4,5 et 10 1A- bornes 6 et 7 2A- bornes 8 5AConsommation 3VA environProtection IP40Temprature admissible- fonctionnement -20...+60C- transport et stockage -50...+60CPosition de montage toute positionPoidscoffret 180gsocle 80gaccessoires AGK... 12g

    Commandes en cas de dysfonctionnement Lumire parasite/allumage anticipDurant le temps de prventilation et/ou de prallumage, il ne doit yavoir aucun signal de flamme. Le signal de flamme pourrait appa-ratre en raison dun allumage anticip d une fuite de llectro-vanne, dun clairage externe, dun court-circuit dans la cellulephotorsistante ou dans le cble de connexion, dun dfaut delamplificateur du signal de flamme, etc.. En ce cas, une fois lestemps de ventilation et de scurit couls, le coffret commande lamise en scurit du brleur et empche la libration du combustible.Absence de flammeEn cas dabsence de flamme la fin du temps de scurit, lappareilcommande immdiatement la mise en scurit.Absence de flamme pendant le fonctionnementEn cas dabsence de flamme durant le fonctionnement, le coffretcoupe lalimentation en combustible et dclenche automatiquementun nouveau programme de mise en route: le temps t4 coul, leprogramme de mise en route est termin.A chaque mise en scurit, les bornes 3-8 et 11 sont mises hors ten-sion en moins dune seconde; la borne 10 signale distance la miseen scurit. Le dverrouillage du coffret est possible envrion 50 saprs la mise en scurit.

  • APPENDICE: CARACTERISTIQUES DES COMPOSANTS 25

    POMPE DELTA TYPE VMDans la pompe Delta de la srie VM, le flux de fuel pressuris est intercept par une vanne lectromagntique incorpore. Ilpeut donc tre libr aprs la mise en route du moteur (prventilation) ou interrompu avant larrt du moteur (la flamme steintinstantanment mais le gicleur ne goutte pas). La pression du fuel est rgle et maintenue constante par la vanne piston quiagit sur louverture dun orifice de dcharge, lexcdant de fuel contenu dans le gicleur tant renvoy au rservoir (installation deux tubes) ou rintroduit en aspiration travers un trou ou by-pass (installation monotube).Les deux versions - un ou deux tubes- de ce modle sont autoamorables. Il est toujours recommand dinstaller un filtreexterne de ligne.Tous les modles fournis dans la version deux tubes peuvent tre employs dans les installations monotube: il suffit de retirerla vis sans tte en nylon et de fermer le canal de retour.

    DONNES TECHNIQUESViscosit de l'huile 2 50 cSt (1,1 6,5E)Temprature de l'huile 60C (140F) max.Puissance absorbe Voir graphiquesDbit gicleur Voir graphiquesVide en aspiration 0,5 bar (15 inHg) max.Pression en aspiration 0,7 bar (10 psi) max.Pression de retour 1,5 bar (21 psi) max.Pression de blocage 4 barVitesse de rotation 3500 t/min max.Filtre Toile en nylon 150 m, 20 cm

    Sur option: acier inox 110m, 65 cmDimensions Moyeu f 32 mm, arbre f 8 mm

    Sur option: flange moyeu f 54 mmSur option: 7/16" arbre

    Raccords Aspiration - Retour: G1/4"Refoulement gicleur : G1/8"Pression - Vide: G1/8"

    Poids 1100 gr

    INSTALLATION BITUBE INSTALLATION MONOTUBELgende1 Regulateur pression2 Engrenages3 Etancheite arbre4 Bouchon de drivation mont5 Retour6 Aspiration7 Prise vacuomtre8 Prise manomtre9 Gicleur

    Lgende1 Regulateur pression2 Engrenages3 Etancheite arbre4 Bouchon de drivation retir5 Retour6 Aspiration7 Prise vacuomtre8 Prise manomtre9 Gicleur

  • APPENDICE: CARACTERISTIQUES DES COMPOSANTS26

    POMPE SUNTEC TYPE AS 47-57-67L'engrenage aspire le fioul du rservoir travers le filtre de la pompe et le transfre au piston qui assure la rgulation de la pression pour laligne gicleur. Le fioul non utilis par le gicleur est renvoy, dans une installation bitube, vers le retour, par le rgulateur de pression. Dans le casd'une installation monotube, ce fioul en excs est renvoy directement l'engrenage au niveau de l'aspiration. Dans ce cas, le bouchon de dri-vation situ dans l'orifice de retour devra tre retir et l'orifice de retour obtur par un bouchon mtallique et une rondelle d'tanchit.L'lectrovanne de la pompe AS est du type "normalement ouverte". Lorsque l'lectrovanne est hors tension, le canal de drivation entre le ctpression du piston et le retour est ouvert, il n'est pas possible de crer une pression capable de faire fonctionner le piston du rgulateur. Lavitesse de rotation de l'engrenage n'a alors aucune influence. Lorsque l'lectrovanne est sous tension, le canal de drivation est ferm : leretour ne communique plus avec le ct pression ; la pleine vitesse de rotation de l'engrenage tant atteinte, la pression monte trs rapidementassurant une ouverture immdiate du piston.CoupureA l'arrt du brleur, l'lectrovanne s'ouvre, rtablissant la circulation entre le ct pression et le retour. Ce systme tablit une coupure nette etimmdiate. L'ouverture et la coupure peuvent tre commandes indpendamment de la vitesse du moteur.Lorsque l'lectrovanne n'est pas excite, le couple d'entranement demand au moteur reste faible, mme pleine vitesse.PurgePour une installation bitube, la purge est automatique; elle pourra tre acclre en ouvrant une prise de pression. Pour une installation mono-tube, il sera ncessaire d'ouvrir une prise de pression pour purger le systme.

    GnralitsMontage Par bride ou pincement du moyeu selon

    la norme EN 225.Raccordements cylindriques selon ISO 228/1Aspiration et retour G 1/4 (avec tanchit directe sur cne,

    sans raccord, pour les modles rvision 5)

    Fonction de la vanne Rgulation de la pression et coupure* piston * lafonction de coupure n'est assure que pour la gamme de pression spci-fique du modle.Filtre surface ouverte: 4 cm2 - taille de la maille: 150 mArbre 8 mm selon la norme EN 225.Bouchon de drivation mont dans l'orifice de retour pour raccordementbitube; retirer avec une cl Allen de 4 mm pour raccordement mono-tube.Poids 1,1- 1,5 kg (selon le modle)Caractristiques hydrauliquesEngrenage Gamme de pression* / Pression de

    livraison47/57 7- 14 bar / 9 bar67 10 - 15 bar / 10 bar* autres gammes disponibles sur demande, se rfrer la plage depression du modle concern.Viscosit 2 - 12 mm/s (cSt)Temprature du fioul 0 - 60C dans la pompe.Pression d'arrive 2 bar max.Pression de retour 2 bar max.Hauteur d'aspiration 0,45 bar max. de vide pour viter le

    dgazage du fioul.Vitesse de rotation 3600 t/min maxi. (AS 47, AS 57) - 2850

    t/min maxi. (AS 67)*Couple ( 45 t/mini.) 0,10 Nm (AS 47/57) - 0,12 Nm (AS 67)

    Caractristiques de l'lectrovanneTension 220-240 ou 110-120 ou 24 V; 50/60

    HzConsommation 9 VA (pour une tension de 220 ou

    110 ou 24 V)Temprature ambiante 0 - 60CPression maximum 15 barApprobation N Certification TV indiqu sur la

    pompeProtection IP 41 - selon IEC 529 - pour utilisa-

    tion avec un connecteur SUNTEC.LgendeA Electrovanne ferme (NO)B Electrovanne ouverteC Retour ferme1 Electrovanne2 Vanne de rgulation de pression3 Rglage de la pression4 Vers le gicleur5 Prise manomtre6 Purgeur7 Joint d'tanchit de l'abre8 Prise vacuomtre9 Bouchon de drivation "P"10 Train d'engrenages11 Arrive12 Retour13 Retour l'aspiration14 Arrive15 Vers joint de l'abre et vers retour

    INSTALLATION BITUBE INSTALLATION MONOTUBE

    X Fioul en aspirationY Fioul sous pressionZ Retour du fioul non utilis au rservoir ou

    l'aspiration

  • APPENDICE: CARACTERISTIQUES DES COMPOSANTS 27

    INSTRUCTIONS POUR L'EMPLOI ET LA MANUTENTION DES POMPES POUR LE COMBUSTIBLE

    ! Si l'installation est monotube prire de vrifier qu' l'intrieur du trou de retour n'y soit pas prsente la douille by-pass. Dans ce cas-l lapompe ne marcherait pas correctement et elle pourrait s'abmer.

    ! Ne pas ajouter des substances au combustible afin d'viter la formation de composs qui avec le temps, pourraient se dposer entre lesdents de l'engrenage et ainsi crer un blocage.

    ! Une fois la citerne remplie, attendre avant de dmarrer le brleur. Cela donne le temps aux ventuelles salets en suspension de se poserau fond et de ne pas tre ainsi inspires par la pompe.

    ! Quand la pompe est mise en marche pour la premire fois et il se prvoit un fonctionnement sec pour un temps considrable (par exemple cause d'une longue conduite d'aspiration), injecter de l'huile lubrifiant par la prise vide.

    ! Pendant la fixation de l'arbre moteur de la pompe faire attention ne pas l'obliger en sens axial ou latral afin d'viter des usures excessivesdu joint, bruit et surcharges d'effort sur l'engrenage.

    ! Les tubes ne doivent pas contenir de l'air. Pour cette raison viter les raccords rapides utilisant prfrablement des raccords filets ou avectanchit mcanique. Sceller avec un produit convenablement dmontable les filetages des raccords, les couds et les jonctions. Limiter aunombre minimal les connexions parce qu'elles sont toutes des sources potentielles de perte.

    ! Eviter l'utilisation de Teflon dans les connexions des flexibles d'aspiration, de retour et dpart afin d'viter une possible mise en circulationdes parts qui se dposeraient sur les filtres de la pompe et du gicleur en limitant l'efficacit. Donner priorit aux raccordements avec OR ouavec tenue mcanique ( ogive ou avec rondelles en cuivre ou aluminium).

    ! Afin d'assurer le fonctionnement sans soucis de la pompe il est conseill de nettoyer le filtre au moins une fois par an. L'enlvement du filtrese fait en enlevant le couvercle, en dvissant les quatre vis avec une cl six pans

    ! Pendant le montage faire attention que les pieds de soutien du filtre regardent vers le corps de la pompe. Si possible remplacer le joint ducouvercle. Toujours prvoir un filtre extrieur dans la tuyauterie d'aspiration avant la pompe.

    Attention:Dconnecter l'alimentation avant d'excuter n'importe quelle opration sur l'installation. Avant le dmarrage du

    systme s'assurer que la chambre de combustion soit vide de combustible dispers ou de ses vapeurs.