View
232
Download
0
Category
Preview:
Citation preview
7/27/2019 305704 Ci MT Manifold
http://slidepdf.com/reader/full/305704-ci-mt-manifold 1/5
7/27/2019 305704 Ci MT Manifold
http://slidepdf.com/reader/full/305704-ci-mt-manifold 2/5
Engineering data sheet
Text1
2
3
4
5
6
7
8
9
Vølundsvej 17DK- 3400 HillerødTel +45 7022 2769
Fax +45 7023 2769
Rev: 20.05.09
Product:
Inergen®
Document: 30570# Ci MT Manifold.doc
Chapter: Ci Page: 2 of 5
Sheet No.: 30570# Ci MT Manifold
Id: MK
Order i ng in for mat ion
When ordering a Ci MT2-10 Manifold an orifice kit must also be ordered for each manifold in order to connectthe manifold to the pipe system. These kits are available with ISO 7 or NPT thread.The Ci MT1 has the orifice integrated in the body and connects directly to the pipe system. The tread of theMT1 is ½” which can be used for both ISO and NPT sockets
Specif icat ions
Pressure:
Work: 400 bar (300 bar fill @ 15°C)Proof (burst): > 1200 bar
Temperature: -40 to +70°C
Flow way: max 380mm2/connection (ø22mm)max 50mm2/connection (ø8mm)
Tread connections:
Hose connection: ISO228 G3/8” (60° seat), malePipe connection: MT1: ISO7 R ½”, male
Orifice connection: MT2-10: M40×1.5, male,Additional outlet: M30x1.5 special O-ring seal (for Ci-MT pressure switch))
Materials: Brass, zinc plated steel, tin-nickel plated steel, Viton
Dimension:
L×D×H: see table ×ø40×51mmWeight: see table
Table 1
Itemnumber
Marking Orificemax.
Weight LengthIncl. Orifice kit
mm kg mm
305701 Ci-MT 1 ø8.0 0.1 41
305702 Ci-MT 2 ø11.3 1.4 160
305703 Ci-MT 3 ø13.80 1.6 200
305704 Ci-MT 4 ø16.0 1.8 240
305705 Ci-MT 5 ø17.9 2.0 280
305706 Ci-MT 6 ø19.6 2.2 320
305707 Ci-MT 7 ø21.1 2.4 360
305708 Ci-MT 8 ø22.0 2.6 400
305709 Ci-MT 9 ø22.0 2.8 440
305710 Ci-MT 10 ø22.0 3.0 480
Markings
Manifold: Fire Eater Logo, Ci-MT##, Serial number, CE1116, 08Arrow for each connection
7/27/2019 305704 Ci MT Manifold
http://slidepdf.com/reader/full/305704-ci-mt-manifold 3/5
Engineering data sheet
Text1
2
3
4
5
6
7
8
9
Vølundsvej 17DK- 3400 HillerødTel +45 7022 2769
Fax +45 7023 2769
Rev: 20.05.09
Product:
Inergen®
Document: 30570# Ci MT Manifold.doc
Chapter: Ci Page: 3 of 5
Sheet No.: 30570# Ci MT Manifold
Id: MK
Ins ta l la t ion
MT1
The orifice in the manifold is calibrated by drilling the hole in accordance with the IMT calculation.
A suitable thread sealant (PTFE tape, yarn or similar) is applied to the thread in accordance with themanufacturer’s recommendations.
The manifold is screwed into the pipe system socket and tightened (50-60 Nm).
MT2-10
The orifice kit is calibrated and installed in accordance with its specification.
The o-ring which comes with the manifold is placed in the grove in the orifice kit.
The manifold is held up to the orifice and the union is screwed onto the manifold and tightened (20-50Nm).It is important to be careful not to soil or damage the o-ring when installing the manifold.
The calibrated orifice kit (manifold adapter) is screwed onto the pipe system.
Operat ing
No operations are necessary.
Maintenance
No requirements.
Rout i ne t est ing
No requirements.
Ci MT 1 Manif o ld
The Ci MT 1 Manifold [305601] does not have a check valve.The orifice is integral to the manifold body.If a check valve is required for the installation, a Ci MT 2 Manifold [305602] can be used, leaving one inletunconnected.
7/27/2019 305704 Ci MT Manifold
http://slidepdf.com/reader/full/305704-ci-mt-manifold 4/5
Engineering data sheet
Text1
2
3
4
5
6
7
8
9
Vølundsvej 17DK- 3400 HillerødTel +45 7022 2769
Fax +45 7023 2769
Rev: 20.05.09
Product:
Inergen®
Document: 30570# Ci MT Manifold.doc
Chapter: Ci Page: 4 of 5
Sheet No.: 30570# Ci MT Manifold
Id: MK
Expl oded view (Ci MT4 Manif o ld shown)
Exp loded v iew (CM MT val ve assembly )
Pos. Item Description
1 212097 O-ring 26 x 1.5
2 212097 O-ring 26 x 1.5
3 305212 SM22 M30 Plug
4 305670 CM MT Valve assembly
5 30568x CM MTx Body (x=2-10)
7/27/2019 305704 Ci MT Manifold
http://slidepdf.com/reader/full/305704-ci-mt-manifold 5/5
Engineering data sheet
Text1
2
3
4
5
6
7
8
9
Vølundsvej 17DK- 3400 HillerødTel +45 7022 2769
Fax +45 7023 2769
Rev: 20.05.09
Product:
Inergen®
Document: 30570# Ci MT Manifold.doc
Chapter: Ci Page: 5 of 5
Sheet No.: 30570# Ci MT Manifold
Id: MK
Declaration of conformity & EC certificate (CPD)
1116
Manufacturer:Fire Eater A/SVølundsvej 14
DK-3400 HillerødDenmark
EN12094-13Check valves and non-return valves
Manifold with build in Check valves
Based upon this certificate of conformity, we declare thatthe combined pressure gauge and pressure switch assemblydesignated above meets the provision of Annex ZA of theEN12094-13 standard.
The device is to be used in conjunction with Fire Eaterequipment.
Certification body for this product isCNPP, B.P. 2265, F-27950 Saint_Marcel, www.cnpp.comCNPP certificate: 1116-CPD-032
Signature: _____________Michael Kroneder, Technical managerDate: 2008-01-17
Recommended