    CORONA BELL 33/11 KV BUS SUPPORT CLAMP(FLEXIBLE)

    8

    11 KV BUS SUPPORT(RIGID/SLIDING)

    33 KV BUS SUPPORT(RIGID & SLIDING)

    PCD - For 11KV : 76mm For 33 KV : 127mm

  • 7/23/2019 Mil. Clamps

    11/20

  • 7/23/2019 Mil. Clamps

    12/20

  • 7/23/2019 Mil. Clamps

    13/20

  • 7/23/2019 Mil. Clamps

    14/20

    TWO BOLT PG CLAMP

    * While calculating the factor W air gap of 4mm to 6mm is considered

    ** Details for other sizes will be given on request.Material of construction : Alloy, GR: 4600 as per IS : 617Material of hardware : M. S. Hot dip Galvanized

    THREE BOLT PG CLAMP

    CAT. NO TYPE RUN TAP BOLT SIZE DIMENSIONS

    ( W C H L

    MPC14 TYPE-A 14 14 M8 55 55 50 55

    MPC16 TYPE-B 16 16 M10 72 64 60 64

    MPC21 TYPE-B 21 21 M10 72 64 60 64

    MPC25 TYPE-B 25 25 M10 102 74 60 74

    MPC30 TYPE-B 30 30 M10 102 74 60 74

    MPC36 TYPE-B 36 36 M10 115 90 90 90

    MPC42 TYPE-B 42 42 M 10 115 90 90 90

    ) ()

    Type-A Type-B

    BUS SUPPORT FOR CONDUCTORS

    CAT. NO. PRIMARY (P) SECONDARY (C) BOLTSIZE(J) DIMENSIONS

    B X Y

    MBSC21 127 21 M10 160 72 28

    MBSC25 127 25 M10 160 82 41

    MBSC32 127 32 M10 160 82 41

    MBSC36 127 36 M 10 160 90 41

    MBSC42 127 42 M10 160 90 41

    12

    All dimensions are in mm.

    All dimensions are in mm.

    ** Details for other sizes will be given on request.Material of construction : Alloy, GR: 4600 as per IS : 617

    Material of hardware : M. S. Hot dip Galvanized

  • 7/23/2019 Mil. Clamps

    15/20

    BRITISH STANDARD

    ALL ALUMINUM ALLOY CONDUCTORS - (AAAC) BS-3242:1970/BS EN-50183 : 2000

    Code Name

    Equivalent

    Copper

    area (mm2)

    Stranding

    and wire

    diameter

    mm

    Overall

    Diameter

    Aluminium

    area (mm2)

    Mass

    (kg/km)

    Ultimate

    tensile

    strength

    (newtons)

    Breaking

    Load (kg)

    Coefficient

    of linear

    expansion /

    C010 -6

    Initialmodulus

    of

    elasticity

    (N/mm2)

    Finalmodulus

    of

    elasticity

    (N/mm2)

    DC

    resistance

    at 200C

    (N/mm2)

    Current

    rating

    (Amps)

    ACACIA 13 7/2.08 6.24 23.790 65 6690 682 23 52500 61000 1.39 133

    ELM 112 19/3.76 18.8 210.90 580 59220 6040 23 49650 59650 0.158 513

    YEW 254 37/4.06 28.42 479.0 1319 134510 13720 23 48250 58600 0.0696 853

    ALL ALUMINIUM CONDUCTOR - (AAC) BS-215 (Part 1) :1970

    Code Name

    Equivalent

    Copper

    area (mm2)

    Stranding

    and wire

    diameter

    mm

    Overall

    Diameter

    Aluminium

    area (mm2)

    Mass

    (kg/km)

    Ultimate

    tensile

    strength

    (newtons)

    Breaking

    Load (kg)

    Coefficient

    of linear

    expansion /

    C010

    -6

    Initial

    modulus

    of

    elasticity

    (N/mm2)

    Final

    modulus

    of

    elasticity

    (N/mm2)

    DCresistance

    at 200C

    (N/mm2)

    Current

    rating

    (Amps)

    SPIDER 145.2 19/3.99 19.95 237.570 652 38300 3900 23 49650 59650 0.1211 589

    MAYBUG 290.3 37/4.09 28.63 486.11 1340 78200 7970 23 48250 58600 0.0593 918

    TARANTULA 483.9 37/5.23 36.61 794.9 2191 126000 12800 23 48250 58600 0.0363 1230

    BULL 527.87 64/4.25 38.25 865.36 2400 139000 14200 23 46200 57570 0.0224 1300

    ALUMINIUM CONDUCTOR STEEL REINFORCED - (ACSR) BS-215 (Part 2) :1970

    Aluminum Steel Total

    WEASEL 19.35 6/1/2.59 2.59 7.77 31.61 5.27 36.88 87 41 128 11450 1160 0.9077 170

    RACCOON 48.39 6/1/4.09 4.09 12.27 78.83 13.14 91.97 217 103 320 27200 2770 0.364 300

    DOG 64.52 6/4.72/1.57 4.71 14.15 104.98 12.7 117.69 288 106 394 34700 3540 0.2733 360

    WOLF 96.77 30/7/2.59 7.77 18.13 158.06 36.88 194.94 438 289 727 69200 7050 0.1828 470PANTHER 129 30/7/3.00 9.00 21 212.06 49.48 261.54 586 388 974 90800 9260 0.1363 560

    DEER 258.1 30/7/4.27 12.81 29.89 429.6 100.24 529.84 1190 792 1980 179000 18200 0.0673 870

    ZEBRA 258.1 54/7/3.18 9.54 28.62 428.88 55.6 484.48 1186 435 1621 133000 13600 0.0674 860

    MOOSE 322.6 54/7/3.53 10.59 31.77 528.49 68.51 596.99 1466 536 2002 162000 16500 0.0547 980

    Total

    area

    (mm2)

    Steel area

    (mm2)

    Aluminium

    area (mm2

    )

    Ultimate

    tensile

    strength

    (newtons)

    DC

    resistance

    at 200C

    (N/mm2)

    Current

    rating

    (Amps)Code Name

    Breaking

    Load (kg)

    Overall

    diameter

    mm (Std.)

    Diameter

    over steel

    (mm)

    Mass Kg/kmStranding

    and wire

    diameter

    mm

    Equivalent

    Copper

    area (mm2)

  • 7/23/2019 Mil. Clamps

    16/20

  • 7/23/2019 Mil. Clamps

    17/20

  • 7/23/2019 Mil. Clamps

    18/20

  • 7/23/2019 Mil. Clamps

    19/20

  • 7/23/2019 Mil. Clamps

    20/20