Upload
lvndrsngh
View
230
Download
0
Embed Size (px)
Citation preview
8/10/2019 harmonics techniques
1/5
A Novel Technique For Optimising Harmonics And Reactive Power With Load
Balancing Under Non-Sinusoidal Supply And Unbalanced Load Conditions
Sincy
George,
Member, IEEE
Department
of
Electrical Engineering,
Indian Institute of Technology -Bombay,
Powai, Mumbai
- 400
076, India
sincy@ee. itb.ac.
in
Abstract:
Generally, conventional power factor corrections
techniques assume ideal conditions,
viz.
sinusoidal supply
voltage and balanced load. But vast majority of the domestic
and industrial loads present in the power distribution system are
non-linear and unbalanced. Under such conditions, attempt to
make the power factor unity result into a non-sinusoidal source
current, which increases total harmonic distortion (THD) in the
system.
On
the other hand attempt to make harmonic free
current may not result in unity power factor because of the
harmonics present in the supply voltage. Thus, there is
a
trade
off between improvement in power factor and reduction in
THD. With the introduction of power quality norms by various
utilities, it has become unavoidable to optimize power factor
while satisfying harmonics limits. I n this paper, a novel
technique for optimisation of THD and power factor subject to
power quality constraints is presented. The algorithm uses
Lagrange multiplier technique to optimise the non-linear
equations. The algorithm calculates the control coefficients by
Newton Raphson method and is used to compute the desired
source current that balances the system besides optimising
power factor satisfying the load power while meeting the THD
limits. Knowing the load current, the compensating current to
be supplied by the shunt active power filter to the power system
is calculated. This technique, besides satisfying the power
quality norms, also balances the imbalance in the system. It is
applicable for single-phase and multi-phase system under
sinusoidal and non-sinusoidal supply conditions. The proposed
scheme does not use the widely used p-q theory and use simple
computational techniques. Simulation using MATLAB has
shown encouraging results. The scheme is being implemented in
hardware using DSP.
Key words: Power Quality and Harmonics, Power factor
compensation, Active Power Filters, DSP Control.
LINTRODUCTION
In electrical power distribution system, most of the loads
are inductive in nature. Residential loads and vast majority of
other single-phase loads cause imbalance in the system. The
increased uses of power electronic devices also impair power
quality in the grid. These non-linear loads draw non-
sinusoidal currents from the system consequently voltage
drops are produced across impedances of transmission line,
transformer and generator causing non-sinusoidal voltages in
the system. This distorted voltage affects other linear or non-
linear loads connected to the system. Effect of these
Vivek Agarwal,
Member, IEEE
Department of Electrical Engineering,
Indian Institute of Technology -Bombay,
Powai, Mumbai
- 400
076, India
agarwal@ee. itb.ac in
0-7803-7754-0/03/ 17.0002003 IEEE
1537
harmonics and voltage imbalance on electrical and electronic
equipment is explained in various papers [ l] .
Harmonic contents vary randomly and consequently the
conventional compensating techniques such as the use of
passive LC filters to perform harmonic reduction are
ineffective [2]. Due to this many types of active filters have
been developed to compensate current and or voltage
harmonics viz. shunt active filter, series active filter or
combination of both [2-51. Controlling the injection of
current harmonic by the non-linear load can eliminate non-
sinusoidal operation of the system. This can be achieved by
the installation of shunt active filters. In this technique, a
current source inverter is connected in parallel with the load.
This injects compensating current into the system to cancel
the undesired components of load current that are responsible
for harmonics and low power factor.
The quality and performance of these filters mainly depend
on the method used to generate the reference current for
compensation [6]. Most of these methods use p-q or d-q
transformation theory and assume a sinusoidal supply
voltage. Control methods adopted by others [7,8] assume a
non-sinusoidal supply, but use only positive sequence voltage
at the fundamental frequency to generate sinusoidal
references to ensure that the supply current is harmonic free
and power factor is unity. However, when the supply voltage
is non-sinusoidal, perfect harmonic compensation (PFC) does
not result into unity power factor (UPF) and vice versa. In
such conditions, non-linear optimisation technique [9 IO] is
found to be an efficient method to optimise the power factor
and total harmonic distortion THD) satisfying the power
quality norms or guidelines. The method adopted in [9] also
uses p-q theory and is not applicable to single-phase
conditions. Also most of the proposed active filters are based
on analogue implementation.
In this paper, an improved control algorithm for the
reference current to the inverter under non-sinusoidal supply
voltage and unbalanced load condition is presented. This
algorithm is based on a non-linear optimisation technique and
does not use p-q or d-q transformation. This technique
considers harmonics in supply voltage for power factor
computation. It is more versatile and flexible and is
applicable to both single phase and multi-phase system with
linear, non-linear, balanced or unbalanced load conditions.
8/10/2019 harmonics techniques
2/5
The control signal is computed using TMS320LF2407A
DSP controller.
This paper is organized into the following sections. Section
I1 details basic concept of the proposed scheme. Section I11
presents the algorithm for the scheme under non-sinusoidal
supply conditions. The result of the computer simulations
using MATLAB is included in section IV. Section V details
conclusion.
I1
BASIC CONCEPTS
OF
THE PROPOSED STRATEGY
The block diagam of the proposed scheme is shown in
Fig.1. The power circuit of the scheme consists of a three-
phase non-sinusoidal supply voltage connected to an
unbalanced non-linear load.
Let the resulting three-phase supply voltage,
v,
contain a set
of harmonic components, n and n . For phase a,
and the corresponding unbalanced load current
i
contain a
set of harmonic current nl n3
where
aan
s the arbitrary angle of supply voltage and vans
the phase angle of nthharmonic component of current.
For unity power factor, currents drawn should be in phase
with, and
of
the same shape, as the source voltage. i.e.
y ~ , ,
0
and the harmonics in current and voltage are
of
the same
order and their ratios equal. However in this case, THD may
not be within the acceptable limit of the utility or power
quality norms. By controlling these harmonic ratios, THD can
be controlled but the power factor may deteriorate. In
general, the desired source current
ius
with displacement
angle set to zero, and making the order of harmonics in
source current same as that of supply voltage may be written
as:
*
(3)
l J
where,
I = K,,,.Va,.
Similarly for phase
b
and c
K ,
K b n K C n
he admittance of the compensating load,
are the control variable in phase a, b, and c respectively.
Therefore, the reference compensating current is calculated as
* .
:c
* *
* .
. *
iac
= ial - 1 , ; bc
= ib, -ibs lee
=IC
-1 ,
(4)
In the proposed scheme, a current source inverter is
connected in parallel with the load. The proposed algorithm
calculates the reference compensating current and generate
control pulses for the inverter using DSP. This compensating
current when injected into the system cancels the undesired
component of load current that are responsible for the low
power factor and high THD.
Fig. Block diagram
of
the proposed scheme
111
CONTROL STRATEGY UNDER N ON-SINUSOIDAL AND
UNBALAN CED CONDITIONS
Non- sinusoidal and unbalanced conditions are common in
a modern power system. In such conditions unity power
factor and power balance can be achieved by making the
source current identical in magnitude, in phase and of same
shape as that of voltage, in all phases. When the source
current is made to have the same shape as voltage, current
THD may not be with in the acceptable limit. To obtain
perfect harmonic compensation, current drawn
from
the
source need to be a perfect sine wave. In this case, unity
power factor is not obtained. By using the proposed optimal
strategy it is possible to optimise the power factor satisfying
power demand and harmonic limit. The relevant theory is
discussed below.
A . POWER UNDER NON-SINUSOIDAL
SUPPLY
AND
UNBALANCED
LOAD
CONDITIONS
When the supply voltage and unbalanced load current
contains harmonics, the complex apparent power is given by
the vector sum of active, reactive and distortion power. The
instantaneous power can be given as:
p t ) =
vu t).ja t ) Vb t).ib t ) vc t ) . i c
t )
p t ) = v t).i+ t )
+
v-
t).i-
t )
+
vo t).iO t )
5 )
These powers can be calculated by sequence component of
voltage and current as:
where
+,
0
0
represents positive, negative and zero
sequence components respectively.
Positive sequence component of power contains mean value
p +
and an alternating component
(p , )
with zero mean
value. Similarly negative sequence and zero sequence
6 )
-
-
1538
8/10/2019 harmonics techniques
3/5
- -
components contain a mean value
p -
p o and an
alternating component(p - Po
- -
I
PO)
=
P+ +P++
P-+
P-+Po +Po
(7)
- - -
The average power is given by pdc = p + + p - + p o .
Load balancing can be achieved by sharing the average
power demand equally among each of the phases as shown in
Fig.2. The active filter supplies the balance power required
by the load.
Fig.
2
Power balance diagram
B. OPTIMSATION TECHNIQUE
Lagrangian-multiplier technique [11,121 is used to
optimise the non-linear equation for reactive volt-ampere
subject to equality and inequality constraints [101.
I. Objectivefunction
Let the order of harmonics in supply voltage and desired
source current be n. The objective is to minimise apparent
input Volt-Ampere, S in each phase and can be written as:
Optimisation is applied to minimise Sas with control
variable
Kan,
o that power factor is maximum in each phase.
II. Equality constraints
The desired source current in each phase is calculated in
such a way that, it should supply only mean value of
corresponding instantaneous real power demanded by the
load after compensation. The compensating circuit supplies
remaining power demanded by the load. Therefore the
equality constraints for phase
a
can be written as:
III. Inequality constraints
Let the total current harmonic distortion be limited to
THDiH
The inequality constraint is given by
The inequality constraint
U
can be written as:
IV. Lagrange
unction
The objective is to minimise
S,
subject to the equality
constraint and the inequality constraint given by
9)
and
1 1)
respectively. The augmented hnction L is given by:
(12)
where2 and p are constants. Using the necessary and
sufficient condition for constraint local minima of L he
unknowns can be found out. By using these unknowns the
reference source current for optimum power factor within
acceptable THD limit [131 is determined.
rV SIMULATION RESULT UNDER NON-SINUSOIDAL AND
UNBAL ANCED CONDITIONS
To verify the proposed theory under unbalanced
conditions, simulation studies have been carried out using
MATLAB
on a balanced three-phase, SO , 415V (rms.)
trapezoidal voltage power supply system (THD 2 1.8%) with
an unbalanced rectifier load of 30kW.
I I I
- - a
- b
400
-400
I I
002
0025
0
03
0
035 0 04
Fio 3 fa\
l i m e se c )
1539
8/10/2019 harmonics techniques
4/5
Waveforms of non-sinusoidal supply voltage considered
for simulation is shown in Fig 3(a) and unbalanced load
current is shown in Fig.
3(b).
Calculated 3-phase source
current at 5% THD after the compensation is shown in Fig.
3(c) and waveform of computed compensating current is
shown in Fig. 3(d). This compensating current is the
reference current for the inverter.
I
I
I
0.04
-100
0 02
0025
o
0.035
F , ~ .(b) Time sec1
W
I I I
By using hysterisis control for the inverter, the sample
system is simulated. The optimised source current computed
and the source current obtained after compensation for
5
THD case is plotted in Fig. 4 (a). Fig 4 (b) shows the
waveforms of source voltage, load current and source current
for phase
a of
the system.
(- Reference I
0
I
0 02
50
0 005
0.01
0.015
Fig
4 a)
Time sec)
-100
I
I
0.m
0 025 0.03
0 035
0 04
Fig, 3 cl Time sec1
Fig 4. Waveform of reference and actual source current,
supply vo ltag e, load current and source current after compensation.
40
I
I
0.02 10 025 0 03 0.035 0 04
Fig 3 Wave forms o f supply v oltage, load current, reference source
current and compensating current
Fig
3(d)
fime sec)
It may be noted from above figure that the source current
after compensation follows the computed current very
closely. Current harmonics in phase a, before and after
compensation is shown in Fig. 5(a) and Fig. 5(b) respectively.
1540
8/10/2019 harmonics techniques
5/5
V CONCLUSIONS
Phase Load Voltage Current Average
current THD (in THD (in power
60
50
40
Q
E
a
3 30
.-
20
10
0
Power
factor
1 e f t * . * . . . . . . .
2
4
6
8 10 12 14 16 18
Order of harmonics
a
b
c
Fig. 5(a) Harmonic spectrum of source current
in phase a before compensation
(A) p.u) p.u) (kW)
60.201 0.2027 0.202 14.774 1.007
37.338 0.2113 0.210
9.122 0.997
26.998 0.2120 0.211 6.599 0.997
0
2
4 6 8 10 12 14 16 18
20
Order of harmonics
Fig.
5 b)
Harmonic spectrum of source current
in
phase
a
after compensation
a
b
c
Summary of load current, voltage
THD,
current
THD,
average power and power factor is shown in Table 1.
Table 1.
Summary of measured values before and after compensation
42.099 0.2027 0.050
10.136 0.988
41.906 0.2113 0.050
10.136 0.987
41.898 0.2120
0.050
10.136 0.987
From the results of the simulation detailed in section IV, it
is evident that the proposed control strategy is well suited for
balancing the power system besides reactive and harmonic
compensation to optimise the power factor satisfying the
THD. The technique presented here is verified under
various conditions of input supply and load viz. linear, non-
linear and its combination under balanced and unbalanced
conditions. For implementation
of
the algorithm, a non-
sinusoidal
3
phase, 60 V , 50Hz supply source is made by
clipping of sine wave using diodes and batteries. Control
algorithm is developed by an inter list of assembly and C
language. The compensating current is injected into the
system using 3-phase inverter Semikron SKH160. This is
being implemented using
DSP
controller TMS320LF2407A.
REFERENCES
[I] V.E Wagner Effect of Harmonicson Equipment Report of IEEE Task
force
on
The effect of Harmonics on Equipment,
IEEE Transactions on
Power Delivery, Vo1.8, No.2, April 1993.
[2] F.Z.Peng, H.Akagi, A.Nabae A Novel Harmonic Power Filter
[3] Hirofumi Akagi New
trends
in Active Filters for Improving Power
Quality, Power
Electronic Drives and Energy System
or
Industrial Growth,
1996, Proceedin gs of 1996 Intemationa l conference Vol.1, pp. 417 -425.
[4]Hirofumi Akagi Trends in Active Power Line Conditioners IEEE
Transaction on Pow er Electronics,
Vo1.9, No. 3, May 1994,pp263-268
[5] Mauricio Aredes, Edson H. Watan abe New control algorithm for
series and shunt 3 phase 4 wire active power filters,
IEEE Tran sactions on
PowerDelivery,
VolO, No.3, July 19 95, pp. 1649-165 6.
[6] Juan W Dixon, Jaime J Garcia and Luis Moran Control System for
Three-phase Active Power Filter Which Simultaneously Compensates Power
Factor and Unbalanced Loads,
IEEE Transactions on Industrial Electronics,
Vo1.42, No.6, Decemb er 1995, pp. 636-641
[7] Cheng-Che Chen, Yuan-Yih Hsu A Novel approach to the design of a
shunt active filter for an unbalanced 3-phase 4-wire system under non-
sinusoidal condition,
IEEE Transactions
on
Power Delivery,
Vo15, No.4,
October 2000, pp. 1258-1264.
[8] Mauricio Aredes, Edson H. Watanabe New control algorithm for
series and shunt 3 phase 4 wire active power filters,
IEEE Transactions on
Power Delivery,
VolO, No.3, July 199 5, pp. 16 49-1656.
[9] S.Mohammad-Reza Rafiei, Hamid A. Toliyat, Reza Ghani and Tilak
Gopalarathnam An optimal and Flexible control strategy for active filtering
and power factor correction under non-sinusoidal line voltages
IEEE
Transactions on Power Delivevy,
Vo1.16, No.2, April 2001, pp. 297-30 5.
[IO] Sincy George, Vivek Ag ama l A Novel Technique for optimising the
Harmonics and Reactive Power under Non-sinusoidal voltage conditions,
Accepted for presentation in
IECONOZ,
o be held in November, 5-8,2002,
in Sevilla, Spain
[I I] A Ravindran, Don T. Phillips, James J. Solberg, Operations Research
Principles and Practice,
John Wiley Sons, pp. 524-542
[I21 Hadi Saadat,
Power System Analysis,
McGraw-Hill Company, pp.258-
266
[I31 IEEE Std 519-1992 IEEE Recommended Practice and Requirements for
Harmonic Control in Electrical Power Systems.
PESC88,April
1 9 8 8 , ~ ~151-I156
1541